eFlowNA8 Series Installation Guide
NEC Power-Limited Wiring Requirements for eFlowNA8 Models:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit
wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited
circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits.
One such example of this is shown below. Your specific application may require different conduit knockouts to
be used. Any conduit knockouts may be used. For power- limited applications use of conduit is optional. All field
wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute).
Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods.
For Canadian installations use shielded wiring for all connections.
Note:
Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire
(Fig. 4a).
Fig. 4
Fig. 4a
* Outputs are power-limited for eFlow4NA8.
Outputs are non power-limited for
eFlow6NA8, eFlow102NA8, and eFlow104NA8.
Input
120VAC
60Hz
(non power-
limited)
Supervisory Connections
(power-limited)
ACM8
outputs*
Battery
Connections
(non power-limited)
Optional
UL Listed
Battery
Enclosure
(non power-
limited)
External
Jacketed
Shield
Incorrect Wire
Handling
Correct Wire
Handling
Pull back
external jacketed
shield approx. 1/2”.
Wire
Insulation
Solid Copper
Conductors