ALTV2416UL Series
- 3 -
2. Set power switch on power distribution board marked [PD] to OFF position for models ALTV2416ULX or
ALTV2416ULCBX
(Figs. 1, 2, pgs. 4, 5)
. Set power disconnect circuit breaker to OFF position for all
other models
(Figs. 3a-8a, pgs. 6-10).
3. All units are factory set for 24VAC operation.
For 28VAC operation, adjust unit prior to mounting and applying power as follows:
Change the wire position so that the wire marked [28V] is connected to the terminal marked [P] and
the wire marked [24V] is connected to the terminal marked [S]
.
Note: ALTV2416ULCBX set for 28VAC operation is not Class 2 Rated, not power limited.
4. Connect AC power to the black and white flying leads of the transformer(s)
(Figs. 1-8, pgs. 4-10)
.
Use 18 AWG or larger for all power connections.
Keep power limited (PTC protected outputs only) wiring separate from non-power limited wiring.
Minimum .25” spacing must be provided.
Use separate knockouts.
5. Set power switch on power distribution board marked [PD] to ON position for models ALTV2416ULX or
ALTV2416ULCBX
(Figs. 1, 2, pgs. 4, 5)
. Set power disconnect circuit breaker to RESET (ON) position for
all other models
(Figs. 3a-8a, pgs. 6-10).
6. Measure output voltage before connecting devices. This helps avoid potential damage.
Terminals marked [1P - 16P] are of the same polarity.
CAUTION: Determine the maximum operating voltage of the equipment being powered before adjusting
the output voltage.
7.
Set power switch on power distribution board marked [PD] to OFF position for models ALTV2416ULX or
ALTV2416ULCBX
(Figs. 1, 2, pgs. 4, 5)
. Set power disconnect circuit breaker to OFF position for all
other models
(Figs. 3a-8a, pgs. 6-10).
8.
Connect devices to terminals marked [1P - 1N through 8P - 8N] on PD8 board
(Figs. 1-4, pgs. 4-7,
Figs. 7-8, pgs. 9-10),
or terminals marked [1P - 1N through 16P - 16N] on PD16W/PD16WCB board
(Figs. 5-6, pg. 8),
carefully observing polarity.
9. Set power switch on power distribution board marked [PD] to ON position for models ALTV2416ULX or
ALTV2416ULCBX
(Figs. 1, 2, pgs. 4, 5)
. Set power disconnect circuit breaker to RESET (ON) position for
all other models
(Figs. 3a-8a, pgs. 6-10).
10. Green LED will illuminate when power is present.
11. Upon completion of wiring, secure enclosure door with screws (supplied). Installation of cam lock is optional.
Caution: Equipment to be installed/serviced by authorized/trained personnel only.
Shut branch circuit power before installing/servicing equipment.
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
This installation should be made by qualified service personnel and should conform to all local codes and in
accordance with the National Electrical Code. Use 75º C or higher rated UL insulated wiring for connecting the
unit to the mains. Replace fuses only with the same type and rating
(refer to Sixteen (16) Output ALTV2416UL
Reference Chart, pg. 2).
Terminal Identification:
PD8 - Power Distribution Module
Terminal Legend
Function/Description
1P - 8P
AC output.
1N - 8N
AC output.
PD16W - Power Distribution Module
Terminal Legend
Function/Description
1P - 16P
AC output.
1N - 16N
AC output.