AL602ADA220 Installation Guide
- 3 -
Power Supply Specifications:
AC Input:
Nominal 220VAC (working range 198VAC - 256VAC), 60Hz, 1.2A.
Output:
Four (4) regulated supervised NAC output circuits, 24VDC, 2.5A maximum current.
One (1) aux. special application 24VDC power output circuit 1A, non-supervised
total output current must not exceed current 6.5A in Alarm Condition.
Battery
Use two (2) 12VDC / 7AH, two (2) 12VDC / 12AH or two (2) 12VDC / 40AH
batteries connected in series.
Stand-by/Alarm
Current Consumption:
90mA/175mA
EOL Resistor (end of line):
2.2K (2200 Ohm), Altronix Model # AL-EOL22 (included).
Ground fault maximum
test impedance:
1000 Ohm.
Stand-by Specifications:
Stand-by Batteries
Stand-by Time Total
(A/Minutes)
Alarm Output
Current
Aux. Output
24VDC/7AH
24 Hours
6.5A/5 minutes
–
24VDC/12AH (use two 12VDC batteries in series)
24 Hours
6.5A/5 minutes
50mA
24VDC/40AH
24 Hours
6.5A/5 minutes
1A
Note: Unit is equipped with 1A max. auxiliary output: “AUX” will remain battery backed up during
power outage. For loads connected to “AUX” please refer to battery “Stand-by Specifications” above
for ratings. When loads are connected to “AUX” output during alarm condition, the remaining outputs
may not exceed 6.5A total alarm current (example: AUX = 1A, outputs up to 5.5A).
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all
local codes and authorities having jurisdiction.
PRODUCT IS INTENDED FOR INDOOR DRY USE ONLY.
Carefully review:
Application Guide for AL602ADA220, AL802ADA220, AL1002ADA220
Power Supply Specifications
(pg. 3)
Stand-by Specifications
(pg. 3)
Output Programming Selection Table
(pg. 4)
Sync Mode Selection Table
(pg. 4)
Terminal Identification Table
(pgs. 5-6)
LED Status Indication Table
(pg. 6)
1. Mount the unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes
in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place
the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower
two holes. Remove the enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper
keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws
(Enclosure Dimensions, pg. 12)
. Secure enclosure to earth ground
(Fig. 1, pg. 3).
Small terminal block wire
gauges range from 16 AWG to 24 AWG, all others range from 14 AWG to 24 AWG.
2. Connect the line (L) and neutral (N) terminals to a separate unswitched AC circuit (220VAC, 60Hz)
dedicated to the Fire Alarm System. Secure ground wire lead to ground lug.
3. Measure output voltage before connecting devices. This helps avoiding potential damage.
4. Connect battery to the terminals marked [+ BAT –] on the Power Supply Board (battery leads included).
Use two (2) 12VDC batteries connected in series.
5. Set output selection switches marked [OUT1 through OUT4] to follow corresponding input [IN1 and IN2]
and desired output signal type
(Output Programming Selection Table, pg. 4).
6. Connect FACP output to the desired AL800LGK9E logic board inputs, and notification appliances to the
desired AL800LGK9E logic board outputs
(see 02 Application Guide).
Fig. 1
L N
Line
Neutral
Ground Lug