AL602ADA220 Installation Guide 

- 3 -

Power Supply Specifications:

AC Input:

Nominal 220VAC (working range 198VAC - 256VAC), 60Hz, 1.2A.

Output:

Four (4) regulated supervised NAC output circuits, 24VDC, 2.5A maximum current. 

One (1) aux. special application 24VDC power output circuit 1A, non-supervised 

total output current must not exceed current 6.5A in Alarm Condition.

Battery

Use two (2) 12VDC / 7AH, two (2) 12VDC / 12AH or two (2) 12VDC / 40AH

batteries connected in series.

Stand-by/Alarm

Current Consumption:

90mA/175mA

EOL Resistor (end of line):

2.2K (2200 Ohm), Altronix Model # AL-EOL22 (included).

Ground fault maximum

test impedance:

1000 Ohm.

Stand-by Specifications:

Stand-by  Batteries  

Stand-by Time Total

(A/Minutes)

Alarm Output 

Current

Aux. Output

24VDC/7AH

24 Hours

6.5A/5 minutes

24VDC/12AH (use two 12VDC batteries in series)

24 Hours

6.5A/5 minutes

50mA

24VDC/40AH

24 Hours

6.5A/5 minutes

1A

Note: Unit is equipped with 1A max. auxiliary output: “AUX” will remain battery backed up during 

power outage. For loads connected to “AUX” please refer to battery “Stand-by Specifications” above 

for ratings. When loads are connected to “AUX” output during alarm condition, the remaining outputs 

may not exceed 6.5A total alarm current (example: AUX = 1A, outputs up to 5.5A).

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all 

local codes and authorities having jurisdiction.

PRODUCT IS INTENDED FOR INDOOR DRY USE ONLY. 

 

Carefully review:

  Application Guide for AL602ADA220, AL802ADA220, AL1002ADA220

  Power Supply Specifications 

(pg. 3)

  Stand-by Specifications 

(pg. 3)

  Output Programming Selection Table 

(pg. 4)

  Sync Mode Selection Table 

(pg. 4)

  Terminal Identification Table 

(pgs. 5-6)

  LED Status Indication Table 

(pg. 6)

1. Mount the unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes 

  in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place 

  the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower 

  two holes. Remove the enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper 

  keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 

 

(Enclosure Dimensions, pg. 12)

. Secure enclosure to earth ground 

(Fig. 1, pg. 3). 

Small terminal block wire 

  gauges range from 16 AWG to 24 AWG, all others range from 14 AWG to 24 AWG.

2. Connect the line (L) and neutral (N) terminals to a separate unswitched AC circuit (220VAC, 60Hz)

  dedicated to the Fire Alarm System. Secure ground wire lead to ground lug.

3. Measure output voltage before connecting devices. This helps avoiding potential damage.

4. Connect battery to the terminals marked [+ BAT –] on the Power Supply Board (battery leads included). 

  Use two (2) 12VDC batteries connected in series. 

5. Set output selection switches marked [OUT1 through OUT4] to follow corresponding input [IN1 and IN2] 

  and desired output signal type

 (Output Programming Selection Table, pg. 4).

6. Connect FACP output to the desired AL800LGK9E logic board inputs, and notification appliances to the 

  desired  AL800LGK9E logic board outputs 

(see 02 Application Guide).

Fig. 1

L       N

Line

Neutral

Ground Lug

Содержание AL602ADA220

Страница 1: ...ee Application Guide for additional information Rev 030320 More than just power TM Installing Company ________________ Service Rep Name ___________________________________ Address ______________________________________________ Phone ___________________ ...

Страница 2: ...ersonnel and should conform to all local codes Input Nominal 220VAC working range 198 256VAC 60Hz 1 2A Two 2 Class A or two 2 Class B FACP inputs Two 2 NC dry contact trigger inputs Output 24VDC 6 5A max total alarm current 2 5A max current per output Separate 1 0A auxiliary output Programmable supervised indicating circuit outputs Four 4 Class B or two 2 Class A or One 1 Class A and Two 2 Class B...

Страница 3: ...02ADA220 AL1002ADA220 Power Supply Specifications pg 3 Stand by Specifications pg 3 Output Programming Selection Table pg 4 Sync Mode Selection Table pg 4 Terminal Identification Table pgs 5 6 LED Status Indication Table pg 6 1 Mount the unit in the desired location Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure Install two upper fasteners and screws in t...

Страница 4: ...connected Sync Mode Selection Table Function Switch Positions Descriptions ON OFF Amseco Sync Mode 1 3 4 2 This mode is designed to work with the Amseco series of horns strobes and horn strobes to provide a means of synchronizing the Temporal coded horns synchronizing the flash timing of the strobe and silencing the horns of the horn strobe combination over a two wire circuit while leaving strobes...

Страница 5: ...puts are set by output switches OUT1 through OUT4 Output Programming Selection Table pg 4 Note these inputs are unidirectional and will not report a trouble condition to the FACP OUT1 OUT2 OUT3 OUT4 Supervised Notification appliances are connected to these regulated outputs see 02 Application Guide pg 2 4 Each power limited output will supply 2 5A Total supply current is 6 5A see note below Output...

Страница 6: ...s Low battery condition will report at approximately 21VDC Battery presence detection will report with in 180 seconds after battery remains undetected missing or removed A restored battery will report within 30 seconds LED Diagnostics AL600ADA Power Supply Board Red DC Green AC Power Supply Status ON ON Normal operating condition ON OFF Loss of AC Stand by battery is supplying power OFF ON No DC o...

Страница 7: ...larm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA C Notification Appliances Current must not exceed 6 5A 6500mA 0mA mA D Total alarm current mA mA E Total current ratings converted to amperes line D x 0 001 A A F Number of standby hours 24 for NFPA 72 Chapter 1 1 5 2 5 H G Multiply lines E and F Total stand by AH AH H Alarm sounding period in hours For example 5 minutes 0 0833 hours H...

Страница 8: ... a simultaneous trouble condition to the FACP s IN1 and IN2 Non Supervised Class E AC Local Power limited Fig 2a DC OUT1 OUT2 OUT3 OUT INP1 INP2 F OUT1 OUT3 OUT2 OUT4 INPUT SELECT TEMPORAL STROBE SYNC IN OUT SYNC INPUT SELECT TEMPORAL STROBE SYNC IN OUT SYNC AUX line neutral RESET Unswitched 220VAC power mains non power limited 5A 250V Use separate knockout Keep 0 25 spacin non power limited wirin...

Страница 9: ... C should connect to the host control panel for local annunciation of the trouble condition Note If common trouble input terminals marked C FAULT NC are not used these terminals must be shorted connect jumper to remain inactive For optional hookups see Fig 2b Maintenance Unit should be tested at least once a year for the proper operation as follows Output Voltage Test Under normal load conditions ...

Страница 10: ...ystem Sensor 2112 24AITR Photoelectric 0 50 60 70 System Sensor 2112 24 D Photoelectric 0 05 50 System Sensor 2112 24R Photoelectric 0 50 60 70 System Sensor 2112 24TR Photoelectric 0 50 60 70 System Sensor 2112 24T D Photoelectric w 135 o Thermal 0 05 50 System Sensor 2112 24TSRB Photoelectric w 135 o Thermal Supervisory Relay 15 45 System Sensor 2312 24TB Photoelectric 0 12 50 System Sensor 2412...

Страница 11: ...ount 96 Rixon Firemark FM 980 Floor Mount single 68 Rixon Firemark FM 996 Surface Wiring 68 Rixon Firemark FM 998 Concealed Wiring 68 A 3 Relays Table A 3 below lists relays compatible with AL602ADA220 AUX output and Outputs 1 8 when programmed as AUX Manufacturer Model Current mA Manufacturer Model Current mA System Sensor PR 1 15 System Sensor R 20T 40 PR 2 30 R 24T 40 PR 3 30 R 10E 23 EOLR 1 30...

Страница 12: ...25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm 2 0 50 8mm 2 0 50 8mm 1 25 31 8mm 1 25 31 8mm Enclosure Dimensions 15 5 x 12 x 4 5 393 7mm x 304 8mm x 114 3mm Altronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail in...

Отзывы: