• AC Fail condition will report approximately one (1) minute after loss of AC. To delay report for 6 hours cut 

jumper J1 on the Power Supply Board (AC trouble output delay option). If this mode is selected the Power Supply 
Board must be reset by removing all power to it for 30 seconds.

• Low battery condition will report at approximately 21VDC (24VDC output setting) or approximately 10.5VDC 

(12VDC output setting).

• Battery presence detection will report approximately 5 minutes after battery remains undetected (missing or removed).

Input / Output Selection Table:

AL600LGK Logic Board

Switch

Input 1

Input 2

OUT 1

Closed

Open

OUT 2

Closed

Open

OUT 3

Closed

Open

OUT 4

Closed

Open 

Note: Switch positions determine which outputs will trigger from either Input 1 or Input 2.

LED Status Indication Table:

LED

OFF

ON

BLINK (LONG)*

BLINK (SHORT)**

Out 1

Normal

Alarm Condition

Trouble Condition

Trouble Condition Memory

Out 2

Normal

Alarm Condition

Trouble Condition

Trouble Condition Memory

Out 3

Normal

Alarm Condition

Trouble Condition

Trouble Condition Memory

Out 4

Normal

Alarm Condition

Trouble Condition

Trouble Condition Memory

Input 1

Normal

Alarm Condition

Trouble Condition

---

Input 2

Normal

Alarm Condition

Trouble Condition

---

Fault

Normal

System Trouble

---

---

AC

AC Loss

AC present

---

---

DC

No DC Output

DC present

---

---

*

Indicates trouble condition. When trouble (open, short or ground) occurs on a specific output, the
corresponding red output LED, (OUT1-OUT4) will blink. The corresponding green input LED will
blink as well.

**

Indicates trouble condition memory. When a trouble condition restores, the units red output LED,
(OUT1-OUT4) will blink with a shorter and distinctly different duration. The green input LED(s) will be
off (normal condition). To reset the memory remove and restore AC and battery power to the unit.
The LED(s) will extinguish.

Note: If indicating circuits have been restored, memory reset is not required for normal operation
of the unit.

OPEN SWITCH

CLOSED SWITCH

Switch Detail

- 4 -

Содержание AL600ULADA

Страница 1: ...Rev 122000 AL600ULADA NAC Power Extender Installation Guide...

Страница 2: ...4 outputs Specifications AL600ULADA NAC Power Extender Agency Listings UL Listed for Control Units and Accessories for Fire Alarm Systems UL 864 and UL Listed Standard for Safety for Fire Protective S...

Страница 3: ...limited wiring separate from non power limited wiring 115VAC 60Hz Input Battery Wires Minimum 25 spacing must be provided 3 Set switch SW1 on Power Supply Board for desired output voltage Open for 24...

Страница 4: ...Condition Memory Out 2 Normal Alarm Condition Trouble Condition Trouble Condition Memory Out 3 Normal Alarm Condition Trouble Condition Trouble Condition Memory Out 4 Normal Alarm Condition Trouble C...

Страница 5: ...esignated input 1 IN1 or input 2 IN2 Input Output Selection Table pg 4 C FAULT N C An open circuit across this pair of terminals will cause IN1 and IN2 to simultaneously Common signal a trouble condit...

Страница 6: ...ng output switches must be set to follow the same input Install two 2 2 2K ohm EOL resistors in parallel across the last notification appliance Note Paralleled output circuit configuration is non powe...

Страница 7: ...W1 CLOSED 12V DC AC RL2 RL3 RLY1 PTC2 AC TROUBLE DELAY OPTION J2 IC3 IC2 AC FAIL NC C NO BAT FAIL NC C NO XFMR These circuits are used to monitor AC and Bat Fail and will cause a simultaneous trouble...

Страница 8: ...t the battery is fully charged Check specified voltage both at battery terminal and at the board terminals marked BAT to insure there is no break in the battery connection wires Note Maximum charging...

Отзывы: