Power Supply Specifications:

AC Input:

115VAC / 3.2 amp @ 60Hz

Output:

12VDC - 24VDC. Maximum 2.0 amp per output.
Total of 6.5 amp in Alarm Condition.

Battery:

For 12VDC operation use a 12VDC / 12AH battery
For 24VDC operation use two (2) 12VDC / 12AH batteries connected in series

Stand-by Current:

75mA

EOL Resistor:

2.2K (2200 ohm)

(end of line)

Stand-by Specifications:

Stand-by Batteries

Stand-by Time

Alarm Output

Aux Output

Total Amp/Minutes

Current

24VDC/12AH

24 Hours

6.5 Amp/15 Minutes

50mA

(use two (2) 12VDC batteries in series)

60 Hours

6.5 Amp/5 Minutes

-

12VDC/12AH

24 Hours

6.5 Amp/15 Minutes

50mA

60 Hours

6.5 Amp/5 Minutes

-

24VDC/7AH

24 Hours

6.5 Amp/5 Minutes

-

Installation Instructions:

The AL600ULADA should be installed in accordance with article 760 of The National Electrical Code as well as 
NFPA 72 and all applicable Local Codes.
1. Mount the AL600ULADA in a desired location. It is recommended to first review the following tables for screw 

terminals, switch selection and LED status indications. This will greatly facilitate installation hook-up. 
Carefully review:
Power Supply Specifications 

(pg. 3)

Stand-by Specifications 

(pg. 3)

Input / Output Selection Table

(pg. 4)

LED Status Indication Table

(pg. 4)

Terminal Identification Table

(pg. 5)

Typical Application Diagrams

(pg. 6)

2. Connect the black and white transformer leads of AL600ULADA to a separate 

unswitched AC circuit (115VAC, 60Hz) dedicated to the 
Fire Alarm System (Fig. 1, pg. 3).  Connect green lead to earth ground.
Keep power limited wiring separate from non-power limited wiring 
(115VAC / 60Hz Input, Battery Wires). Minimum .25” spacing must be provided.

3. Set switch SW1 on Power Supply Board for desired output voltage. Open for 24VDC 

(factory set), Close for 12VDC.

4. Measure output voltage before connecting devices. This helps avoid potential damage.
5. Connect battery to terminals marked [+ BAT --] on the Power Supply Board 

(battery leads included). Use two (2) 12VDC batteries connected in series for 24VDC operation.

6. Set output selection switches marked (OUT1 through OUT4) to follow corresponding input (IN1 & IN2) 

(Input/Output Selection Table pg. 4).

7. Connect FACP output to desired AL600LGK logic board inputs and notification appliances to desired  AL600LGK 

logic board outputs (Typical Application Diagrams pg. 6).

8. For connection of smoke detectors, digital dialer (Optional Hookup Diagram pg. 7).
9. To disable ground fault detection install insulating washer between the board and standoff (Fig. 4B/4C, pg. 7).

General Information:

• For all Class B hookups SW1 & SW2 on the AL600LGK logic board must be open.

For all Class A hookups SW1 & SW2 on the AL600LGK logic board must be closed.

AC

AL601ULB

AC

AC

+

BAT --- 

OPEN = 24V SW1 CLOSED = 12V

DC

RL2

RL3

RLY1

POWER SUPPLY

ALTRONIX CORP.

PTC2

AC

TROUBLE

DELAY

OPTION

J2

IC3

IC2

AC

FA

IL

NC

C

NO

BAT

F

AIL

NC

C

NO

XFMR

Green 

Lead

(ground)

AL600LGK

ALTRONIX CORP.
BKLYN, NY 11220

SW1

--

  DC  

+

SW2

+ OUT1 --- 

+ OUT2 --- 

+ OUT3 --- 

+ OUT4 --- 

OUT1  OUT2  OUT3  OUT4

INP1  INP2  

FAULT

--- AUX  +

NO  REMOTE C

NC

C

NO

C

"FAULT"

NC

AUX
RESET

OUT1

OUT3

CLOSED - INP1

OPEN - INP2

OUT2

OUT4

CLOSED - INP1

OPEN - INP2

LOWER TERMINALS

IN1+

UPPER TERMINALS

Black

Lead

White

Lead

115 VAC input

60 Hz,

3.2 amp 

+

DC  

--

 

IN1--

IN2+ IN2--

RET1+ RET1-- RET2+ RET2--

Fig. 1

- 3 -

Содержание AL600ULADA

Страница 1: ...Rev 122000 AL600ULADA NAC Power Extender Installation Guide...

Страница 2: ...4 outputs Specifications AL600ULADA NAC Power Extender Agency Listings UL Listed for Control Units and Accessories for Fire Alarm Systems UL 864 and UL Listed Standard for Safety for Fire Protective S...

Страница 3: ...limited wiring separate from non power limited wiring 115VAC 60Hz Input Battery Wires Minimum 25 spacing must be provided 3 Set switch SW1 on Power Supply Board for desired output voltage Open for 24...

Страница 4: ...Condition Memory Out 2 Normal Alarm Condition Trouble Condition Trouble Condition Memory Out 3 Normal Alarm Condition Trouble Condition Trouble Condition Memory Out 4 Normal Alarm Condition Trouble C...

Страница 5: ...esignated input 1 IN1 or input 2 IN2 Input Output Selection Table pg 4 C FAULT N C An open circuit across this pair of terminals will cause IN1 and IN2 to simultaneously Common signal a trouble condit...

Страница 6: ...ng output switches must be set to follow the same input Install two 2 2 2K ohm EOL resistors in parallel across the last notification appliance Note Paralleled output circuit configuration is non powe...

Страница 7: ...W1 CLOSED 12V DC AC RL2 RL3 RLY1 PTC2 AC TROUBLE DELAY OPTION J2 IC3 IC2 AC FAIL NC C NO BAT FAIL NC C NO XFMR These circuits are used to monitor AC and Bat Fail and will cause a simultaneous trouble...

Страница 8: ...t the battery is fully charged Check specified voltage both at battery terminal and at the board terminals marked BAT to insure there is no break in the battery connection wires Note Maximum charging...

Отзывы: