4.  Connect 5VDC devices to be powered at 5VDC to the terminals marked [+ 5VDC -- ]
5. Connect 12VDC devices to be powered at 12VDC to the terminals marked [+ 12VDC -- ]. 
6. Connect 24VDC devices to be powered at 24VDC to the terminals marked [+ 24VDC -- ]. 
7.  Connect two (2) 12V Stand-by batteries. 

Note: For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in 
the loss of output voltage. Batteries must be lead acid or gel type if used. Two (2) 12V Stand-by batteries 
connected in series to the terminals marked [+ BAT -- ] (Fig. 1 , pg. 3)

8.  It is required to connect supervisory trouble reporting devices to outputs marked [AC FAIL, LOW BAT] (Fig. 1, pg. 3)

Use 22 AWG to 18 AWG for AC Fail & Low Battery reporting. AC Failure will report in 5 minutes. 
Note: When used in fire alarm or access control applications, “AC Fail” relay should be utilized to visually indicate 
that AC power is on.  To delay report for 6 hours cut “AC Delay” jumper (Fig. 1a, pg. 3)

9. Please ensure that the cover is secured with the provided Key Lock. 

Fig. 1 

CAUTION: De-energize unit prior to servicing. For continued protection against risk of electric shock and fire hazard 

replace fuse with the same type and rating.  Do not expose to rain or moisture. 

+

 DC  ---

NC 


NO 

NC 

NO 

 BAT  ---

AC 

DC 

Bat 

Risk of Fire,

Replace Fuses

As Marked 

Opened - 24V

Closed - 12V 

AC Fail

Bat Fail 

J1 

SW1 

5A 
250V 

15A 

250V 

AC Delay 

15

 

Wire Strap 

(from 

Enclosure 

to Door) 

+ 12VDC 

--­

+ 5VDC 

--­

+ 24VDC 

--­

+ INPUT1 

--­

24VDC output 

is non 

power-limited 

5VDC and 

12VDC outputs 

are power-limited 

Battery 

connection 

(non power-limited) 

(non power-limited) 

(non 

power­

limited) 

Earth

 

Ground

 

CAUTION: Optional rechargeable stand-by batteries must match the power supply 

output voltage setting. 

Optional Rechargeable 

Stand-by Battery 

Optional Rechargeable 

Stand-by Battery 

Battery and 

AC Supervision 

Circuit 

(power-limited) 

J1 

AC Delay 

Fig. 1a 

Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing. 

AL600UL3/AL600UL3X 

- 3 ­

                    Available from A1 Security Cameras 

    www.a1securitycameras.com email: [email protected]

Содержание AL600UL3

Страница 1: ...stallation Guide For a red enclosure add an R suffix to the part e g AL600UL3R Altronix Corp 140 58th St Brooklyn NY LISTED SECURITY SIGNALING LISTED Available from A1 Security Cameras www a1securityc...

Страница 2: ...d by 5 Minutes of Alarm 60 hr of Stand by 5 Minutes of Alarm 5VDC 1 75 amp 5VDC 0 3 amp 5VDC 0 1 amp 24VDC 40AH Battery 12VDC 1 75 amp 12VDC 0 3 amp 12VDC 0 1 amp 24VDC 3 amp 24VDC 0 3 amp 24VDC 0 1 a...

Страница 3: ...t AC Delay jumper Fig 1a pg 3 9 Please ensure that the cover is secured with the provided Key Lock Fig 1 CAUTION De energize unit prior to servicing For continued protection against risk of electric s...

Страница 4: ...d Bat Battery Status ON Normal operating condition OFF Battery fail low battery Terminal Identification AL600ULXB Power Supply Charger Terminal Legend Function Description L G N 115VAC 60 Hz DC 24VDC...

Страница 5: ...0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 39 2W MOD Loop Test Maintenance Mod 30 50 4W B 12 24 volt Pho...

Страница 6: ...Notes 6 AL600UL3 AL600UL3X Available from A1 Security Cameras www a1securitycameras com email sales a1securitycameras com...

Страница 7: ...30mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm 3 25 83mm 3 25 83mm 1 0 25mm 1 0 10 5 1 0 1 0 25mm 0 75 19mm 0 75 19mm 0 9375 24mm 0 9375 24mm 11 0...

Страница 8: ...14mm 0 91 23 114mm 1 375 34 925mm 1 125 28 575mm 15 5 393 7mm 4 615 117 22mm 12 23 310 64mm 4 615 117 22mm 1 5 1 5 4 615 4 615 1 25 38 1mm 117 22mm 117 22mm 38 1mm Altronix is not responsible for any...

Отзывы: