AL400ULX series 

- 3 - 

Power

Distribution

Module(s)

 

+

  DC  --- 

 

NC    C   NO     NC   C     NO

 

 BAT  --- 

 

AC

DC

Bat

Risk of Fir

e,

Replace Fuses

As Marked

AC Fail

Bat Fail

J1

SW1

5A  250V

15A  250V

AC Delay

15

N

Door

CAUTION: De-energize unit prior to servicing. For continued protection against risk
of electric shock and fire hazard replace fuse with the same type and rating.
Do not expose to rain or moisture.

Green

Lead

Battery connection (non power limited)

Switch Position:
24VDC = SW1 OFF
12VDC = SW1 ON

Wire 

Strap

(from

Enclosure

to Door)

115VAC 

power mains

non-power 

limited

 

 

Battery & AC

Supervision

Circuit

(power limited)

Class 1

-

Divider

power limited

For 12VDC Operation

use hook-up in the

inset on the right

CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC

stand-by battery.

Keep power limited wiring separate from non-power limited. Use minimum 0.25" spacing.

12VDC Rechargeable Battery

(optional)

12VDC Rechargeable Battery

(optional)

SW1

Battery & AC Supervision

Circuit

(power-limited)

NC    C   NO     NC   C     NO AC Fail

Bat Fail

J1

AC Delay

OFF - 24V

ON - 12V

ON

1

OFF - 24V

ON - 12

V

ON

1

Stand-by Specifications 

(total current shown)

:

Output

4 hr. of Stand-by and

5 Minutes of Alarm

24 hr. of Stand-by and

5 Minutes of Alarm

60 hr. of Stand-by and

5 Minutes of Alarm

12VDC / 40AH Battery

Stand-by = 4.0A

Alarm = 4.0A

Stand-by = 1.0A

Alarm = 4.0A

Stand-by = 300mA

Alarm = 4.0A

24VDC / 12AH Battery

--------

Stand-by = 200mA

Alarm = 3.0A

--------

24VDC / 40AH Battery

Stand-by = 3.0A

Alarm = 3.0A

Stand-by = 1.0A

Alarm = 3.0A

Stand-by = 300mA

Alarm = 3.0A

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local 

codes and authorities having jurisdiction. Product is intended for indoor use only. 

1.  Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the

 

enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s

 

upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the

 

enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper keyholes over the two

 

upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 7-8).

Fig. 1

Fig. 1a

Fig. 1b

Fig. 1c

Содержание AL400ULPD4

Страница 1: ...0ULX Single Output AL400ULPD4 AL400ULPD4CB Four 4 Fused Outputs Four 4 PTC Outputs AL400ULPD8 AL400ULPD8CB Eight 8 Fused Outputs Eight 8 PTC Outputs AL400ULXPD16 AL400ULXPD16CB Sixteen 16 Fused Outputs Sixteen 16 PTC Outputs For a red enclosure add an R suffix to the part e g AL400ULPD8R ...

Страница 2: ...50V 15A 32V AL400ULPD4CB PD4ULCB x 2 5 AL400ULPD8 PD8UL 8 x 3 5 5A 250V 15A 32V AL400ULPD8CB PD8ULCB x 2 5 AL400ULXPD16 Two 2 PD8UL 16 x 3 5 5A 250V 15A 32V AL400ULXPD16CB Two 2 PD8ULCB x 2 5 Do not exceed total output rating of 4A 12VDC or 3A 24VDC per unit Specifications Power Supply Output Specifications Output Switch Position 12VDC SW1 ON Fig 1c 24VDC SW1 OFF Fig 1c Input Input 115VAC 60Hz 3 5...

Страница 3: ...F 24V ON 12V ON 1 Stand by Specifications total current shown Output 4 hr of Stand by and 5 Minutes of Alarm 24 hr of Stand by and 5 Minutes of Alarm 60 hr of Stand by and 5 Minutes of Alarm 12VDC 40AH Battery Stand by 4 0A Alarm 4 0A Stand by 1 0A Alarm 4 0A Stand by 300mA Alarm 4 0A 24VDC 12AH Battery Stand by 200mA Alarm 3 0A 24VDC 40AH Battery Stand by 3 0A Alarm 3 0A Stand by 1 0A Alarm 3 0A ...

Страница 4: ...pplications batteries are optional When batteries are not used a loss of AC will result in the loss of output voltage When the use of stand by batteries is desired they must be lead acid or gel type 7 Connect appropriate signaling notification devices to AC FAIL BAT FAIL Fig 1a pg 3 supervisory relay outputs Note When used in fire alarm burglar alarm or access control applications AC Fail relay sh...

Страница 5: ...Legend PD4UL PD4ULCB Terminal Legend PD8UL PD8ULCB Function Description 1P to 4P 1P to 8P Positive DC power outputs 1N to 4N 1N to 8N Negative DC power outputs Power Distribution Module s LED F1 F2 F3 F4 1P 1N 2P 2N 3P 3N 4P 4N DC Output to devices 1P 4P Power Outputs 1N 4N Common Outputs From Power Supply Board Factory Installed Replace fuses with the same type and rating 3 5A 250V Fig 2a Fig 3a ...

Страница 6: ...135o Thermal Supervisory Relay 15 45 2312 24TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 39 2W MOD Loop Test Maintenance Mod 30 50 4W B 12 24 volt Photoelectric I3 0 05 23 4WT B 12 24 volt Photoelectric I3 w Therm 0 05 23 4WTA B 12 24 volt I3 Photo w Therm Sounder 0 05 35 4WTR B 12 24 vol...

Страница 7: ... 342 9mm x 330 2mm x 82 55mm 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm 3 25 83mm 3 25 83mm 1 0 25mm 1 0 25mm 10 5 267mm 1 0 25mm 1 0 25mm 0 75 19mm 0 75 19mm 0 9375 24mm 0 9375 24mm 11 0 279mm 12 5 318mm ...

Страница 8: ...4 AL400ULXPD4CB AL400ULXPD8 AL400ULXPD8CB AL400ULXPD16 AL400ULXPD16CB 15 5 x 12 x 4 5 393 7mm x 304 8mm x 114 3mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 1 5 38 1mm 2 0 50 8mm 2 0 50 8mm 1 75 44 45mm 1 75 44 45mm 4 5 114 3mm 1 25 31 75mm 4 5 114 3mm 1 25 31 75mm 1 25 31 75mm 1 25 31 75mm 1 1 27 94mm 1 1 27 94mm 0 79 20 06mm 1 1 27 94mm 0 91 23 114mm 0 91 23 114mm 1 375 34 925mm 1 ...

Отзывы: