background image

4.  Connect devices to be powered to the terminals marked

  [+ DC – ] (Fig. 1)

5.  Measure output voltage before connecting devices. 

  This helps avoiding potential damage.

6.  For Access Control applications batteries are optional.  

  When batteries are not used, a loss of AC will result in the  

  loss of output voltage. When the use of stand-by batteries 

  is desired, they must be lead acid or gel type. 

  Connect battery to the terminals [– BAT +] (Fig. 1) as 

  marked on the unit (battery leads included). 

  Use two (2) 12VDC batteries connected in series for   

  24VDC operation.

7.  Connect supervisory trouble reporting devices to the

  outputs marked [LOW BAT, AC FAIL] supervisory relays  

  marked [NC, NO, C ] (Fig. 1). 
  
Use 22 AWG to 18 AWG for AC Fail and Low Battery reporting. 

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper voltage level 

(Power Supply Output Specifications Table).

Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage both 

at the battery terminal and at the board terminals marked [- BAT +] to ensure that there is no break in the battery 

connection wires.

Note: Maximum charging current under discharges is 1.25 amp.

Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed.

LED Diagnostics:

LED

ON

OFF

AC (Green)

Normal operation

No AC input

BAT (Red)

Battery connected

Battery disconnected

DC (Red)

Normal operation

No DC output

Terminal Identification:

Terminal Legend

Function/Description

AC, AC

Low voltage (28VAC) transformer connections.

+ DC –

12VDC @ 4 amp or 24VDC @ 3 amp continuous power-limited output.

AC Fail

NC, NO, C

Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally ener-

gized when AC power is present. Contact rating 1 amp @ 30VDC. 

Bat Fail

NC, C, NO

Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC 

power is present. Contact rating 1 amp @ 30VDC.

--  BAT +

Stand-by battery connections. Maximum charge current 1.2 amp.

+   DC   --

AC FAIL   NC    NO     C     NC    C    NO   LOW BAT

-- 

BA

T  

+

DC

AC

1

  

2

  

3

  

4

ON

AC   AC

24V - SW1, 2 OFF

SW3, 4 ON

12V - SW1, 2 ON

SW3, 4 OFF

Fig. 1

Altronix is not responsible for any typographical errors. 

140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: [email protected]. Lifetime Warranty, Made in U.S.A.
IIAL400ULB - Rev. 061400 

H12N

MEMBER

Отзывы: