- 2 -
AL400UL3 / AL400UL3X Installation Guide
Overview:
Altronix AL400UL3/AL400UL3X multi-output power supply/charger is specifically designed for use with access
control, burglar alarm, fire and nurse call systems and accessories. AL400UL3/AL400UL3X converts a 115VAC
60Hz input into three (3) individual power-limited outputs (see specifications).
Features:
Agency Listings:
• UL Listed:
UL294*
Access Control Systems
UL603
Power Supplies for use with
Burglar-Alarm Systems,
UL1069
Hospital Signaling and
Nurse Call Equipment,
UL1481
Power Supplies for Fire
Protective Signaling Systems.
• cUL Listed:
CSA Standard C22.2 No.205-M1983,
Signal Equipment.
•
MEA
- NYC Department of Buildings Approved.
• CSFM
- California State Fire Marshal Approved.
• NFPA 72 Compliant
(Fire-Protective Signaling Service).
Input:
• Input 115VAC, 60Hz, 3.5A.
• Input fuse rated @ 5A/250V.
Output:
• Class 2 Rated power-limited auto-resettable output(s).
• 1.75A continuous supply current at 5VDC.
• 1.75A continuous supply current at 12VDC.
• 1.5A continuous supply current at 24VDC.
Burglar Alarm Applications (UL 603):
12VDC = 10VDC-13.2VDC.
24VDC = 20VDC-26.4VDC.
• 100 mV p/p output ripple.
• Output fuse rated @ 15A/32V.
• Filtered and electronically regulated output(s).
• Short circuit and thermal overload protection.
LED Indicators:
• AC input, DC output and Battery LED indicators.
Battery Backup:
• Built-in charger for sealed lead acid or
gel type batteries.
• Automatic switch over to stand-by battery
when AC fails.
• Maximum charge current 0.7A.
• Zero voltage drop when switched over to
battery backup.
Supervision:
• AC fail supervision (form “C” contacts).
• Low battery and battery presence supervision
(form “C” contacts).
Additional Features:
• Power supply, enclosure, cam lock and battery leads.
Enclosure Dimensions
(H x W x D)
:
AL400UL3:
13.5” x 13” x 3.25”
(342.9mm x 330.2mm x 82.6mm).
Accommodates up to two (2)
12VDC/7AH batteries.
AL400UL3X:
15.5” x 12” x 4.5”
(393.7mm x 304.8mm x 114.3mm).
Accommodates up to two (2)
12VDC/12AH batteries.
*Access Control Performance Levels:
Destructive Attack - I; Endurance - IV; Line Security - I; Stand-by Power - II.
Stand-by Specifications
(total current shown)**
:
Battery
30 Minutes of Alarm
(for Access Control)
4 hr. of Stand-by and
5 Minutes of Alarm
24 hr. of Stand-by and
5 Minutes of Alarm
60 hr. of Stand-by and
5 Minutes of Alarm
7AH
Stand-by = 3.0A
Alarm = 3.0A
–
–
–
12AH
–
–
Stand-by = 200mA
Alarm = 3.0A
–
40AH
–
Stand-by = 3.0A
Alarm = 3.0A
Stand-by = 1.0A
Alarm = 3.0A
Stand-by = 300mA
Alarm = 3.0A
** Current is measured between power supply and ALX3B board.