- 6 -
AL300X220 Series
Wiring:
Use 14 AWG or larger for all power connections.
Note:
Take care to keep power-limited circuits separate from non power-limited wiring (220VAC, Battery).
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test:
Under normal load conditions the DC output voltage should be checked for proper
voltage level
(
Power Supply Voltage Output Specifications Chart
, pg. 3).
Battery Test:
Under normal load conditions check that the battery is fully charged, check specified
voltage both at the battery terminal and at the board terminals marked [+ BAT –] to
ensure that there is no break in the battery connection wires.
Note:
Maximum charging current under discharges is 0.7A.
Note:
Expected battery life is 5 years; however, it is recommended changing batteries in
4 years or less if needed.