background image

 

AL300X220 Series 

- 5 -

Terminal Identification:

Power Supply Board

Terminal Legend Function/Description

L, G, N

Connect 220VAC (working range 198VAC - 256VAC), 50/60Hz to these terminals: 

L to Hot, N to Neutral. Do not use the [G] terminal.

+ DC –

12VDC or 24VDC @ 2.5A continuous power-limited output.

AC Fail

NC, C, NO

Indicates loss of AC power, e.g. connect to annunciator/alarm panel. Relay normally ener-

gized when AC power is present. Contact rating 1A @ 28VDC. AC Fail condition will report 

approximately within one (1) minute after loss of AC. To delay report for 6 hours cut jumper 

J1 on the Power Supply Board (AC trouble output delay option). If this mode is selected, the 

Power Supply Board must be reset by removing all power to it for 30 seconds.

Bat Fail

NC, C, NO

Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized 

when DC power is present. Contact rating 1A @ 28VDC. Low battery conditions will report 

approximately 21VDC (24VDC output setting) or approximately 10.5VDC (12VDC output 

setting). Battery presence detection will report approximately 1 minute after battery remains 

undetected (missing or removed). 

+ BAT –

Stand-by battery connections. Maximum charge current 0.7A.

Power Distribution Module

Terminal Legend

Function/Description

PD4/PD4CB

PD8/PD8CB

1P to 4P

1P to 8P

Positive DC power outputs.

1N to 4N

1N to 8N

Negative DC power outputs.

Power Distribution Module(s):

Fig. 2a  -  PD4 Power Distribution Board 

Fig. 2b  -  PD4CB - Power Distribution Board

 

  Fuse Protected Outputs 

 

  PTC Protected Outputs

Fig. 3a  -  PD8 Power Distribution Board 

Fig. 3b  -  PD8CB - Power Distribution Board

 

  Fuse Protected Outputs 

 

  PTC Protected Outputs

LED

F1

F2

F3

F4

1P

1N

2P

2N

3P

3N

4P

4N

DC Output to devices

1P-4P Power Outputs,

1N-4N Common Outputs

From Power Supply

Board

(Factory Installed)

Replace fuses with the same type and rating 3.5A/250V  

N

COMMON   POWER   OUTPUTS

P

FUSED    POWER    OUTPUTS

8

D1

INPUT

R1

LED

DC Output to devices

1P-8P Power Outputs,

1N-8N Common Outputs

From Power Supply

Board

(Factory Installed)

Replace fuses with the same type and rating 3.5A/250V  

LED

F1

F2

F3

F4

1P

1N

2P

2N

3P

3N

4P

4N

DC Output to devices

1P-4P Power Outputs,

1N-4N Common Outputs

From Power Supply

Board

(Factory Installed)

N

COMMON   POWER   OUTPUTS

P

FUSED    POWER    OUTPUTS

8

D1

INPUT

R1

LED

DC Output to devices

1P-8P Power Outputs,

1N-8N Common Outputs

From Power Supply

Board

(Factory Installed)

Содержание AL300X220 Series

Страница 1: ...Include For a red enclosure add an R suffix to the part e g AL300PD8R220 For a larger enclosure add an X suffix to the part e g AL300XPD8220 Installation Guide AL300X220 Single Output AL300PD4220 Four 4 Fuse Protected Outputs AL300PD8220 Eight 8 Fuse Protected Outputs AL300XPD16220 Sixteen 16 Fuse Protected Outputs AL300PD4CB220 Four 4 PTC Protected Outputs AL300PD8CB220 Eight 8 PTC Protected Outp...

Страница 2: ...2 12VDC 12AH AL300PD8CB220 PD8CB P 2 5A 2 5A Two 2 12VDC 7AH AL300XPD8CB220 Two 2 12VDC 12AH AL300XPD16220 Two 2 PD8 16 P 2 5A 2 5A Two 2 12VDC 12AH AL300XPD16CB220 Two 2 PD8CB P 2 5A 2 5A Two 2 12VDC 12AH Specifications Agency Listing CE European Conformity Input Nominal 220VAC working range 198 256VAC 50 60Hz 1 7A AC input and DC output LED indicators Output 12VDC or 24VDC selectable output s 2 ...

Страница 3: ...itch Position 24VDC SW1 OFF 12VDC SW1 ON Battery AC Supervision Circuit power limited J1 AC Delay Green Lead 115VAC power mains non power limited Class 1 DC Output to devices power limited CAUTION When power supply board is set for 12VDC use only one 1 12VDC stand by battery Keep power limited wiring separate from non power limited Use minimum 0 25 spacing For 12VDC Operation use hook up in the in...

Страница 4: ...ribution Models connect devices to be powered to the terminal pairs 1 to 4 marked 1P 1N through 4P 4N Fig 2a 2b pg 6 or 1 to 8 marked 1P 1N through 8P 8N Fig 3a 3b pg 6 carefully observing correct polarity 6 For Access Control applications batteries are optional When batteries are not used a loss of AC will result in the loss of output voltage When the use of stand by batteries is desired they mus...

Страница 5: ...tected missing or removed BAT Stand by battery connections Maximum charge current 0 7A Power Distribution Module Terminal Legend Function Description PD4 PD4CB PD8 PD8CB 1P to 4P 1P to 8P Positive DC power outputs 1N to 4N 1N to 8N Negative DC power outputs Power Distribution Module s Fig 2a PD4 Power Distribution Board Fig 2b PD4CB Power Distribution Board Fuse Protected Outputs PTC Protected Out...

Страница 6: ...DC output voltage should be checked for proper voltage level Power Supply Voltage Output Specifications Chart pg 3 Battery Test Under normal load conditions check that the battery is fully charged check specified voltage both at the battery terminal and at the board terminals marked BAT to ensure that there is no break in the battery connection wires Note Maximum charging current under discharges ...

Страница 7: ... 82 6mm 1 40 35 6mm 1 40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40 35 6mm 5 10 129 5mm 6 5625 166 7mm 3 25 82 6mm 3 25 82 6mm 3 25 82 6mm 10 5 266 7mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm 13 0 330 2mm 5 10 129 5mm 1 20 30 5mm ...

Страница 8: ...81 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warranty Made in U S A IIAL300X220 Series G02U MEMBER 1 5 38 1mm 1 5 38 1mm 4 615 117 2mm 4 615 117 2mm 1 5 38 1mm 1 5 38 1mm 4 615 117 2mm 4 615 117 2mm 1 75 44 5mm 1 75 44 5mm 1 375 34 9mm 1 125 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1 25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm...

Отзывы: