Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with 
all local codes and authorities having jurisdiction. Product is intended for indoor use only. 
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes 
  in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place 
  the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower 
  two holes. Remove the enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper 
  keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 
  (Enclosure Dimensions, pg. 8). Secure enclosure to earth ground. 
2. Set the unit to the desired DC output voltage by setting SW1 (Fig. 1c, pg. 5) to the appropriate position 
  (Power Supply Output Specification Chart, pg. 2).
3. Secure cabinet to earth gourd. Connect AC power (115VAC, 60 Hz) to the terminals marked [L, N] 
  (Fig. 1, pg. 5). Use 14 AWG or larger for all power connections (Battery, DC output, AC input).
  Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).
 

Keep power-limited wiring separate from non-power limited wiring (115VAC / 60Hz Input, 

  Battery Wires). Minimum 0.25” spacing must be provided.
  For Fire Alarm applications the outputs are “Special Applications” only, see list (refer to Appendix A, pg. 6)
4. Measure output voltage before connecting devices. This helps avoiding potential damage. 
  When servicing the unit, AC mains should be removed.
5. Connect devices to the terminals marked [+ DC –] (Fig. 1, pg. 5).
6. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result 
  in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.
  Connect one (1) 12VDC battery to the terminals marked [+ BAT –] for 12VDC operation. 
  Use two (2) 12VDC batteries wired in series for 24VDC operation.
7. Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 1a, pg. 5) supervisory 
  relay outputs.
 

Note: When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay should be

  utilized to visually indicate that AC power is on. To delay report for 6 hours cut “AC Delay” jumper 
  (Fig. 1b, pg. 5)
8. Please ensure that the cover is secured with the provided key lock.

Wiring:

Use 14 AWG or larger for all power connections.
Note: Take care to keep power-limited circuits separate from non power-limited wiring (115VAC, Battery).

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: 

Under normal load conditions, the DC output voltage should be checked for proper 

   

voltage level (refer to Power Supply Voltage Output Specifications chart).

Battery Test: 

Under normal load conditions check that the battery is fully charged, check specified 

   

voltage both at the battery terminal and at the board terminals marked [+ BAT –] to 

   

ensure that there is no break in the battery connection wires.

  

Note: Maximum charging current under discharge is 0.7A.

  

Note: Expected battery life is 5 years, however it is recommended changing batteries 

   

in 4 years or less if needed.

Содержание AL300ULXJ

Страница 1: ...More than just power TM Rev 102612 AL300ULXJ Power Supply Charger Installation Guide Altronix Corp 140 58th St Brooklyn NY For a grey enclosure add a G suffix to the part number...

Страница 2: ...2V Filtered and electronically regulated output s Short circuit and thermal overload protection LED Indicators AC input DC output and Battery LED indicators Battery Backup Built in charger for sealed...

Страница 3: ...his helps avoiding potential damage When servicing the unit AC mains should be removed 5 Connect devices to the terminals marked DC Fig 1 pg 5 6 For Access Control applications batteries are optional...

Страница 4: ...lly energized when AC power is present Contact rating 1A 28VDC AC Fail condition will report approximately within one 1 minute after loss of AC To delay report for 6 hours cut jumper J1 on the Power S...

Страница 5: ...ction against risk of electric shock and fire hazard replace fuse with the same type and rating Do not expose to rain or moisture CAUTION Optional rechargeable stand by batteries must match the power...

Страница 6: ...Thermal Supervisory Relay 15 45 2312 24TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 39 2...

Страница 7: ...AL300ULXJ 7 Notes...

Страница 8: ...MEMBER 4 5 114 3mm 1 25 31 75mm 1 25 31 8mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 8 5 215 9mm 18 0 457 2mm 18 0 457 2mm 18 0 457 2mm 6 0 152 4mm 2 75...

Отзывы: