AL176220 Series Installation Guide 

- 3 -

5. Connect battery to the terminals marked [+ BAT –] on the power supply board (battery leads included). 

  Use two (2) 12VDC batteries connected in series for 24VDC operation.

 

Note:

 For Access Control applications batteries are optional. 

  When batteries are not used, a loss of AC will result in the loss of output voltage. 

  When the use of stand-by batteries is desired, they must be lead acid or gel type. 

6. Connect appropriate signaling notification devices to AC Fail and Low Bat supervisory relay outputs. 

 

Note:

 AC Supervisory outputs must be connected to the zone of Alarm Control Panel or to visual 

  AC trouble indicator. 

7. For Access Control Device connections refer to the Terminal Identification Chart. 

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test

:  Under normal load conditions the DC output voltage should be checked for proper 

 

voltage level

 

(see 

Power Supply Output Specifications Chart

).

Battery Test

Under normal load conditions check that the battery is fully charged, check specified 

 

voltage both at the battery terminal and at the board terminals marked [+ BAT –] to 

 

ensure that there is no break in the battery connection wires.

Note:

  

Maximum charging current under discharges is 400mA.

Note:

  

Expected battery life is 5 years; however, it is recommended changing batteries in 

 

4 years or less if needed.

LED Diagnostics:

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal function.

ON

OFF

Loss of AC. Battery backup is powering output.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or missing stand-by battery. No DC output.

Terminal Identification:

Terminal Legend

Function/Description

XFMR INPUT

Low voltage AC input (28VAC, 56VA).

+ DC OUT –

Continuous positive (+) DC power output voltage. 
Common negative (–) output (ground).

+ BAT –

Stand-by battery connections. 

AC FAIL

NO, C, NC

Used to notify loss of AC, e.g. connect audible device or alarm panel. 

Relay is normally energized when AC power is present. Contact rating 1A @ 28VDC.

LOW BAT

NO, C, NC

Used to notify low battery condition, e.g. connect audible device or alarm panel. 

Relay is normally energized. Contact rating 1A @ 28VDC.

Содержание AL176220 Series

Страница 1: ..._________________ Phone ___________________ AL176220 Series Access Control Power Supply Chargers Models Include AL176220 Enclosure Dimensions 8 5 x 7 5 x 3 5 215 9mm x 190 5mm x 88 9mm Accommodates on...

Страница 2: ...e two lower screws and make sure to tighten all screws Enclosure Dimensions pgs 7 and 8 Secure enclosure to earth ground 2 Connect unswitched AC circuit 220VAC 50 60Hz as follows Green branch wire gro...

Страница 3: ...tions Chart Battery Test Under normal load conditions check that the battery is fully charged check specified voltage both at the battery terminal and at the board terminals marked BAT to ensure that...

Страница 4: ...ide Fig 1 Black Lead White Lead 220VAC Input 50 60Hz 0 3A 12VDC JUMPER OUT 24VDC JUMPER IN VR1 AC ON XFMR INPUT BAT DC OUT AC FAIL NO C NC LOW BAT NO C NC DC ON Battery and AC Supervision Devices or L...

Страница 5: ...AL176220 Series Installation Guide 5 Notes...

Страница 6: ...6 AL176220 Series Installation Guide Notes...

Страница 7: ...mm 0 6 15 2mm 0 6 15 2mm 0 6 15 2mm 0 6 15 2mm 2 50 8mm 2 50 8mm 8 125 206 4mm 1 25 4mm 1 25 4mm 1 25 4mm 1 25 31 75mm 1 25 31 75mm 1 25 4mm 1 25 4mm 5 25 133 35mm 6 05 153 7mm 3 5 88 9mm Enclosure Di...

Страница 8: ...5 82 6mm 3 25 82 6mm 10 5 266 7mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm 13 0 330 2mm 5 10 129 5mm 1 20 30 5mm Enclosure Dimensions H x W x D approximate AL176X220 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 55...

Отзывы: