AL176220 Series Installation Guide

Overview:

Altronix AL176220 and AL176X220 are power supply/chargers that converts a 220VAC (working range 198VAC - 

256VAC), 50/60Hz input into 12VDC or 24VDC output (see specifications). Units must be installed in accordance 

with National and Local Electrical Codes and Regulations.

Specifications:

Power Supply Output Specifications:

Output VDC

Jumper

Max. Stand-by 

Load DC

Max. Alarm 

Load DC

Battery (optional)

12VDC

Jumper Removed

1.75A

1.75A

1.75A

1.75A

12VDC

24VDC

Jumper On

Two (2) 12VDC

Stand-by Specifications:

Output

4 hr. of Stand-by and 5 Minutes of Alarm

12VDC / 7 AH Battery

Stand-by = 1.25A

Alarm = 1.25A

24VDC / 7 AH Battery

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI and with all 

local codes and authorities having jurisdiction. Product is intended for indoor use only. 

See Terminal Identification Chart on page 3 for a description of each terminal function.

1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes 

  in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place 

  the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower 

  two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s 

  upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 

 

(Enclosure Dimensions, pgs. 7 and 8)

. Secure enclosure to earth ground. 

2. Connect unswitched AC circuit (220VAC, 50/60Hz) as follows: Green branch wire (ground) connects to the 

  terminal marked     , Line connects to the terminal marked [L], and Neutral connects to the terminal marked 

  [N] of the Inlet Appliance Connector. Use 18 AWG or larger for all power connections (Battery, AC input). 

  Use 22 AWG to 18 AWG for power-limited circuits (DC output, AC FAIL, and LOW BAT supervisory relays).

  Keep power-limited wiring separate from non power-limited wiring (220VAC, 50/60Hz Input, 

  Battery Wires). Minimum 0.25” spacing must be provided.

3. Set the unit to the desired DC output voltage by either removing or leaving the jumper. 

 

(Power Supply Output Specification Table).

4. Measure output voltage before connecting devices. This helps avoiding potential damage.

Input:

•   Input  220VAC  (working range 198VAC - 256VAC), 

50/60Hz, 0.3A.

Output:

•  12VDC or 24VDC selectable output.

•  1.75A continuous supply current.

•  Filtered and electronically regulated output.

•  Short circuit and thermal overload protection.

Battery Backup:

•  Built-in charger for sealed lead acid or 

  gel type batteries.

•  Maximum charge current: 400mA.

•  Automatic switch over to stand-by battery 

  when AC fails.

Supervision:

•  AC fail supervision (form “C” contacts). 

•  Low battery supervision (form “C” contacts).

Visual Indicators:

•  AC input and DC output LED indicators.

Added Features:

•  Includes power supply, transformer, and enclosure.

Enclosure Dimensions:

AL176220:

  8.5” x 7.5” x 3.5” (215.9mm x 190.5mm x 88.9mm).

AL176X220:

  13.5” x 13” x 3.25” 

  (342.9mm x 330.2mm x 82.6mm).

Black Lead

White Lead

220VAC Input

50/60Hz, 0.3A

12VDC = JUMPER OUT
24VDC = JUMPER IN

VR1

AC ON

XFMR INPUT

+ BAT ----

+ DC OUT ----

AC FAIL

NO     C     NC

LOW BAT

NO     C     NC

DC ON

Battery and AC

Supervision

Devices

or Load

Stand-by

Battery

(optional)

XFMR

Содержание AL176220 Series

Страница 1: ..._________________ Phone ___________________ AL176220 Series Access Control Power Supply Chargers Models Include AL176220 Enclosure Dimensions 8 5 x 7 5 x 3 5 215 9mm x 190 5mm x 88 9mm Accommodates on...

Страница 2: ...e two lower screws and make sure to tighten all screws Enclosure Dimensions pgs 7 and 8 Secure enclosure to earth ground 2 Connect unswitched AC circuit 220VAC 50 60Hz as follows Green branch wire gro...

Страница 3: ...tions Chart Battery Test Under normal load conditions check that the battery is fully charged check specified voltage both at the battery terminal and at the board terminals marked BAT to ensure that...

Страница 4: ...ide Fig 1 Black Lead White Lead 220VAC Input 50 60Hz 0 3A 12VDC JUMPER OUT 24VDC JUMPER IN VR1 AC ON XFMR INPUT BAT DC OUT AC FAIL NO C NC LOW BAT NO C NC DC ON Battery and AC Supervision Devices or L...

Страница 5: ...AL176220 Series Installation Guide 5 Notes...

Страница 6: ...6 AL176220 Series Installation Guide Notes...

Страница 7: ...mm 0 6 15 2mm 0 6 15 2mm 0 6 15 2mm 0 6 15 2mm 2 50 8mm 2 50 8mm 8 125 206 4mm 1 25 4mm 1 25 4mm 1 25 4mm 1 25 31 75mm 1 25 31 75mm 1 25 4mm 1 25 4mm 5 25 133 35mm 6 05 153 7mm 3 5 88 9mm Enclosure Di...

Страница 8: ...5 82 6mm 3 25 82 6mm 10 5 266 7mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm 13 0 330 2mm 5 10 129 5mm 1 20 30 5mm Enclosure Dimensions H x W x D approximate AL176X220 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 55...

Отзывы: