 The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the 

presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of sufficient 
magnitude to constitute an electric shock. 

The exclamation point within an equilateral triangle is intended to alert the user to the presence of important 

operating and maintenance (servicing) instructions in the literature accompanying the appliance. 

CAUTION: To reduce the risk of electric shock do not open enclosure. There are 
no user serviceable parts inside. Refer servicing to qualified service personnel. 

Maintenance: 

Unit should be tested at least once a year for the proper operation as follows: 
Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level 
(Power Supply Output Specifications Table, pg. 1). 
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage both at battery 
terminal and at the board terminals marked [+ BAT -- ] to ensure that there is no break in the battery connection wires. 
Note: Maximum charging current under discharge is 400mA. 
Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed. 

LED Diagnostics: 

Red 

Power Supply Status 

ON 

Normal function. 

OFF 

No DC output. 

Slow Blink 

Loss of AC. 

Rapid Blink 

Unit is triggered, awaiting reset. Fire alarm interface activated. 

Fig. 1 - Application Diagram: 

VR1 

NO 

NO

GND 

GND 

FACP1 FACP2 

COM--

LOCK+

+ AUX --

TRIG  INPUT 

RESET 

SW1 

XFMR

+ BAT 

--

SW2: 
OFF-12VDC 
ON-24VDC 

Normally Open 

Access Control 

Triggering 

Device 

Normally Open 

Reset Device 

2.2K EOL 

(supplied) 

MAG LOCK 

NC 

FACP 

NO 

FACP 

Note: If 2.2K resistor is not installed 

unit will be in alarm condition. 

Card 

Reader 

ON

 

ON

 

Transformer 

Stand-by 

Batteries 

Fig. 1a 
SW2 

SW2: 
OFF-12VDC 
ON-24VDC 

ON

 

ELECTRIC 

STRIKE 

COM--

LOCK+

+ AUX --

AL125ULseries 

- 3 ­

                    Available from A1 Security Cameras 

    www.a1securitycameras.com email: [email protected]

Содержание AL125UL

Страница 1: ...cludes power supply transformer cam lock and enclosure 8 5 x 7 5 x 3 5 215 9mm x 190 5mm x 88 9mm Accommodates one 1 12VDC 4AH battery AL125ULP includes power supply 24VAC 40VA plug in transformer cam lock and enclosure 8 5 x 7 5 x 3 5 215 9mm x 190 5mm x 88 9mm Accommodates one 1 12VDC 7AH battery or two 2 12VDC 4AH batteries AL125ULE includes power supply cam lock and enclosure 8 5 x 7 5 x 3 5 2...

Страница 2: ...am pg 3 6 Connect normally open access control device i e card reader request to exit device access control system to the terminals marked TRG INPUT NO GND Fig 1 Application Diagram pg 3 7 Connect FACP interface to the terminals marked FACP1 and FACP2 Wire the 2 2K resistor supplied in series for a normally closed input or in parallel for a normally open input Fig 1 Application Diagram pg 3 If req...

Страница 3: ... 1 Battery Test Under normal load conditions check that the battery is fully charged check specified voltage both at battery terminal and at the board terminals marked BAT to ensure that there is no break in the battery connection wires Note Maximum charging current under discharge is 400mA Note Expected battery life is 5 years however it is recommended changing batteries in 4 years or less if nee...

Страница 4: ...m 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm 3 25 83mm 3 25 83mm 1 0 25mm 1 0 25mm 10 5 267mm 1 0 25mm 1 0 25mm 0 75 19mm 0 75 19mm 0 9375 24mm 0 9375 24mm 11 0 279mm 12 5 318mm 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 55mm Altronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11...

Отзывы: