LED Diagnostics: 

Power Supply Board 

Red (DC) 

Green (AC) 

Power Supply Status 

ON 

ON 

Normal operating condition. 

ON 

OFF 

Loss of AC. Stand-by battery supplying power. 

OFF 

ON 

No DC output. 

OFF 

OFF 

Loss of AC. Discharged or no stand-by battery. No DC output. 

Power Distribution Module 

Green 

Power Distribution Module Status 

ON 

Normal operating condition. 

OFF 

No Power Output. 

Terminal Identification: 

Power Supply Board 

Terminal 
Legend 

Function/Description 

L, N 

Connect 220VAC (working range 198VAC-256VAC), 50/60Hz to these terminals: 
L to hot, N to neutral. 

+ DC – 

24VDC @ 8A continuous, 10A in alarm non power-limited output. 
10A continuous when batteries are not used 

AC Fail 
NC, C, NO 

Indicates loss of AC power, e.g. connect to audible device or alarm panel. 
Relay normally energized when AC power is present. Contact rating 1A @ 28VDC. 
AC or brownout fail is reported within 1 minute of event. 
To delay reporting for up to 6 hrs., cut “AC delay” jumper and reset power to unit. 

Bat Fail 
NC, C, NO 

Indicates low battery condition, e.g. connect to alarm panel. 
Relay normally energized when DC power is present. Contact rating 1A @ 28VDC. 
A removed battery is reported within 5 minutes. 
Battery reconnection is reported within 1 minute. 
Low battery threshold: 24VDC output threshold set @ approximately 21VDC. 

– BAT + 

Stand-by battery connections. Maximum charge current 3.6A. 

Power Distribution Module 

Terminal Legend 

Function/Description

PD4/PD4CB 

PD8/PD8CB 

1P to 4P 

1P to 8P 

Positive DC power outputs. 

1N to 4N 

1N to 8N 

Negative DC power outputs. 

AL1024X220 Series 

- 5 ­

                    Available from A1 Security Cameras 

    www.a1securitycameras.com email: [email protected]

Содержание AL1024X220 Series

Страница 1: ...s AL1024XPD16220 Sixteen 16 Fuse Protected Outputs AL1024XPD4CB220 Four 4 PTC Protected Outputs AL1024XPD8CB220 Eight 8 PTC Protected Outputs AL1024XPD16CB220 Sixteen 16 PTC Protected Outputs For a re...

Страница 2: ...teries Automatic switch over to stand by battery when AC fails Maximum charge current 3 6A Battery Backup cont d Zero voltage drop when switched over to battery backup Supervision AC fail supervision...

Страница 3: ...ded CAUTION Do not touch exposed metal parts Shut branch circuit power before installing or servicing equipment There are no user serviceable parts inside Refer installation and servicing to qualified...

Страница 4: ...oor 220VAC power mains Divider INPUT Power Distribution Module s Battery and AC Supervision Circuit Battery Connections Keep power limited wiring separate from non power limited Use minimum 0 25 spaci...

Страница 5: ...ble device or alarm panel Relay normally energized when AC power is present Contact rating 1A 28VDC AC or brownout fail is reported within 1 minute of event To delay reporting for up to 6 hrs cut AC d...

Страница 6: ...S 1 2 3 4 5 6 7 8 D1 INPUT R1 LED DC Output to devices From Power Supply 1P 8P Power Outputs Board 1N 8N Common Outputs Factory Installed PTC Protected Outputs LED 1P 1N 2P 2N 3P 3N 4P F1 F2 F3 F4 4N...

Страница 7: ...25 Hour H Battery capacity required for Alarm I Total calculated battery capacity J Battery capacity required stand by stand by A B C Alarm Alarm Alarm E F G D H I 1 8 safety factor 0 05 A A H AH 0 0...

Страница 8: ...91 23 114mm 1 375 34 925mm 1 125 28 575mm 15 5 393 7mm 4 615 117 22mm 12 23 310 64mm 4 615 117 22mm 1 5 1 5 4 615 4 615 1 25 38 1mm 117 22mm 117 22mm 38 1mm Altronix is not responsible for any typogra...

Отзывы: