Installation Instructions: 

Wiring methods should be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI and with 
all local codes and authorities having jurisdiction. Product is intended for indoor use only. 
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes 

in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place 
the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower 
two holes. Remove the enclosure. Drill the lower holes and install the fasteners. Place the enclosure’s upper 
keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 
(Enclosure Dimensions, pg. 8). Secure enclosure to earth ground. 

2. Connect AC circuit (220VAC, 50/60Hz) as follows: Green branch wire connects to earth (safety) ground 

lug  . Line and Neutral to the connector on power supply board marked [L, N] respectively (Fig. 1, pg. 4).
Use 14 AWG or larger for all power connections (Battery, DC output, AC input). 
Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting). 

3. Measure output voltage before connecting devices. This helps avoiding potential damage. 

Keep power-limited wiring separate from non power-limited wiring (220VAC 50/60Hz Input,
Battery Wires). Minimum 0.25” spacing must be provided. 
CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing
equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified
service personnel. 

4. Connect devices to be powered: 

a.  For Power Supply Board: connect to the terminals marked [+ DC –] (Fig. 1, pg. 4). 
b. For Power Distribution Module(s): connect devices to be powered to the terminal pairs 1 to 4 marked 

[1P & 1N] through [4P & 4N] (Fig. 2, pg. 6) or 1 to 8 marked [1P & 1N] through [8P & 8N] 
(Fig. 3, pg. 6), carefully observing correct polarity. 

Note: When servicing the unit, AC mains should be removed. 

5. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result 

in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type. 

6. Connect appropriate signaling notification devices to terminals marked [AC FAIL] and [BAT FAIL] 

(Fig. 1, pg. 4) supervisory relay outputs. 
Note: When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay must be used 
to provide a visual indication of AC power on. 

7. Please ensure that the cover is secured with the provided key lock. 

Wiring: 

Use 14 AWG or larger for all power connections. 
Note: Take care to keep power-limited circuits separate from non power-limited wiring (220VAC, Battery). 

Maintenance: 

Unit should be tested at least once a year for the proper operation as follows: 
Output Voltage Test:  Under normal load conditions the DC output voltage should be checked for the proper 

voltage level. 

Battery Test: 

Under normal load conditions check that the battery is fully charged, check specified 
voltage both at the battery terminal and at the board terminals marked [– BAT +] to 
ensure that there is no break in the battery connection wires. 

Note: 

Maximum charging current under discharges is 3.6A. 

Note: 

Expected battery life is 5 years; however, it is recommended changing batteries in 
4 years or less if needed. 

AL1024X220 Series 

- 3 ­

                    Available from A1 Security Cameras 

    www.a1securitycameras.com email: [email protected]

Содержание AL1024X220 Series

Страница 1: ...s AL1024XPD16220 Sixteen 16 Fuse Protected Outputs AL1024XPD4CB220 Four 4 PTC Protected Outputs AL1024XPD8CB220 Eight 8 PTC Protected Outputs AL1024XPD16CB220 Sixteen 16 PTC Protected Outputs For a re...

Страница 2: ...teries Automatic switch over to stand by battery when AC fails Maximum charge current 3 6A Battery Backup cont d Zero voltage drop when switched over to battery backup Supervision AC fail supervision...

Страница 3: ...ded CAUTION Do not touch exposed metal parts Shut branch circuit power before installing or servicing equipment There are no user serviceable parts inside Refer installation and servicing to qualified...

Страница 4: ...oor 220VAC power mains Divider INPUT Power Distribution Module s Battery and AC Supervision Circuit Battery Connections Keep power limited wiring separate from non power limited Use minimum 0 25 spaci...

Страница 5: ...ble device or alarm panel Relay normally energized when AC power is present Contact rating 1A 28VDC AC or brownout fail is reported within 1 minute of event To delay reporting for up to 6 hrs cut AC d...

Страница 6: ...S 1 2 3 4 5 6 7 8 D1 INPUT R1 LED DC Output to devices From Power Supply 1P 8P Power Outputs Board 1N 8N Common Outputs Factory Installed PTC Protected Outputs LED 1P 1N 2P 2N 3P 3N 4P F1 F2 F3 F4 4N...

Страница 7: ...25 Hour H Battery capacity required for Alarm I Total calculated battery capacity J Battery capacity required stand by stand by A B C Alarm Alarm Alarm E F G D H I 1 8 safety factor 0 05 A A H AH 0 0...

Страница 8: ...91 23 114mm 1 375 34 925mm 1 125 28 575mm 15 5 393 7mm 4 615 117 22mm 12 23 310 64mm 4 615 117 22mm 1 5 1 5 4 615 4 615 1 25 38 1mm 117 22mm 117 22mm 38 1mm Altronix is not responsible for any typogra...

Отзывы: