Altronix AL1012ULACMCB Скачать руководство пользователя страница 7

ACMCBseries

- 7 -

Terminal Identification Tables:

Power Supply Board

Terminal

Function/Description

Legend

L, G, N

Connect 115VAC 60Hz to these terminals: L to hot, N to neutral, G to ground.

- DC +

AL400ULACMCB - 12VDC @ 4 amp or 24VDC @ 3 amp to ACM8CB board (power limited). 
AL600ULACMCB - 12VDC/24VDC @ 6 amp to ACM8CB board (power limited).
AL1012ULACMCB - 12VDC @ 10 amp to ACM8CB board (power limited).
AL1024ULACMCB - 24VDC @ 10 amp to ACM8CB board (power limited).

AC FAIL

Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay

NC, C, NO

normally energized when AC power is present. Contact rating 1 amp @ 28VDC.
AC or brownout fail is reported within 1 minute of event. To delay reporting of up to 
6 hrs., cut “AC delay” jumper and reset power to unit.

BAT FAIL

Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally

NC, C, NO

energized when DC power is present. Contact rating 1 amp @ 28VDC.
A removed battery is reported within 5 minutes. Battery reconnection is reported 
within 1 minute.
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC (N/A for AL1024ULACMCB), 
24VDC output threshold set @ approximately 21VDC (N/A for AL1012ULACMCB).

- BAT +

Stand-by battery connections. AL400ULXB, AL600ULXB and AL1012ULXB (Power Supply 
Board) maximum charge current is .7 amp. AL1024ULXB (Power Supply Board)
maximum charge current is 3.6 amp.

ACM8CB Access Power Controller

Terminal

Function/Description

Legend

- Power  +

12VDC or 24VDC input from power supply board.

- C

These terminals can be connected to a separate power limited, UL listed power supply to 
provide isolated operating power for the ACM8 (jumpers J1and J2 Must be removed).

TRIGGER  

From normally open  and/or open collector sink trigger inputs   

INPUT 1- INPUT 8

(request to exit buttons, exit pir’s, etc.).

IN, GND

OUTPUT 1-OUTPUT 8

12 to 24 volts AC/DC trigger controlled outputs:

NC, C, NO, COM

Fail-Safe [NC positive (+) & COM Negative (-)], 
Fail-Secure [NO positive (+) & COM Negative (-)], 
Auxiliary output [C positive (+) & COM Negative (-)] 
(When using AC power supplies polarity need not be observed), 
NC, C, NO become  form “C”  5 amp 24VAC/VDC rated dry outputs when fuses are 
removed. Contacts shown in a non-triggered state.

FACP INTERFACE

Fire Alarm Interface trigger input from FACP.  Trigger inputs can be normally open,

T, + INPUT  -- 

normally closed from an FACP output circuit (Fig. 4 through 8 , pg. 8).

FACP INTERFACE  

Form “C” relay contact rated @ 1 amp 28VDC for alarm reporting.

NC, C, NO

(This output has not been evaluated by UL).

Содержание AL1012ULACMCB

Страница 1: ...uide Models Include AL400ULACMCB AL600ULACMCB 4 amp 12VDC 6 amp 12VDC or 24VDC or 3 amp 24VDC PTC Outputs PTC Outputs AL1012ULACMCB AL1024ULACMCB 10 amp 12VDC 10 amp 24VDC PTC Outputs PTC Outputs Rev...

Страница 2: ...Secure power outputs Eight 8 auxiliary power outputs unswitched PTC protected outputs are rated 2 5 amp ACM8CB board main fuse is rated at 10 amp Red LEDs indicate outputs are triggered relays energiz...

Страница 3: ...et output voltage AL400ULACMCB and AL600ULACMCB set desired DC output voltage by setting switch SW1 to the appropriate position on the power supply board AL1012ULACMCB is 12VDC and AL1024ULACMCB is 24...

Страница 4: ...latching hook up Fig 8 pg 8 c FACP Signaling Circuit input trigger Connect the positive and negative from the FACP signaling circuit output to the terminals marked INP Connect the FACP EOL to the ter...

Страница 5: ...or DC POWER SUPPLY req d FACP Fire Alarm Control Panel UL Listed POWER SUPPLY For this application corresponding fuse F8 must be removed SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8 FACP Interface Enabled FACP In...

Страница 6: ...IL BAT FAIL Battery and AC Supervision Circuit power limited Battery connection non power limited Door Wire Strap from Enclosure to Door DC Output to devices power limited Fire Alarm Interface Insulat...

Страница 7: ...approximately 21VDC N A for AL1012ULACMCB BAT Stand by battery connections AL400ULXB AL600ULXB and AL1012ULXB Power Supply Board maximum charge current is 7 amp AL1024ULXB Power Supply Board maximum c...

Страница 8: ...ching FACP trigger input with reset This output has not been evaluated by UL Fig 4 Polarity reversal input from FACP signaling circuit output polarity is referenced in alarm condition Fig 3 Optional h...

Страница 9: ...arm ______________________ A G Alarm duration Hours example 15 Min 25 Hour Alarm ______________________ H H Battery capacity required for Alarm E F G ______________________ AH I Total calculated batte...

Страница 10: ...10 ACMCBseries 875 1 0 0 0 0 10 75 1 5 6 10 5 2 0 1 25 4 5 12 15 5 4 5 4 5 1 25 1 25 14 25 13 5 10 6 625 TOP BOTTOM Enclosure Dimensions 15 5 H x 12 W x 4 5 D...

Страница 11: ...ACMCBseries 11 Notes...

Страница 12: ...Street Brooklyn New York 11220 USA 718 567 8181 fax 718 567 9056 web site www altronix com e mail info altronix com Lifetime Warranty Made in U S A IIACMCB series L06G MEMBER Altronix is not responsi...

Отзывы: