Altronix AL1012ULACMCB Скачать руководство пользователя страница 6

- 6 -

ACMCBseries

LED Diagnostics:

Power Supply Board

LED

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC, Stand-by battery supplying power.

OFF

ON

No DC output. Short circuit or thermal overload condition. 

OFF

OFF

No DC output. Loss of AC. Discharged battery. 

ACM8 Access Power Controller 

LED ON 

OFF

LED 1- LED 8 (Red)

Output relay(s) energized.

Output relay(s) de-energized.

Trg (Green)

FACP input triggered (alarm condition).

FACP normal (non-alarm condition).

 -

-- 

  

D

C

  

+

 

L       G        N

ALTRONIX CORP.

BKLYN, N.Y. 11220

MADE IN USA

 -

-- 

  

B

A

T

  

+

 

AC FAIL

BAT FAIL

Battery and AC 

Supervision Circuit 

(power limited)

Battery connection (non-power limited)

Door

Wire
Strap
(from
Enclosure
to Door)

DC Output to devices (power limited)

Fire
Alarm
Interface

Insulating
Barrier

Inputs (power limited)

unswitched 115VAC 

power mains 

(non-power limited)

Power Supply Board

CAUTION: De-energize unit prior to servicing. 

For continued protection against fire hazard replace

fuse with the same type and rating .

Replace fuse cover before energizing.

Green 

Lead

Green 

Lead

Keep power limited wiring separate from non-power limited. Use minimum .25" spacing.

12VDC Rechargeable Battery

(optional)

12VDC Rechargeable Battery

(optional)

CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC
stand-by battery.

Fig. 2

Содержание AL1012ULACMCB

Страница 1: ...uide Models Include AL400ULACMCB AL600ULACMCB 4 amp 12VDC 6 amp 12VDC or 24VDC or 3 amp 24VDC PTC Outputs PTC Outputs AL1012ULACMCB AL1024ULACMCB 10 amp 12VDC 10 amp 24VDC PTC Outputs PTC Outputs Rev...

Страница 2: ...Secure power outputs Eight 8 auxiliary power outputs unswitched PTC protected outputs are rated 2 5 amp ACM8CB board main fuse is rated at 10 amp Red LEDs indicate outputs are triggered relays energiz...

Страница 3: ...et output voltage AL400ULACMCB and AL600ULACMCB set desired DC output voltage by setting switch SW1 to the appropriate position on the power supply board AL1012ULACMCB is 12VDC and AL1024ULACMCB is 24...

Страница 4: ...latching hook up Fig 8 pg 8 c FACP Signaling Circuit input trigger Connect the positive and negative from the FACP signaling circuit output to the terminals marked INP Connect the FACP EOL to the ter...

Страница 5: ...or DC POWER SUPPLY req d FACP Fire Alarm Control Panel UL Listed POWER SUPPLY For this application corresponding fuse F8 must be removed SW1 SW2 SW3 SW4 SW5 SW6 SW7 SW8 FACP Interface Enabled FACP In...

Страница 6: ...IL BAT FAIL Battery and AC Supervision Circuit power limited Battery connection non power limited Door Wire Strap from Enclosure to Door DC Output to devices power limited Fire Alarm Interface Insulat...

Страница 7: ...approximately 21VDC N A for AL1012ULACMCB BAT Stand by battery connections AL400ULXB AL600ULXB and AL1012ULXB Power Supply Board maximum charge current is 7 amp AL1024ULXB Power Supply Board maximum c...

Страница 8: ...ching FACP trigger input with reset This output has not been evaluated by UL Fig 4 Polarity reversal input from FACP signaling circuit output polarity is referenced in alarm condition Fig 3 Optional h...

Страница 9: ...arm ______________________ A G Alarm duration Hours example 15 Min 25 Hour Alarm ______________________ H H Battery capacity required for Alarm E F G ______________________ AH I Total calculated batte...

Страница 10: ...10 ACMCBseries 875 1 0 0 0 0 10 75 1 5 6 10 5 2 0 1 25 4 5 12 15 5 4 5 4 5 1 25 1 25 14 25 13 5 10 6 625 TOP BOTTOM Enclosure Dimensions 15 5 H x 12 W x 4 5 D...

Страница 11: ...ACMCBseries 11 Notes...

Страница 12: ...Street Brooklyn New York 11220 USA 718 567 8181 fax 718 567 9056 web site www altronix com e mail info altronix com Lifetime Warranty Made in U S A IIACMCB series L06G MEMBER Altronix is not responsi...

Отзывы: