Terminal Identification Tables: 

Power Supply Board 

Terminal Legend  Function/Description 
L, N 

Connect 115VAC 60Hz to these terminals: L to hot, N to neutral. 

+ DC – 

AL400ULACM - 12VDC @ 4 amp or 24VDC @ 3 amp to ACM8 board (power-limited). 

AL600ULACM - 12VDC/24VDC @ 6 amp to ACM8 board (non power-limited). 

AL1012ULACM - 12VDC @ 10 amp to ACM8 board (non power-limited). 

AL1024ULACM - 24VDC @ 10 amp to ACM8 board (non power-limited). 

AC FAIL 

NC, C, NO 

Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay normally 

energized when AC power is present. Contact rating 1 amp @ 28VDC. AC or brownout fail is 

reported within 1 minute of event. To delay reporting of up to 6 hrs. cut “AC delay” jumper and 

reset power to unit. 

BAT FAIL 

NC, C, NO 

Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally energized when 

DC power is present. Contact rating 1 amp @ 28VDC. A removed battery is reported within 5 min­

utes. Battery reconnection is reported within 1 minute. 

Low battery threshold: 

12VDC output threshold set @ approximately 10.5VDC (N/A for AL1024ULACM), 

24VDC output threshold set @ approximately 21VDC (N/A for AL1012ULACM). 

+ BAT – 

Stand-by battery connections. AL400ULXB2, AL600ULXB and AL1012ULXB 

(Power Supply Board) maximum charge current is 0.7 amp. AL1024ULXB2 

(Power Supply Board) maximum charge current is 3.6 amp. 

ACM8 Access Power Controller 

Terminal Legend 

Function/Description 

– Power  + 

12VDC or 24VDC input from power supply board. 

– C 

These terminals can be connected to a separate power-limited UL Listed power supply to 

provide isolated operating power for the ACM8 (jumpers J1and J2 Must be removed). 

TRIGGER 

INPUT 1 - INPUT 8 

IN, GND 

From normally open and/or open collector sink trigger inputs 

(request to exit buttons, exit pir’s, etc.). 

OUTPUT 1 -

OUTPUT 8 

NC, C, NO, COM 

12 to 24 volts AC/DC trigger controlled outputs: 

Fail-Safe [NC positive (+) & COM Negative (-)], 

Fail-Secure [NO positive (+) & COM Negative (-)], 

Auxiliary output [C positive (+) & COM Negative (-)] 

(When using AC power supplies polarity need not be observed), 

NC, C, NO become form “C” 5 amp 24VAC/VDC rated dry outputs when fuses are removed. 

Contacts shown in a non-triggered state. 

FACP INTERFACE 

T, + INPUT  – 

Fire Alarm Interface trigger input from FACP. Trigger inputs can be normally open, 

normally closed from an FACP output circuit (Fig. 4 through 8, pg. 8)

FACP INTERFACE 

NC, C, NO 

Form “C” relay contact rated @ 1 amp 28VDC for alarm reporting. 

(This output has not been evaluated by UL). 

ACM series 

- 7 ­

                                Available from A1 Security Cameras           

   www.a1securitycameras.com email:[email protected]

Содержание AL1012ULACM

Страница 1: ...4 amp 12VDC or 24VDC 6 amp or 24VDC 3 amp Fused Outputs Fused Outputs AL1012ULACM AL1024ULACM 12VDC 10 amp 24VDC 10 amp Fused Outputs Fused Outputs For a red enclosure add an R suffix to the part e g...

Страница 2: ...r inputs external power supply is required current is determined by the power supply connected not to exceed a maximum of 10 amp total Eight 8 Access Control System trigger inputs Input options a Eigh...

Страница 3: ...y 5 mins Alarm 24 hr Stand by 5 mins Alarm 12VDC SW1 ON 40AH 5 5 amp 5 5 amp 0 5 amp 5 5 amp 24VDC SW1 OFF 40AH 5 75 amp 5 75 amp 0 75 amp 5 75 amp AL1012ULACM Voltage Switch Position Stand by Battery...

Страница 4: ...and C FACP for normally closed output 9 Battery Connections Fig 2 pg 6 For Access Control applications batteries are optional If batteries are not used a loss of AC will result in the loss of output...

Страница 5: ...NO C NC FACP Intact Dry Input Cut Wet Input O N 1 2 3 4 O N Fig 1b 1 2 3 4 Enabled Disabled FACP Interface SW1 SW8 ON ON 1 1 J2 Control J1 Intact One P S Input Intact DC Input Cut Dual P S Input NC C...

Страница 6: ...CAUTION Optional rechargeable stand by batteries must match the power supply output voltage setting Optional Rechargeable Stand by Battery Optional Rechargeable Stand by Battery OFF 24V ON 12V ON NC...

Страница 7: ...s AL400ULXB2 AL600ULXB and AL1012ULXB Power Supply Board maximum charge current is 0 7 amp AL1024ULXB2 Power Supply Board maximum charge current is 3 6 amp ACM8 Access Power Controller Terminal Legend...

Страница 8: ...nced in alarm condition Fig 3 Optional hook up using two 2 isolated power supply inputs J2 J1 CUT JUMPERS J1 AND J2 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC LOCK POWER ISOLATED POWER INPUT 12 OR 24 VA...

Страница 9: ...in 0 25 Hour Alarm ___________________ H H Battery capacity required for Alarm E F G ___________________ AH I Total calculated battery capacity D H ___________________ AH J Battery capacity required I...

Страница 10: ...5mm 4 5 114 3mm 1 25 31 75mm 4 5 114 3mm 1 25 31 75mm 1 25 31 75mm 31 75mm 1 1 27 94mm 1 1 27 94mm 0 79 20 06mm 1 1 27 94mm 0 91 23 114mm 0 91 23 114mm 1 375 34 925mm 1 125 28 575mm 15 5 393 7mm 4 615...

Страница 11: ...Notes ACM series 11 Available from A1 Security Cameras www a1securitycameras com email sales a1securitycameras com...

Страница 12: ...t Brooklyn New York 11220 USA 718 567 8181 fax 718 567 9056 web site www altronix com e mail info altronix com Lifetime Warranty Made in U S A IIACM series J09O MEMBER 12 ACM series Available from A1...

Отзывы: