(b)  Form “C” outputs: 

When form “C” outputs are desired the corresponding output fuse (1-8) must be removed. Connect negative (–) 

of the power supply directly to the locking device. Connect the positive (+) of the power supply to the terminal 

marked [C]. For Fail-Safe operation connect the positive (+) of the device being powered to the terminal 

marked NC]. For Fail-Secure operation connect the positive (+) of the device being powered to the 

terminal marked [NO]. 

(c)  Auxiliary Power outputs (unswitched): 

Connect positive (+) input of the device being powered to the terminal marked [C] and the negative (–) of the 

device being powered to the terminal marked [COM]. Output can be used to provide power for card readers, 

keypads, 

etc. 

6.  

Input trigger options (Fig. 1, pg. 5)

(a)  Normally Open [NO] input trigger: 

Inputs 1-8 are activated by normally open or open collector sink inputs. 

Connect devices (card readers, keypads, request to exit buttons etc.) to terminals marked [IN] and [GND].

(b)  Open Collector Sink inputs: 

Connect the access control panel open collector sink positive (+) to the terminal marked [IN] and the negative (–) 

to the terminal marked [GND]. 

7.  

Fire Alarm Interface options (Figs. 4 through 8, pg. 8)

A normally closed [NC], normally open [NO] input or polarity reversal input from FACP signaling circuit will 

trigger selected outputs. To enable FACP Disconnect for an output turn the corresponding switch [SW1-SW8] OFF. 

To disable FACP disconnect for an output turn the corresponding switch [SW1-SW8] ON. 

(a)  Normally Open [NO] input: 

For non-latching hook-up (Fig. 5, pg. 8). For latching hook-up (Fig. 6, pg. 8)

(b)  Normally Closed [NC] input: 

For non-latching hook-up (Fig. 7, pg. 8). For latching hook-up (Fig. 8, pg. 8)

(c)  FACP Signaling Circuit input trigger: 

Connect the positive (+) and negative (–) from the FACP signaling circuit output to the terminals marked [+ INP –]. 

Connect the FACP EOL to the terminals marked [+ RET –] (polarity is referenced in an alarm condition). 

Jumper located next to TRG LED must be cut (Fig. 1a, pg. 5)

8.  

FACP Dry form “C” output (Fig. 1a, pg. 5)

Connect desired device to be triggered by the unit’s dry contact output to the terminals marked [NO] and [C] 

FACP for normally open output or the terminals marked [NC] and [C] FACP for normally closed output. 

9.  

Battery Connections (Fig. 2, pg. 6)

For Access Control applications batteries are optional. If batteries are not used, a loss of AC will result in the loss of 

output voltage. Batteries must be lead acid or gel type. Connect one (1) 12VDC battery to the terminals marked 

[+ BAT -] for 12VDC operation. Use two (2) 12VDC batteries wired in series for 24VDC operation. 

10.  

Battery and AC Supervision output (Fig. 2, pg. 6)

It is required to connect supervisory trouble reporting devices to outputs marked [AC Fail, BAT FAIL] supervisory 

relay outputs marked [NC, C, NO] to appropriate notification devices. Use 22 AWG to 18 AWG for AC Fail & 

Low/No Battery reporting. Cut “AC delay” jumper to delay report for 6 hours. 

Note: A tamper switch must be installed and connected to the appropriate notification device to report a 

trouble condition when the enclosure door is open. 

11.  

Multiple power supply inputs (Fig. 1, pg. 5)

When using two (2) power supplies jumpers J1 and J2 (located to the left of the power/control terminals) must 

be cut (Fig. 1c, pg. 5 & Fig. 3 pg. 8). Connect power for the ACM8 to the terminals marked [– C] and 

connect power for the locking devices to the terminals marked [– Power +]. When using DC power supplies polarity 

must be observed. When using AC power supplies polarity need not be observed (Fig. 1d, pg. 5)

Note: For UL compliance the additional power supply must be power-limited, UL Listed for Access Control 

Systems and accessories. 

Maintenance: 

Unit should be tested at least once a year for the proper operation as follows: 

Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level

(Output Voltage and Stand-by Specification Charts, pg. 3). 

Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage at the battery 

terminals and at the board terminals marked [– BAT +] to ensure that there is no break in the battery connection wires. 

Note:  AL400ULXB2, AL600ULXB, AL1012ULXB (Power Supply Board) maximum charge current is 0.7 amp. 

AL1024ULXB2 

(Power Supply Board) maximum charge current is 3.6 amp. 

Expected battery life is 5 years, however it is recommended to change batteries within 4 years or less if necessary. 

- 4 - 

ACM series 

                                Available from A1 Security Cameras           

   www.a1securitycameras.com email:[email protected]

Содержание AL1012ULACM

Страница 1: ...4 amp 12VDC or 24VDC 6 amp or 24VDC 3 amp Fused Outputs Fused Outputs AL1012ULACM AL1024ULACM 12VDC 10 amp 24VDC 10 amp Fused Outputs Fused Outputs For a red enclosure add an R suffix to the part e g...

Страница 2: ...r inputs external power supply is required current is determined by the power supply connected not to exceed a maximum of 10 amp total Eight 8 Access Control System trigger inputs Input options a Eigh...

Страница 3: ...y 5 mins Alarm 24 hr Stand by 5 mins Alarm 12VDC SW1 ON 40AH 5 5 amp 5 5 amp 0 5 amp 5 5 amp 24VDC SW1 OFF 40AH 5 75 amp 5 75 amp 0 75 amp 5 75 amp AL1012ULACM Voltage Switch Position Stand by Battery...

Страница 4: ...and C FACP for normally closed output 9 Battery Connections Fig 2 pg 6 For Access Control applications batteries are optional If batteries are not used a loss of AC will result in the loss of output...

Страница 5: ...NO C NC FACP Intact Dry Input Cut Wet Input O N 1 2 3 4 O N Fig 1b 1 2 3 4 Enabled Disabled FACP Interface SW1 SW8 ON ON 1 1 J2 Control J1 Intact One P S Input Intact DC Input Cut Dual P S Input NC C...

Страница 6: ...CAUTION Optional rechargeable stand by batteries must match the power supply output voltage setting Optional Rechargeable Stand by Battery Optional Rechargeable Stand by Battery OFF 24V ON 12V ON NC...

Страница 7: ...s AL400ULXB2 AL600ULXB and AL1012ULXB Power Supply Board maximum charge current is 0 7 amp AL1024ULXB2 Power Supply Board maximum charge current is 3 6 amp ACM8 Access Power Controller Terminal Legend...

Страница 8: ...nced in alarm condition Fig 3 Optional hook up using two 2 isolated power supply inputs J2 J1 CUT JUMPERS J1 AND J2 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC LOCK POWER ISOLATED POWER INPUT 12 OR 24 VA...

Страница 9: ...in 0 25 Hour Alarm ___________________ H H Battery capacity required for Alarm E F G ___________________ AH I Total calculated battery capacity D H ___________________ AH J Battery capacity required I...

Страница 10: ...5mm 4 5 114 3mm 1 25 31 75mm 4 5 114 3mm 1 25 31 75mm 1 25 31 75mm 31 75mm 1 1 27 94mm 1 1 27 94mm 0 79 20 06mm 1 1 27 94mm 0 91 23 114mm 0 91 23 114mm 1 375 34 925mm 1 125 28 575mm 15 5 393 7mm 4 615...

Страница 11: ...Notes ACM series 11 Available from A1 Security Cameras www a1securitycameras com email sales a1securitycameras com...

Страница 12: ...t Brooklyn New York 11220 USA 718 567 8181 fax 718 567 9056 web site www altronix com e mail info altronix com Lifetime Warranty Made in U S A IIACM series J09O MEMBER 12 ACM series Available from A1...

Отзывы: