ACMS8/CB Sub-Assembly 

- 3 -

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code NFPA 70/NFPA 72/ ANSI / Canadian 
Electrical Code / CAN/ULC-S524/ULC-S527/ULC-S537, and with all local codes and authorities having 
jurisdiction. Product is intended for indoor dry use only.
1.  Refer to Sub-Assembly Installation Instruction for mounting Rev. MS050913.
  Carefully review: 
  Terminal Identification Table 

(pg. 4) 

Typical Application Diagram 

(pg. 7)

  LED Diagnostics 

(pg. 4) 

Hook-up Diagrams 

(pg. 8-9)

2.  Ensure all output jumpers [OUT1] - [OUT8] are placed in the OFF (center) position.
3.  Connect low voltage DC power supplies to terminals marked [+ PWR1 –], [+ PWR2 –] 
4.  Set each output [OUT1] - [OUT8] to route power from power supply 1 or 2 
 

(Fig. 1, pg. 3).

 

Note:  Measure output voltage before connecting devices. 

        This helps avoiding potential damage.
5.  Turn power off before connecting devices.
6.  Output options: The ACMS8(CB) will provide up to eight (8) switched power
  outputs or eight (8) dry form “C” outputs, or any combination of both switched
  power and form “C” outputs, plus eight (8) unswitched auxiliary power outputs.
 

Switched Power outputs:

    Connect the negative (–) input of the device being powered to the terminal marked [COM].
    •  For Fail-Safe operation connect the positive (+) input of the device being powered to the terminal 
      marked [NC].
    •  For Fail-Secure operation connect the positive (+) input of the device being powered to the terminal 
      marked [NO].
 

Form “C” outputs:

    When form “C” outputs are desired, the corresponding jumper (1-8) must be placed in the OFF position 
  (Fig. 1, pg. 3). Alternatively, the corresponding output fuse (1-8) can be removed (ACMS8 only).
    Connect negative (–) of the power supply directly to the locking device. 
    Connect the positive (+) of the power supply to the terminal marked [C].
    •  For Fail-Safe operation connect the positive (+) of the device being powered to the terminal 
      marked [NC].
    •  For Fail-Secure operation connect the positive (+) of the device being powered to the terminal 
      marked [NO].
  Dry contacts rated @ 3A.
 

Auxiliary Power outputs (unswitched):

    Connect positive (+) input of the device being powered to the terminal marked [C] and the negative (–) 
    of the device being powered to the terminal marked [COM]. Output can be used to provide power for 
    card readers, keypads etc.
7.  Turn main power on after all devices are connected
8.  Input Trigger options:
 

Note: If Fire Alarm disconnect is not used, connect a 10K ohm resistor to terminals marked [GND and EOL],

  plus connect a jumper to terminals marked [GND, RST].
 

Normally Open (NO) Input:

    Slide input control logic DIP switch into the ON position for [Switch 1-8] 
  (Fig. 2, on right). Connect your wires to terminals marked 
    [+ INP1 –] to [+ INP8 –].
 

Normally Closed (NC) Input:

    Slide input control logic DIP switch into the OFF position for [Switch 1-8] 
  (Fig. 2, on right). Connect your wires to terminals marked 
    [+ INP1 –] to [+ INP8 –].
 

Open Collector Sink Input:

    Connect the open collector sink input to the terminal marked 
    [+ INP1 –] to [+ INP8 –].
 

Wet (Voltage) Input Configuration:

 

  Carefully observing polarity, connect the voltage input trigger wires and the supplied 10K resistor to 

 

  terminals marked [+ INP1 –] to [+ INP8 –].

 

  If applying voltage to trigger input - set the corresponding INP Logic switch to the “OFF” position

    If removing voltage to trigger input - set the corresponding INP Logic switch to the “ON” position.

1

2

3

4

ON

INP Logic

NO <-- > NC

PWR1

PWR2

OFF

Fig. 1

Fig. 2

Содержание ACMS8 Series

Страница 1: ...Rev 102617 ACMS8 Series Sub Assembly Access Power Controllers Installation Guide Models Include ACMS8 Eight 8 Fuse Protected Outputs ACMS8CB Eight 8 PTC Protected Outputs More than just power TM ...

Страница 2: ... supply ratings ACMS8CB PTC protected outputs rated 2A per output Class 2 power limited Total output 16A max Do not exceed the individual power supply ratings Total output current should not exceed max current rating of the power supplies employed on each input See Maximum Output of Altronix Power Supplies Eight 8 selectable independently controlled outputs or eight 8 indepently controlled Form C ...

Страница 3: ...tively the corresponding output fuse 1 8 can be removed ACMS8 only Connect negative of the power supply directly to the locking device Connect the positive of the power supply to the terminal marked C For Fail Safe operation connect the positive of the device being powered to the terminal marked NC For Fail Secure operation connect the positive of the device being powered to the terminal marked NO...

Страница 4: ...triggered by the unit s dry contact output to the terminals marked NC and C When EOL JMP is kept intact the output is of 0 Ohm resistance in a normal condition When EOL JMP is clipped a 10k resistance will be passed to next device when in a normal condition LED Diagnostics ACMS8 and ACMS8CB Access Power Controller LED ON OFF LED 1 LED 8 Red Output relay s de energized Output relay s energized FACP...

Страница 5: ...P3 INP4 INP5 INP6 INP7 INP8 3 3 3 3 3 3 3 3 3 ACMS8 ACMS8CB Altronix Corp Brooklyn NY 11220 1 2 3 4 ON 3 PWR1 PWR2 COM COM 5 6 7 8 1 2 3 4 5 6 7 8 ON ON ON PWR2 OFF PWR1 PWR2 NC RST EOL F R C GND GND F R NO C NC COM NO C NC COM Output 1 Output 2 NO C NC COM NO C NC COM Output 3 Output 4 NO C NC COM NO C NC COM Output 5 Output 6 NO C NC COM NO C NC COM Output 7 Output 8 OUT1 RISK OF FIRE REPLACE FU...

Страница 6: ...1 of ACMS8 CB Thus Input 1 of ACMS8 CB is 24VDC from power supply and Input 2 is determined by VR6 s settings 5VDC or 12VDC 6 Complete steps 4 10 pgs 3 4 Power Input Output Input 24VDC 1 75A Output 5VDC 6A Input 24VDC 3 5A Output 12VDC 6A Output 5VDC or 12VDC regulated output Output rating 6A max Surge suppression LED Indicators Input and output LEDs Electrical Operating temperature 0ºC to 49ºC am...

Страница 7: ...ooklyn NY 11220 1 2 3 4 ON 3 PWR1 PWR2 COM COM 5 6 7 8 1 2 3 4 5 6 7 8 ON ON ON PWR2 OFF PWR1 PWR2 NO C NC COM NO C NC COM Output 1 Output 2 NO C NC COM NO C NC COM Output 3 Output 4 NO C NC COM NO C NC COM Output 5 Output 6 NO C NC COM NO C NC COM Output 7 Output 8 FACP FACP EOL JMP NC RST EOL F R C GND GND F R NC NO C Normally Open N O Door Releasing Device Access Control Panel Output Relay Mag ...

Страница 8: ...ngle Reset FACP FACP NC RST EOL F R C GND GND F R FACP FACP Jumper Jumper NC RST EOL F R C GND GND F R EOL JMP EOL JMP FACP FACP NC RST EOL F R C GND GND F R FACP FACP Jumper NC RST EOL F R C GND GND F R EOL JMP EOL JMP N O Switch FACP FACP NC RST EOL F R C GND GND F R FACP FACP NC RST EOL F R C GND GND F R EOL JMP EOL JMP N O Switch N O Switch Fig 9 Daisy chaining one or more ACMS8 units EOL Jump...

Страница 9: ...n Latching FACP FACP N O Switch EOL NC RST EOL F R C GND GND F R Hook Up Diagrams FACP FACP Jumper 10K EOL NC RST EOL F R C GND GND F R Fig 12 Normally Closed trigger input Non Latching FACP FACP Jumper 10K EOL NC RST EOL F R C GND GND F R Fig 13 Normally Closed trigger input Latching FACP FACP NC RST EOL F R C GND GND F R N O Switch Jumper EOL Fig 14 Normally Open trigger input Non Latching FACP ...

Страница 10: ... 10 ACMS8 CB Sub Assembly Notes ...

Страница 11: ...ACMS8 CB Sub Assembly 11 Notes ...

Страница 12: ...not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warranty Made in U S A IIACMS8 ACMS8CB C20R MEMBER Notes ...

Отзывы: