ACMCB220 series
- 9 -
AL1024ACMCB220 Battery Size Calculation Worksheet:
A. AL1024ACMCB220 internal current consumption
(stand-by)
_____________________________ 0.35 A
B. Load current consumption
(stand-by)
_____________________________ A
C. Stand-by time required (Hours)
_____________________________ H
D. Battery capacity required for stand-by
(A+B)*C
_____________________________ AH
E. AL1024ACMCB220 internal power consumption
(Alarm)
_____________________________ 0.35 A
F. Load current consumption
(Alarm)
_____________________________ A
G. Alarm duration (Hours, example: 15 Min. = 0.25 Hour) (Alarm)
_____________________________ H
H. Battery capacity required for Alarm
(E+F)*G
_____________________________ AH
I. Total calculated battery capacity
D+H
_____________________________ AH
J. Battery capacity required
I*1.8 (safety factor) _____________________________ AH
Note: AL1024ACMCB220 power supply is designed to work with batteries up to 65AH. Please note, line [I]
must not exceed 36AH. You have to reduce either stand-by current consumption or stand-by time in
order to comply with requirement.
To determine actual battery size please round line [J] to the nearest larger standard battery size.
Содержание ACMCB220 Series
Страница 11: ...ACMCB220 series 11 Notes Notes ...