Altronix ACMCB220 Series Скачать руководство пользователя страница 4

 

- 4 -  

ACMCB220 series

  (b) Auxiliary Power outputs (unswitched):

   

Connect positive (+) input of the device being powered to the terminal marked [C] and the negative (–) of the 

   

device being powered to the terminal marked [COM]. Output can be used to provide power for card readers,

   

keypads etc.

6. 

Input trigger options (Fig. 1, pg. 5):

  (a) Normally Open [NO] input trigger:

   

Inputs 1-8 are activated by normally open or open collector sink inputs.

   

Connect devices (card readers, keypads, request to exit buttons etc.) to terminals marked [IN] and [GND]. 

  (b) Open Collector Sink inputs:

   

Connect the access control panel open collector sink positive (+) to the terminal marked [IN] and the negative (–)

   

to the terminal marked [GND].

7. 

Fire Alarm Interface options (Figs. 4 through 8, pg. 8)

  A normally closed [NC], normally open [NO] input or polarity reversal input from FACP signaling circuit will

  trigger selected outputs. To enable FACP Disconnect for an output open the corresponding switch [SW1-SW8]. 

  To disable FACP disconnect for an output close the corresponding switch [SW1-SW8].

  (a) Normally Open [NO] input:

   

For non-latching hook-up (Fig. 5, pg. 8). For latching hook-up (Fig. 6, pg. 8).

  (b) Normally Closed [NC] input:

   

For non-latching hook-up (Fig. 7, pg. 8). For latching hook-up (Fig. 8, pg. 8).

  (c) FACP Signaling Circuit input trigger:

   

Connect the positive (+) and negative (–) from the FACP signaling circuit output to the terminals marked [+ INP –]. 

   

Connect the FACP EOL to the terminals marked [+ RET –] (polarity is referenced in an alarm condition).

   

Jumper J3 must be cut (Fig. 4, pg. 8)

8. 

FACP Dry form “C” output (Fig. 1a, pg. 5):

  Connect desired device to be triggered by the unit’s dry contact output to the terminals marked [NO] and [C] 

  FACP for normally open output or the terminals marked [NC] and [C] FACP for normally closed output.

9. 

Battery Connections (Fig. 2, pg. 6):

  For Access Control applications batteries are optional. If batteries are not used, a loss of AC will result in the loss of 

  output voltage. Batteries must be lead acid or gel type. Connect one (1) 12VDC battery to the terminals marked 

  [+ BAT -] for 12VDC operation. Use two (2) 12VDC batteries wired in series for 24VDC operation. 

10. 

Battery and AC Supervision output (Fig. 2, pg. 6):

  It is required to connect supervisory trouble reporting devices to outputs marked [AC Fail, BAT FAIL] and 

  supervisory  relay outputs marked [NC, C, NO] to appropriate notification devices. Use 22 AWG to 18 AWG for AC 

  Fail & Low/No Battery reporting. Cut “AC delay” jumper to delay report for 6 hours.

 Note: A tamper switch must be installed and connected to the appropriate notification device to report a

  trouble condition when the enclosure door is open. 

11. 

Multiple power supply inputs (Fig. 1, pg. 5):

  When using two (2) power supplies, jumpers J1 and J2 (located to the left of the power/control terminals) must 

  be cut (Fig. 1b, pg. 5 & Fig. 3 pg. 8). Connect power for the ACM8 to the terminals marked [– C] and 

  connect power for the locking devices to the terminals marked [– Power +]. When using DC power supplies polarity 

  must be observed. When using AC power supplies polarity need not be observed.

 

Note: For UL compliance the additional power supply must be power-limited, UL Listed for Access Control 

  Systems and accessories.

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper voltage level 

(Output Voltage and Stand-by Specification Charts, pg. 3).

Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage at the battery 

terminals and at the board terminals marked [– BAT +] to ensure that there is no break in the battery connection wires.
Note:  AL400XB2V, AL600XB220, AL1012XB220 (Power Supply Board) maximum charge current is 0.7 amp. 
 

AL1024XB220 (Power Supply Board) maximum charge current is 3.6 amp.

Expected battery life is 5 years; however, it is recommended to change batteries within 4 years or less if necessary.

Содержание ACMCB220 Series

Страница 1: ...L400ACMCB220 AL600ACMCB220 12VDC 4 amp 12VDC or 24VDC 6 amp or 24VDC 3 amp PTC Protected Outputs PTC Protected Outputs AL1012ACMCB220 AL1024ACMCB220 12VDC 10 amp 24VDC 10 amp PTC Protected Outputs PTC Protected Outputs Rev 010213 For a red enclosure add an R suffix to the part e g AL1024ACMCBR220 ...

Страница 2: ...wer inputs external power supply is required current is determined by the power supply connected not to exceed a maximum of 10 amp total Eight 8 Access Control System trigger inputs Input options a Eight 8 normally open NO inputs b Eight 8 open collector inputs c Any combination of the above Eight 8 independently controlled outputs Fail Safe and or Fail Secure power outputs Eight 8 auxiliary power...

Страница 3: ...tage Switch Position Stand by Battery 4 hr Stand by 5 mins Alarm 24 hr Stand by 5 mins Alarm 12VDC SW1 Closed 40AH 5 5 amp 5 5 amp 0 5 amp 5 5 amp 24VDC SW1 Open 40AH 5 75 amp 5 75 amp 0 75 amp 5 75 amp AL1012ACMCB220 Voltage Switch Position Stand by Battery 4 hr Stand by 5 mins Alarm 24 hr Stand by 5 mins Alarm 12VDC N A 40AH 9 5 amp 9 5 amp 0 5 amp 9 5 amp AL1024ACMCB220 refer to AL1024ACM220 Ba...

Страница 4: ...AC will result in the loss of output voltage Batteries must be lead acid or gel type Connect one 1 12VDC battery to the terminals marked BAT for 12VDC operation Use two 2 12VDC batteries wired in series for 24VDC operation 10 Battery and AC Supervision output Fig 2 pg 6 It is required to connect supervisory trouble reporting devices to outputs marked AC Fail BAT FAIL and supervisory relay outputs ...

Страница 5: ...N GND 3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3 LED4 LED5 LED6 LED7 LED8 J2 J1 TRG NC C NO COM OUTPUT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6 NO C NC INP T RET NC C NO COM OUTPUT 7 NC C NO COM OUTPUT 8 Power Control F2 F3 F6 F7 F8 F4 F5 J3 J2 J1 3 5A 250V 3 5A 250V 3 5A 250V 3 5A 250V 3 5A 250V 3 5A 250V 3 5A 250V 3 5A 250V FACP INTERFACE 10A 250V NC NO...

Страница 6: ...Y Battery and AC Supervision Circuit Door Wire Strap from Enclosure to Door DC Output to devices Fire Alarm Interface Insulating Barrier Inputs unswitched 220VAC power mains Keep power limited wiring separate from non power limited Use minimum 0 25 spacing CAUTION Optional rechargeable stand by batteries must match the power supply output voltage setting Earth Ground Optional Rechargeable Stand by...

Страница 7: ...1012ULACM BAT Stand by battery connections AL400XB2V AL600XB220 and AL1012XB220 Power Supply Board maximum charge current is 0 7 amp AL1024XB220 Power Supply Board maximum charge current is 3 6 amp ACM8 Access Power Controller Terminal Legend Function Description Power 12VDC or 24VDC input from power supply board Control These terminals can be connected to a separate power limited UL Listed power ...

Страница 8: ...ut from FACP signaling circuit output polarity is referenced in alarm condition Fig 3 Optional hook up using two 2 isolated power supply inputs J2 J1 CUT JUMPERS J1 AND J2 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC LOCK POWER ISOLATED POWER INPUT 12 OR 24 VAC OR VDC ACM8 POWER CUT JUMPER J3 FROM FACP OUTPUT CIRCUIT FACP OUTPUT EOL TRG J3 NO C NC FACP INTERFACE JUMPER N C DRY TRIGGER INPUT TRG J3 NO ...

Страница 9: ...ion Alarm ______________________________ A G Alarm duration Hours example 15 Min 0 25 Hour Alarm ______________________________ H H Battery capacity required for Alarm E F G ______________________________ AH I Total calculated battery capacity D H ______________________________ AH J Battery capacity required I 1 8 safety factor ______________________________ AH Note AL1024ACMCB220 power supply is ...

Страница 10: ...0 127 0mm 1 5 38 1mm 2 0 50 8mm 2 0 50 8mm 1 75 44 45mm 1 75 44 45mm 4 5 114 3mm 1 25 31 75mm 4 5 114 3mm 1 25 31 75mm 1 25 31 75mm 1 25 31 75mm 1 1 27 94mm 1 1 27 94mm 0 79 20 06mm 1 1 27 94mm 0 91 23 114mm 0 91 23 114mm 1 375 34 925mm 1 125 28 575mm 15 5 393 7mm 4 615 117 22mm 12 23 310 64mm 4 615 117 22mm 1 5 38 1mm 1 5 38 1mm 4 615 117 22mm 4 615 117 22mm ...

Страница 11: ...ACMCB220 series 11 Notes Notes ...

Страница 12: ...t responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA 718 567 8181 fax 718 567 9056 web site www altronix com e mail info altronix com Lifetime Warranty Made in U S A IIACMCB220 series G01N MEMBER Notes ...

Отзывы: