ACMCB220 Series

Access Power Controllers

with Power Supplies

Installation Guide

Models Include:

  • AL400ACMCB220 

• AL600ACMCB220

    -  12VDC @ 4 amp 

  -  12VDC or 24VDC @ 6 amp.

      or 24VDC @ 3 amp 

  -  PTC Protected Outputs 

 

    -  PTC Protected Outputs 

 

    
  • AL1012ACMCB220 

• AL1024ACMCB220

  - 

12VDC @ 10 amp.  

 

24VDC @ 10 amp.

  

PTC Protected Outputs 

 

PTC Protected Outputs

Rev. 010213

For a red enclosure add an “R” suffix to the part # e.g. AL1024ACMCBR220

Содержание ACMCB220 Series

Страница 1: ...L400ACMCB220 AL600ACMCB220 12VDC 4 amp 12VDC or 24VDC 6 amp or 24VDC 3 amp PTC Protected Outputs PTC Protected Outputs AL1012ACMCB220 AL1024ACMCB220 12VDC 10 amp 24VDC 10 amp PTC Protected Outputs PTC Protected Outputs Rev 010213 For a red enclosure add an R suffix to the part e g AL1024ACMCBR220 ...

Страница 2: ...wer inputs external power supply is required current is determined by the power supply connected not to exceed a maximum of 10 amp total Eight 8 Access Control System trigger inputs Input options a Eight 8 normally open NO inputs b Eight 8 open collector inputs c Any combination of the above Eight 8 independently controlled outputs Fail Safe and or Fail Secure power outputs Eight 8 auxiliary power...

Страница 3: ...tage Switch Position Stand by Battery 4 hr Stand by 5 mins Alarm 24 hr Stand by 5 mins Alarm 12VDC SW1 Closed 40AH 5 5 amp 5 5 amp 0 5 amp 5 5 amp 24VDC SW1 Open 40AH 5 75 amp 5 75 amp 0 75 amp 5 75 amp AL1012ACMCB220 Voltage Switch Position Stand by Battery 4 hr Stand by 5 mins Alarm 24 hr Stand by 5 mins Alarm 12VDC N A 40AH 9 5 amp 9 5 amp 0 5 amp 9 5 amp AL1024ACMCB220 refer to AL1024ACM220 Ba...

Страница 4: ...AC will result in the loss of output voltage Batteries must be lead acid or gel type Connect one 1 12VDC battery to the terminals marked BAT for 12VDC operation Use two 2 12VDC batteries wired in series for 24VDC operation 10 Battery and AC Supervision output Fig 2 pg 6 It is required to connect supervisory trouble reporting devices to outputs marked AC Fail BAT FAIL and supervisory relay outputs ...

Страница 5: ...N GND 3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3 LED4 LED5 LED6 LED7 LED8 J2 J1 TRG NC C NO COM OUTPUT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6 NO C NC INP T RET NC C NO COM OUTPUT 7 NC C NO COM OUTPUT 8 Power Control F2 F3 F6 F7 F8 F4 F5 J3 J2 J1 3 5A 250V 3 5A 250V 3 5A 250V 3 5A 250V 3 5A 250V 3 5A 250V 3 5A 250V 3 5A 250V FACP INTERFACE 10A 250V NC NO...

Страница 6: ...Y Battery and AC Supervision Circuit Door Wire Strap from Enclosure to Door DC Output to devices Fire Alarm Interface Insulating Barrier Inputs unswitched 220VAC power mains Keep power limited wiring separate from non power limited Use minimum 0 25 spacing CAUTION Optional rechargeable stand by batteries must match the power supply output voltage setting Earth Ground Optional Rechargeable Stand by...

Страница 7: ...1012ULACM BAT Stand by battery connections AL400XB2V AL600XB220 and AL1012XB220 Power Supply Board maximum charge current is 0 7 amp AL1024XB220 Power Supply Board maximum charge current is 3 6 amp ACM8 Access Power Controller Terminal Legend Function Description Power 12VDC or 24VDC input from power supply board Control These terminals can be connected to a separate power limited UL Listed power ...

Страница 8: ...ut from FACP signaling circuit output polarity is referenced in alarm condition Fig 3 Optional hook up using two 2 isolated power supply inputs J2 J1 CUT JUMPERS J1 AND J2 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC LOCK POWER ISOLATED POWER INPUT 12 OR 24 VAC OR VDC ACM8 POWER CUT JUMPER J3 FROM FACP OUTPUT CIRCUIT FACP OUTPUT EOL TRG J3 NO C NC FACP INTERFACE JUMPER N C DRY TRIGGER INPUT TRG J3 NO ...

Страница 9: ...ion Alarm ______________________________ A G Alarm duration Hours example 15 Min 0 25 Hour Alarm ______________________________ H H Battery capacity required for Alarm E F G ______________________________ AH I Total calculated battery capacity D H ______________________________ AH J Battery capacity required I 1 8 safety factor ______________________________ AH Note AL1024ACMCB220 power supply is ...

Страница 10: ...0 127 0mm 1 5 38 1mm 2 0 50 8mm 2 0 50 8mm 1 75 44 45mm 1 75 44 45mm 4 5 114 3mm 1 25 31 75mm 4 5 114 3mm 1 25 31 75mm 1 25 31 75mm 1 25 31 75mm 1 1 27 94mm 1 1 27 94mm 0 79 20 06mm 1 1 27 94mm 0 91 23 114mm 0 91 23 114mm 1 375 34 925mm 1 125 28 575mm 15 5 393 7mm 4 615 117 22mm 12 23 310 64mm 4 615 117 22mm 1 5 38 1mm 1 5 38 1mm 4 615 117 22mm 4 615 117 22mm ...

Страница 11: ...ACMCB220 series 11 Notes Notes ...

Страница 12: ...t responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA 718 567 8181 fax 718 567 9056 web site www altronix com e mail info altronix com Lifetime Warranty Made in U S A IIACMCB220 series G01N MEMBER Notes ...