DIGITAL ANNUNCIATOR

INSTALLATION INSTRUCTIONS

DD-40NTS-O, DD-40NTS-U

DD-NTS II 5-02

WARNING:  READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR
OPERATING THE DD ANNUNCIATOR SYSTEM.  AN IMPROPERLY INSTALLED OR
OPERATING DEVICE MAY RESULT IN AN UNSAFE OPERATING CONDITION OF THE
MONITORED MACHINE WHICH CONSEQUENTLY COULD POSE THE THREAT OF
PERSONAL INJURY TO OPERATORS OR OTHER NEARBY PERSONNEL.

1.0  DESCRIPTION

1.1 The Altronic DD-40NTS digital annunciator is an electronic, 40-point monitor and shutdown

device.  The annunciator has a built-in hourmeter / tachometer with over speed protection.
A front mounted keypad serves as a user interface along with a LCD display.

1.2 The DD-40NTS annunciator system is suitable for use in Class I, Group C or D, Division 2

hazardous locations and consists of the following items:  

DD-40NTS-O Annunciator, 40 normally open points
DD-40NTS-U Annunciator, 40 normally closed or open points (can be mixed)

(requires terminal module part no. 672169-1)

691200-1

Power Supply - 10 to 30 Vdc, 50 mA max. or 100 to 400 volt negative ground
CD ignition systems.

693115-1

Cable, DB-25 (2 required for DD-40NTS-U unit only) 

693116-1

Cable, DB-9 (for RS-232 serial communications)

1.3 RS-232 / RS-485 serial communications are provided for remote engine monitoring via

modem or satellite.  Serial communications require the use of the DC power option.

1.4 For reliable operation, the following instructions must be adhered to strictly.

2.0  MOUNTING

2.1 ANNUNCIATOR UNIT - Using four #10 screws, mount the Annunciator Unit inside a control

panel or to a suitable flat surface so that the display is at a convenient viewing height.  A
drilling template is provided.  The annunciator unit box must be grounded.

NOTE:

Avoid mounting with the LCD display facing direct sunlight.  The display
temperature range is -40°F. to +175°F.

2.2 691200-1 POWER SUPPLY - The Power Supply mounts directly to the back of the

Annunciator Unit using two 8-32 x 5/16" length screws provided.

2.3 The terminal strip board (only applicable on the -U version) can be snapped on 32 or 35 mm

DIN mounting rails.

Содержание DD-40NTS-O

Страница 1: ...ed requires terminal module part no 672169 1 691200 1 Power Supply 10 to 30 Vdc 50 mA max or 100 to 400 volt negative ground CD ignition systems 693115 1 Cable DB 25 2 required for DD 40NTS U unit onl...

Страница 2: ...be connected to any passive device using contacts suchas standard switch gauges or level switches DO NOT connect sensor leads to relay contacts or to any voltage producing element b Sensors will be e...

Страница 3: ...time to allow values to be modified Otherwise selected items may only be viewed There is no similar protection for the TIMER button Class B1 and B2 timers or hourmeter MODE TYPE OF POINTS CHANNELS NOT...

Страница 4: ...ition powered applications RS 232 ASCII A 232 RS 232 Modbus RTU 232 RS 485 ASCII A 485 or RS 485 Modbus RTU 485 Use the UP and DOWN keys to select and ENTER to save 4 9 PROGRAM NODE NUMBER This select...

Страница 5: ...display reads 00 push and hold the TEST key a reading of 80 indicates satisfactory battery voltage The operating voltage may be checked when the machine is operating and the display reads 01 push and...

Страница 6: ...ansition from 00 to 01 indicates the end of the last start up tim er interval 89 Test From 01 display press and hold TEST button indicates adequate operating voltage 09 Test Press and release TEST but...

Страница 7: ...here is no drain from the battery This allows for a battery life of up to 5 years in normal operation The battery in the power supply is replaceable use ONLY Altronic part no 601952 Be sure to observe...

Страница 8: ...mand as an example The hexadecimal values for the characters are shown only as a reference for those using low level assembly language decoding and will not appear on the communications terminal scree...

Страница 9: ...ing it a half duplex system When the master is in the transmit mode the slave is in the receive mode and visa versa B ELECTRICAL OPERATING RANGE RS 485 is a communications standard to satisfy the need...

Страница 10: ...e maximum number of units connected together in a system is 99 8 8 RS 232 COMMUNICATIONS A For proper operation the wire length should not exceed 50 feet B Use standard DB 9 connector and computer cab...

Страница 11: ...ITION AND CD FUEL VALVE M50 CD WIRING DIAGRAM DC POWERED FUEL VALVE M50 B WIRING DIAGRAM DC POWERED FUEL VALVE M50 FS WIRING DIAGRAM DC POWERED RELAY WIRING DIAGRAM TACHOMETER INPUT IGNITION SHUTDOWN...

Страница 12: ......

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ...C 690040 1 AC DC CONTROL FUEL VALVE FUEL VALVE E C B D S MURPHY 221 PH CD IGNITION SHUTDOWN LEAD 12 24VDC 1 2 CAUTION LUB TERMINAL 8TH FROM LEFT REPLACES RPM TERMINAL ON THE 691200 1 POWER SUPPLY IF R...

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ......

Страница 29: ......

Страница 30: ......

Отзывы: