LOADING - RS-485 uses a balanced differential pair of wires switching from 0 to 5 volts
to communicate data.  In situations where many units (99 max.) are connected together
on a long run, voltage drop on the communications leads becomes a major problem.
Voltage drops on the RS-485 minus lead appear as a common mode voltage to the
receivers.  While the receivers are rated to a maximum voltage difference of +/

!

 7 volts,

!

7V to +12V, a practical system should not have a voltage difference exc/

!

 3

volts under normal conditions.  The wire gauge used for the connections therefore limits
the maximum number of units or the maximum length of wire between units in each
application.  The following formula can be used as a guideline to select the appropriate
wire gauge.

For 18 AWG wire

No. of annunciator units = (4000) / (ft of wire used)

For 20 AWG wire

No. of annunciator units = (3600) / (ft of wire used)

For 22 AWG wire

No. of annunciator units = (2400) / (ft of wire used) 

NOTE: The maximum number of units connected together in a system is 99.

8.8 RS-232 COMMUNICATIONS

A.

For proper operation, the wire length should not exceed 50 feet.

B.

Use standard DB-9 connector and computer cable, Altronic no. 693 116-x or equivalent.

8.9 MODBUS STRUCTURE - The annunciator can operate as a Modbus RTU slave.   A

command must be transmitted to the unit by the master (computer or PLC) before the slave
can respond with useful data.  A slave unit can never initiate a communications sequence. 

Select the Modbus communications option. See section 4.8. Communication to the
annunciator can then be performed using standard Modbus RTU protocol.  Multiple register
reads are supported, specify number of registers.   

Register

(16 bit binary register value)

40001

RPM ( 0-2500 )

40002

Hourmeter hours ( 0-65535 )

40003

Class B1 timer ( seconds )

40004

Shutdo wn S tatus  ( 0 = O K, 1 =  Fau lt )

40005

Outpu t Status ( bit 0 = SW 1, bit 1 = SW 2, 1 = tripped, 0 = running ) 

40006

Input  ( chan. 10-27; bit 0 = 10, bit 8 = 20, bit 15 = 27 )

40007

Input  ( chan. 30-47; bit 0 = 30, bit 8 = 40, bit 15 = 47 ) 

40008

Input  ( chan. 50-57; bit 0 = 50, bit 7 = 57, bit 8 = ovrspd, bit 9 = loss of sp d) 

Inpu t OK  = 1, Inp ut Fa ult = 0;  40 006 , 400 07, 4 000 8 all FF  for ru nning O K. 

Содержание DD-40NTS-O

Страница 1: ...ed requires terminal module part no 672169 1 691200 1 Power Supply 10 to 30 Vdc 50 mA max or 100 to 400 volt negative ground CD ignition systems 693115 1 Cable DB 25 2 required for DD 40NTS U unit onl...

Страница 2: ...be connected to any passive device using contacts suchas standard switch gauges or level switches DO NOT connect sensor leads to relay contacts or to any voltage producing element b Sensors will be e...

Страница 3: ...time to allow values to be modified Otherwise selected items may only be viewed There is no similar protection for the TIMER button Class B1 and B2 timers or hourmeter MODE TYPE OF POINTS CHANNELS NOT...

Страница 4: ...ition powered applications RS 232 ASCII A 232 RS 232 Modbus RTU 232 RS 485 ASCII A 485 or RS 485 Modbus RTU 485 Use the UP and DOWN keys to select and ENTER to save 4 9 PROGRAM NODE NUMBER This select...

Страница 5: ...display reads 00 push and hold the TEST key a reading of 80 indicates satisfactory battery voltage The operating voltage may be checked when the machine is operating and the display reads 01 push and...

Страница 6: ...ansition from 00 to 01 indicates the end of the last start up tim er interval 89 Test From 01 display press and hold TEST button indicates adequate operating voltage 09 Test Press and release TEST but...

Страница 7: ...here is no drain from the battery This allows for a battery life of up to 5 years in normal operation The battery in the power supply is replaceable use ONLY Altronic part no 601952 Be sure to observe...

Страница 8: ...mand as an example The hexadecimal values for the characters are shown only as a reference for those using low level assembly language decoding and will not appear on the communications terminal scree...

Страница 9: ...ing it a half duplex system When the master is in the transmit mode the slave is in the receive mode and visa versa B ELECTRICAL OPERATING RANGE RS 485 is a communications standard to satisfy the need...

Страница 10: ...e maximum number of units connected together in a system is 99 8 8 RS 232 COMMUNICATIONS A For proper operation the wire length should not exceed 50 feet B Use standard DB 9 connector and computer cab...

Страница 11: ...ITION AND CD FUEL VALVE M50 CD WIRING DIAGRAM DC POWERED FUEL VALVE M50 B WIRING DIAGRAM DC POWERED FUEL VALVE M50 FS WIRING DIAGRAM DC POWERED RELAY WIRING DIAGRAM TACHOMETER INPUT IGNITION SHUTDOWN...

Страница 12: ......

Страница 13: ......

Страница 14: ......

Страница 15: ......

Страница 16: ......

Страница 17: ......

Страница 18: ......

Страница 19: ...C 690040 1 AC DC CONTROL FUEL VALVE FUEL VALVE E C B D S MURPHY 221 PH CD IGNITION SHUTDOWN LEAD 12 24VDC 1 2 CAUTION LUB TERMINAL 8TH FROM LEFT REPLACES RPM TERMINAL ON THE 691200 1 POWER SUPPLY IF R...

Страница 20: ......

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Страница 26: ......

Страница 27: ......

Страница 28: ......

Страница 29: ......

Страница 30: ......

Отзывы: