The indoor unit should be configured by the installer to match the
installation environment (outdoor climate, installed options, etc.) and
user demand. Thereto, a number of so called field settings are
available. These field settings are accessible and programmable
through the user interface on the indoor unit.

Each field setting is assigned a 3-digit number or code, for example
[5-03], which is indicated on the user interface display. The first digit
[5] indicates the 'first code' or field setting group. The second and
third digit [03] together indicate the 'second code'.

A list of all field settings and default values is given under 

"Field

settings table" on page 15

.  In this same list, we provided for 2

columns to register the date and value of altered field settings at
variance with the default value.

A detailed description of each field setting is given under 

"Detailed

description" on page 11

.

Procedure

To change one or more field settings, proceed as follows.

1

Press the 

z

 button for a minimum of 5 seconds to enter FIELD

SET MODE.
The 

$

 icon (3) will be displayed. The current selected field

setting code is indicated 

;

 (2), with the set value displayed to

the right 

-

 (1).

2

Press the 

bgi

  button to select the appropriate field

setting first code.

3

Press the 

bgj

  button to select the appropriate field

setting second code.

4

Press the 

pfi

  button and 

pfj

  button to change

the set value of the select field setting.

5

Save the new value by pressing the 

pr

 button.

6

Repeat step 2 through 4 to change other field settings as
required.

7

When finished, press the 

z

 button to exit FIELD SET MODE.

Detailed description

[0] User permission level

If required, certain user interface buttons can be made unavailable for
the user.

Three permission levels are defined (see the table below). Switching
between level 1 and level 2/3 is done by simultaneously pressing
buttons 

pfi

  and 

pfj

  immediately followed by

simultaneously pressing buttons 

s

  and 

ba

, and keeping all 4

buttons pressed for at least 5 seconds (in normal mode). Note that no
indication on the user interface is given. When level 2/3 is selected,
the actual permission level — either level 2 or level 3 — is
determined by the field setting [0-00].

[1] Weather dependent set point (heating operation only)

The weather dependent set point field settings define the parameters
for the weather dependent operation of the unit. When weather
dependent operation is active the water temperature is determined
automatically depending on the outdoor temperature: colder outdoor
temperatures will result in warmer water and vice versa. During
weather dependent operation, the user has the possibility to shift up
or down the target water temperature by a maximum of 5°C. See

"Selecting weather dependent set point operation (only in heating
mode)" on page 6

 for more details on weather dependent operation.

[1-00] Low ambient temperature (Lo_A): low outdoor
temperature.

[1-01] High ambient temperature (Hi_A): high outdoor
temperature.

[1-02] Set point at low ambient temperature (Lo_Ti): the
target outgoing water temperature when the outdoor
temperature equals or drops below the low ambient
temperature (Lo_A). 
Note that the Lo_Ti value should be higher than Hi_Ti, as for
colder outdoor temperatures (i.e. Lo_A) warmer water is
required.

[1-03] Set point at high ambient temperature (Hi_Ti): the
target outgoing water temperature when the outdoor
temperature equals or rises above the high ambient
temperature (Hi_A). 
Note that the Hi_Ti value should be lower than Lo_Ti, as for
warmer outdoor temperatures (i.e. Hi_A) less warm water
suffices.

NOTE

Changes made to a specific field setting are only
stored when the 

pr

 button is pressed. Navigating to a

new field setting code or pressing the 

z

  button will

discard the change made.

NOTE

Before shipping, the set values have been set as
shown under 

"Field settings table" on page 15

.

When exiting FIELD SET MODE, "

88

" may be

displayed on the user interface LCD while the unit
initialises itself.

2

3

1

NOTE

Only field settings relevant for this model are
explained.

Button

Permission level

1

2

3

Quiet mode button 

s

operable

Weather dependent 
set point button

ba

operable

Schedule timer 
enable/disable button 

pr

operable

operable

Programming button 

<

operable

Time adjust buttons

pf

i

pf

j

operable

Inspection/test 
operation button 

z

operable

Содержание EKHBHE008AA3V3

Страница 1: ...OPERATION MANUAL EKHBHE008AA3V3 EKHBXE008AA3V3 Indoor unit for air to water heat pump system and options For installation WITH restricted power supply condition 6 kW ...

Страница 2: ...an coil units floor heating low temperature radiators the Daikin domestic hot water tanks and the solar option kit The AD indoor unit range consists of two main versions a heating cooling EKHBX version and a heating only EKHBH version Both versions are delivered with an integrated backup heater The backup heater only serves as a backup in case of malfunctioning of the outdoor unit or when the unit...

Страница 3: ...l start up for example Refer to Initial start up at low outdoor ambient temperatures and Re start at low outdoor ambient temperatures in the installation manual During heating operation the water temperature becomes too low and drops ot of the operation range Refer to Checking the water volume and expansion vessel pre pressure in the installation manual to minimize the backup heater operation Malf...

Страница 4: ...on will never be displayed If the solar option is installed and active the w icon will be blinking 4 EXTERNAL CONTROL ICON e This icon indicates that an external room thermostat with higher priority is controlling your installation This external room thermostat can start and stop the space heating cooling operation and change the operation mode cooling heating When an external room thermostat with...

Страница 5: ...able the schedule timer The button is also used to program the controller The function of the button depends on the actual status of the controller or on previous actions carried out by the operator If the controller is set in permission level 3 refer to Field settings on page 11 the schedule timer button will not be operable 31 TIME ADJUST BUTTON pi and pj These multi purpose buttons are used to ...

Страница 6: ...ating should only be set lower than 25 C during commissioning of the installation When set lower than 25 C only the backup heater will operate In order to avoid overheating space heating is not operable when the outdoor ambient temperature rises above a certain temperature as set through field setting 4 02 refer to Field settings on page 11 Temperature range for cooling 5 C to 22 C 3 Switch on the...

Страница 7: ...t a scheduled time Five actions can be programmed per mode These actions are repeated daily 3 Booster heating refer to Programming quiet mode booster heating or domestic water heating on page 9 Allow or disallow booster heating at a scheduled time Five actions can be programmed per mode These actions are repeated daily 4 Domestic water heating refer to Programming quiet mode booster heating or dom...

Страница 8: ...er If 2 or more actions are programmed for the same day and at the same time only the action with the highest action number will be executed You can always alter add or remove the programmed actions later When programming heating actions time and set point cooling actions are added automatically at the same time but with the predefined default cooling set point Conversely when programming cooling ...

Страница 9: ... to select x to switch cooling or heating and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation only in heating mode 10 Use the pi and pj buttons to set the correct action time 11 Repeat steps 8 to 10 to program the other actions of the selected day When all actions have been programmed make sure that the display shows the high...

Страница 10: ...ulting space cooling or space heating is carried out as follows 1 Use the button to select the operation mode cooling or heating you want to consult 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to consult by means of the pi and pj buttons The selected day is blinking 5 Press the button to c...

Страница 11: ...y will show the next day e g 2 if 1 was selected first This indicates that the day has been copied You can return to step 2 by pressing the pr button Deleting one or more programmed actions Deleting one or more programmed actions is done at the same time as storing the programmed actions When all actions for one day have been programmed make sure that the display shows the highest action number yo...

Страница 12: ...seconds in normal mode Note that no indication on the user interface is given When level 2 3 is selected the actual permission level either level 2 or level 3 is determined by the field setting 0 00 1 Weather dependent set point heating operation only The weather dependent set point field settings define the parameters for the weather dependent operation of the unit When weather dependent operatio...

Страница 13: ...erature Shift value The disinfection function field settings must be configured by the installer according to national and local regulations TDHW Domestic hot water temperature TU User set point temperature as set on the user interface TH High set point temperature 2 03 t Time Space cooling heating always has priority over the disinfection function The disinfection function is only possible when t...

Страница 14: ...revents the booster heater from repeatedly turning on and off i e chattering to maintain the domestic hot water set point temperature Note the booster heater will turn back on when the domestic hot water temperature drops 2 C fixed value below the booster heater OFF temperature 7 00 Domestic hot water step length temperature difference above the domestic hot water set point temperature before the ...

Страница 15: ...aving water temperature for cooling operation 9 03 Cooling set point lower limit minimum leaving water temperature for cooling operation 9 04 Overshoot setting defines how much the water temperature may rise above the setpoint before the compressor stops This function is only applicable in heating mode C Solar priority mode C 00 For information concerning the EKSOLHW solar kit refer to the install...

Страница 16: ...rity temperature 00 Not applicable Do not change the default value 1 01 Not applicable Do not change the default value 0 02 Not applicable Do not change the default value 0 03 Not applicable Do not change the default value 0 04 Not applicable Do not change the default value 10 6 DT for domestic water heating 00 Start 5 1 20 1 C 01 Stop 2 2 10 1 C 7 Domestic hot water step length 00 Domestic hot wa...

Страница 17: ... readout 00 Software version Read only 01 EEPROM version Read only 02 Unit model identification Read only 03 Liquid refrigerant temperature Read only C 04 Inlet water temperature Read only C First code Second code Setting name Installer setting at variance with default value Default value Range Step Unit Date Value Date Value ...

Страница 18: ...eck if the clock and the day of the week are set correctly correct if necessary DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local and national legislation Do not try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil and other parts must be done by a qua...

Страница 19: ......

Страница 20: ...4PW48442 1B Copyright Daikin ...

Отзывы: