Settings
P846/EN ST/D
MiCOM P846
(ST) 4-7
ST
Setting Range
Menu Text
Default Setting
Min. Max.
Step Size
VTS
Ι
2> Inhibit
100A
100A
1000A
20A
The setting is used to override a voltage supervision block in the event of a fault occurring
on the system with negative sequence current above this setting which could trigger the
voltage supervision logic. Default setting and setting range specified here are for a primary
CT ratio of 2000:1 A
1.3
Control and support settings
The control and support settings are part of the main menu and are used to configure the
relays global configuration. It includes submenu settings as below and are discussed in
more detail below:
•
Reset
LEDs
•
Active protection setting group
•
Password & language settings
•
Circuit breaker control
•
Communications
settings
•
Measurement
settings
•
Event & fault record settings
•
User interface settings
•
Commissioning
settings
1.3.1
System data
This menu provides information for the device and general status of the relay.
Setting Range
Menu Text
Default Setting
Min. Max.
Step Size
Language
English
The default language used by the device. Selectable as English, French, German,
Russian, Spanish.
Password
****
Device default password.
Sys. Fn. Links
0
1
Setting to allow the fixed function trip LED to be self resetting.
Description
MiCOM P846
16 character relay description. Can be edited.
Plant Reference
MiCOM
Associated plant description and can be edited.
Model Number
P846318A4N0300J
Relay model number. This display cannot be altered.
Serial Number
149188B
Relay model number. This display cannot be altered.
Frequency
50 Hz
10 Hz
Relay set frequency. Settable between 50 and 60 Hz
Содержание MiCOM P846
Страница 2: ......
Страница 4: ......
Страница 5: ...Safety Section P846 EN SS H11 SS SAFETY SECTION...
Страница 6: ...P846 EN SS H11 Safety Section SS...
Страница 8: ...P846 EN SS H11 Safety Section SS 2 SS...
Страница 16: ...P846 EN IT D Introduction MiCOM P846 IT...
Страница 18: ...P846 EN IT D Introduction IT 1 2 MiCOM P846 IT...
Страница 26: ...P846 EN TD D Technical Data MiCOM P846 TD...
Страница 38: ...P846 EN GS D Getting Started MiCOM P846 GS...
Страница 58: ...P846 EN ST D Getting Started MiCOM P846 ST...
Страница 60: ...P846 EN ST D Settings ST 4 2 MiCOM P846 ST...
Страница 78: ...P846 EN OP D Operation MiCOM P846 OP...
Страница 104: ...P846 EN OP D Operation OP 5 26 MiCOM P846 OP...
Страница 106: ...P846 EN AP D Application Notes MiCOM P846 AP...
Страница 108: ...P846 EN AP D Application Notes AP 6 2 MiCOM P846 AP...
Страница 122: ...P846 EN AP D Application Notes AP 6 16 MiCOM P846 AP...
Страница 124: ...P846 EN PL D Programmable Logic MiCOM P846 PL...
Страница 126: ...P846 EN PL D Programmable Logic PL 7 2 MiCOM P846 PL...
Страница 144: ...P846 EN MR D Measurements and Recording MiCOM P846 MR...
Страница 146: ...P846 EN MR D Measurements and Recording MR 8 2 MiCOM P846 MR...
Страница 160: ...P846 EN FD D Firmware Design MiCOM P846 FD...
Страница 182: ...P846 EN CM D Commissioning MiCOM P846 CM...
Страница 228: ...P846 EN CM D Commissioning CM 10 46 MiCOM P846 CM...
Страница 230: ...P846 EN MT D Maintenance MiCOM P846 MT...
Страница 232: ...P846 EN MT D Maintenance MT 11 2 MiCOM P846 MT...
Страница 238: ...P846 EN TS D Troubleshooting MiCOM P846 TS...
Страница 240: ...P846 EN TS D Troubleshooting TS 12 2 MiCOM P846 TS...
Страница 252: ...P846 EN SC D SCADA Communications MiCOM P846 SC...
Страница 272: ...P846 EN SG D Symbols and Glossary MiCOM P846 SG...
Страница 280: ...P846 EN SG D Symbols and Glossary SG 14 8 MiCOM P846 SG...
Страница 282: ...P846 EN IN D Installation MiCOM P846 IN...
Страница 284: ...P846 EN IN D Installation IN 15 2 MiCOM P846 IN...
Страница 293: ...Installation P846 EN IN D MiCOM P846 IN 15 11 7 P846 CASE DIMENSIONS Figure 3 Case dimensions IN...
Страница 295: ...Installation P846 EN IN D MiCOM P846 IN 15 13 P1756ENa IN Figure 5 Model B with 32 output contacts and 24 digital inputs...
Страница 296: ...P846 EN IN D Installation IN 15 14 MiCOM P846 IN...
Страница 297: ......