alre JDS-211 Скачать руководство пользователя страница 16

E32.0.A3.6C-01                    Manual for connection and operation of the JDS-211                        page 16 of 16

Tips for identification of the integral time „1.Int“

     Please set the following values by the configuration of your device:

Set point value “1.SP“: 

desired temperature

Proportional band “1.Pb“:

value identified in chapter A.2

Integral time “1.Int“:

3600

Derivative time “1.dEr“:

0    (off)

Cyclic time “1.CyC“: 

2s  (10s for inert control system)

Derivative time “1.dEr“ is switched off. The device works as PI-controller. Start the control and wait until the
temperature gets to the set point. If this takes too much time shorten the value of “1.Int“. To avoid overshoots
please watch how fast the temperature rises. Is the rise too small, shorten “1.Int“ again. Is the rise already
very big, raise “1.Int“. If “1.Int“ is not too small the temperature should be stable at the set point.
Now there has to be an external interference on the control system (i.e. fill in cold water, put a cold object
onto the controlled metal block, etc.). This interference should be a quite realistic to that under operating
conditions.  If no external interference can be carried out, you can also change the set point value.
Watch how the device regulates the temperature to the set point. If there is a overshoot the “1.Int” value has
to be raised. If the temperature approach the set point only very slowly the “1.Int” value can be shorten.
Please consider to wait the settling time (up to several minutes for some control systems) after each change
of “1.Int”.

Your “1.Int” value is 1.2 times the value identified by that procedure.   

4. Derivative time „1.dEr“

If cold water is filled in a heated water tank the temperate falls rapidly. A human operator, who regulates the
temperature of the tank manually, will intuitively turn immediately the full heating power on, then cut it down to
approach the set point by small changes of the heating power.
The D-action (derivative action) of the PID-controller is responsible for the intervention at that big by big tem-
perature changes. The D-action doesn’t react on the divergence between actual and set point temperature, but
on temperature changes. If the temperature falls very quickly there will be a big heating power due to the D-
action. If the actual temperature approaches the set point very fast the D-action reduces the heating power
calculated by the P- and I-action. If there is no temperature change the D-action is zero.
The strength of this effect is adjusted by the derivative time “1.dEr“. A small “1.dEr“ value means, that there is
only a small reaction on temperature changes. A big one means, that there is a big reaction on changes.
In a lot of application the use of the device as a PI-controller is entirely satisfactory. In this case set the deriva-
tive time “1.dEr“ to 0.
If the PID-control is needed, “1.dEr“ has to be identified. This requires exact information about the controlled
process and knowledge of control engineering. However, a derivative time “1.dEr“=Integral time “1.Int”/5 has
delivered an optimal performance in practice.

Your “1.dEr“ value is 0.2 times the “1.Int“ value.

5. Cyclic time “1.CyC“

The device regulates the heating power by switching the existing heating on and off. If only 50% of the ex-
isting heating power are needed the heating is only half the time switched on. The frequency switching on
and off is adjusted by the cyclic time “1.CyC“.
   Example:   existing heating power 1000 W, 600 W heating power are needed

   At a period time T=10s: the device switches the heating on for 6s and then off for 4s
   At a period time T=200s: the device switches the heating on for 120s and then off for 80s

If the cyclic “1.CyC“ is too high the temperature of the heated object will get too high during the switch-on
period (although „1.SP“, „1.Int“, „1.dEr“ are correct) , only to cool down in the following switch-off period.
A very small “1.CyC“ value means that the relays switches a lot of times and that shortens the durability.
Therefore the cyclic time is ideally set to that value that is as high as possible, but where the effect during the
switch-on and –off periods is just not perceptible.

Tips for identification of the Cyclic time “1.CyC“:

Raise the cyclic time as long as the of the controlling deterioration is just not perceptible.

Your „1.CyC“ is 08. times the value identified by that procedure.  

Содержание JDS-211

Страница 1: ...connection and operation of the JDS 211 page 1 of 16 Manual for connection and operation of JDS 211 item number G800040900 as of version 2 3 Fa ALRE IT Regeltechnik GmbH Richard Tauber Damm 10 D 12277...

Страница 2: ...ntroller with alarm 7 5 1 2 Min Max Alarm getrennt oder gemeinsam 8 5 2 Offset and slope adjustment Menu calling and adjustment 8 6 Operation 9 6 1 Min max value memory 9 6 2 Switching points and alar...

Страница 3: ...The device must be switched off and must be marked against using again in case of obvious malfunc tions of the device which are e g visible damage no prescripted working of the device storing the dev...

Страница 4: ...suggest to connect the device s switching outputs after You have configured the device properly Hint By calling a configuration menu for the offset and slope adjustment the measurement and regulation...

Страница 5: ...hould be connected as 3 wire system too If a 2 wire system is essential the potential deviation can be compensated by the offset adjustment chapter 5 2 Pt100 temperature probe 3 wire Pt100 temperature...

Страница 6: ...ting the adjustment will be cancelled the changing discarded and it will be changed to the parameter view If you don t press any button for more than 60 sec in the menu the menu will be automatically...

Страница 7: ...t C 3point motorised valve control cooling only at 2P 1 SP set point value possible settings min max display range 1 Pb Proportional band possible settings 1 9999 position of the dot depends on displa...

Страница 8: ...e settings min display range AL Hi A dEL alarm delay in sec possible settings 0 9999 When pressing button 1 the display shows outP again Now you have finished the configuration Press now button 4 to e...

Страница 9: ...tching points and alarm boundaries will be called Depending on the configuration you have made in the output configuration menu you will get different display values Please follow the specific chapter...

Страница 10: ...in sec possible settings 0 1 320 0 AL Hi Maximum alarm value possible settings AL Lo max display range AL Lo Minimum alarm value possible settings min display range AL Hi A dEL Delay of the alarm fun...

Страница 11: ...nds The device displays 1 Set 1 SEt manipulating variable in possible settings 0 0 100 0 Depending on the configurated type of control the manual adjustment of the manipulating variable is different P...

Страница 12: ...that the valid display range 9999 digit of the device has been exceeded Err 4 Values below display range Indicates that display value is below the valid display range of the device 1999 digit Err 7 S...

Страница 13: ...dard or the corresponding designation on the label on the housing Nominal temp 25 C Operating ambient 20 to 50 C Relative humidity 0 to 80 RH non condensing Storage temp 30 to 70 C Housing Dimensions...

Страница 14: ...rvene weakly The control gets inert 1 Int Integral time I action Integral time in sec of the PID control algorithms The higher the set value the weaker the effect The control tends to swinging if inte...

Страница 15: ...nt and derivative time 1 dEr are switched off The device works as P controller Start the control and wait until the temperature gets constant This temperature although much below the set point has to...

Страница 16: ...gence between actual and set point temperature but on temperature changes If the temperature falls very quickly there will be a big heating power due to the D action If the actual temperature approach...

Отзывы: