E32.0.A3.6C-01 Manual for connection and operation of the JDS-211 page 10 of 16
“
1.CyC
“
cyclic time in sec
possible settings:: 0,1 ...320,0.
“
2.0n
“
turn-on-point of switching function 2
( only at “
3P
“)
possible settings:: min. ... max. display range
“
2.0ff“
turn-off-point of switching function 2
( only at “
3P
“)
possible settings:: min. ... max. display range
When pressing button 1, the display shows “
1.SP
“ again. Now you have finished the configuration.
Press now button 4 to exit the menu.
6.2.2. 2-point-controller with alarm
This chapter describes how to adjust the switching values of the device used as a 2-point-controller with
alarm. This instruction demands that you selected “
2P.AL
as your desired output function like it is explained
in chapter 5.1. .
By means of
button 1
you
validate
the set parameter or go to the
next parameter
.
By means of
button 2
or
button 3
you
choose
your desired
value
.
By means of
button 4
you
exit
the output configuration menu.
“
1.SP
“
set point value
possible settings: min. ... max. display range
“
1.Pb
“
proportional band
possible settings:: 1...9999 (
position of the dot depends on display range
)
“
1.Int
“
integral time in sec. (I-action)
possible settings:: off, 1...9999.
“
1.dEr“
derivative time in sec. (D-action)
possible settings:: off, 1...9999.
“
1.CyC
“
cyclic time in sec
possible settings:: 0,1 ...320,0.
“
AL.Hi
“
Maximum alarm-value
possible settings: AL.Lo .. max. display range
“
AL.Lo
“
Minimum alarm-value
possible settings: min. display range .. AL.Hi
“
A.dEL
“
Delay of the alarm-function
in sec
possible settings: 0 .. 9999
Example: You want to have a temperature alarm-monitoring of a cold room. The alarm should start when
the temperature rises above -15°C or falls below -30°C. Therefore your settings will be -15°C for
the maximum alarm-value “AL.HI“ and -30°C for the minimum alarm-value “AL.Lo“.
=> The alarm will be starting after the temperature rises above -15°C and stays above -15°C for
the entered delay time or after it had been falling below -30°C and stays below -30°C for the en-
tered delay time.
Please note that the alarm-outputs are inverted! This means, that the output will be active when
there is no alarm!
When pressing button 1, the display shows “
1.SP
“ again. Now you have finished the configuration. Press now
button 4 to exit the menu.
6.2.3.
Minimum/maximum-alarm (individual or common)
This chapter describes how to adjust the device‘s alarm boundaries for min-/max-alarm-monitoring.
This instruction demands that you selected “
AL.F1
“ or “
AL.F2
“ as your desired output function like it is ex-
plained in chapter 5.1.
By means of
button 1
you
validate
the set parameter or go to the
next parameter
.
By means of
button 2
or
button 3
you
choose
your desired
value
.
By means of
button 4
you
exit
the output configuration menu.