36
Alpha Pro Tec - Programming the Boiler PCB
The boiler is supplied with the PCB configuration set according to the boiler model, however it is possible to adjust certain
parameters according to the boiler and system configuration.
Note:
These parameters should only be adjusted by an approved Alpha engineer or Agent.
To access the programming menu, press and hold buttons 'B'
and
'C'
simultaneously. The screen will display the letter P and a corresponding
parameter number and then display the corresponding set value for that
parameter. Scroll through the parameters by using the CH + and – buttons
('1' as shown in Fig. 9.1). To change a parameter value press the DHW +
and – buttons ('2' as shown in Fig. 9.11) to the desired value.
The parameter value is stored by either moving to the next parameter or by
pressing button 'B'.
Exit the parameter menu saving your new settings by pressing the buttons
'B'
and
'C' simultaneously. The boiler will then run a self-diagnostics cycle
displaying PARA and Auto on the screen.
Note:
After approximately 2 minutes the boiler will automatically exit this
menu without saving any changes and running a self-diagnostics cycle displaying PARA and Auto on the screen.
A
B
C
RESET
1
2
Fig. 9.1
9 PROGRAMMING THE BOILER PCB
Parameter
Feature
Description
85
85
5
3
3
4
3
100
0
14
0
20
Pro Tec 50 = 50
Pro Tec 70 = 70
Pro Tech 90 = 90
Pro Tec 115 = 115
0
30
65
5
60
50
0
Set CH flow temp.
Set max. flow temp.
Heating hysteresis (cycling)
Anti cycling time
Stabalisation period
CH ramp up time
Post circulation
Max. heat power output
Min. heat power output
Min. pump flow rate
Anti humidity setting
Not used
Boiler power value
External sensor setting
External sensor offset
DHW set temp.
Not used
DHW reheat temp.
DHW overrun cycle
Max. DHW output power
Min. DHW ouput power
P01
P02
P03
P04
P05
P06
P07
P08
P09
P10
P11
P12
P13
P14
P15
P16
P17
P18
P19
P20
P21
Adjustment
Default value
CH flow temp. range.
Max. flow temp.
Flow temp. differential between cycling.
Time delay between firing to avoid boiler cycling.
Initial stabalisation period at min. rate.
Time to ramp up the CH flow temp. (0 is no ramp up).
Overrun time after CH set temp. is achieved.
Output power according to max. available.
Min. output setting.
Min. flow rate to activate the boiler.
Note:
Do not adjust this
parameter.
Fan speed setting for anti heat exchanger humidity cycle (0 =
disabled, recommended value = 40.
Boiler power information value - software setting for boiler type.
External sensor operating gradient, 0 is disabled.
CH offset in relation to external sensor gradient P14.
Set temp. for DHW when using boiler DHW function.
Temp. differential to reheat DHW function from P16.
Overrun time after DHW set temp. is achieved.
Max. power available during DHW function.
Min. power available during DHW function.
20 - P02 °C
20 - 95°C
2 - 10°C
0 - 15 mins
3 - 10 mins
0 - 60°C
1 - 30 mins
P09 - 10%
0 - P08%
5 - 47 l/min
P26 - 120 RPM x 50
0 - 255 kW
0 - 10
20 - 70°C
20 - 65°C
2 - 10°C
0 - 180 sec
P21 - 100%
0 - P20%
Parameter Programming Menu