11
031-295-B0-001, Rev. B (11/2018)
1.3 Battery Runtime
Table 1-2, XM2-300HP Battery Runtime
1.0 Overview, continued
XM2-300HP 12V (Configured for 60V output)
Power Supply Input Voltage
120V 60Hz
Output Load (A)
1
2
3
4
5
Battery Type
100XTV
Runtime
(minutes,
approximate)*
591
290
181
125
93
150XTV (1 Battery)
860
415
259
180
134
150XTV (2 Batteries)
1218
617
397
283
215
3.5HP
1132
559
354
250
188
4.0HP
1251
607
386
276
213
Power Supply Input Voltage
230V 50Hz
Output Load (A)
1
2
3
4
5
Battery Type
100XTV
Runtime
(minutes,
approximate)*
599
294
185
129
96
150XTV (1 Battery)
872
421
264
185
138
150XTV (2 Batteries)
1840
910
583
415
315
3.5HP
1148
566
361
256
193
4.0HP
1269
615
394
283
218
* Actual runtimes are a function of battery life, equipment loading and environmental conditions.
XM2-300HP 12V (Configured for 90V output)
Power Supply Input Voltage
120V 60Hz
Output Load (A)
1
2
3
Battery Type
100XTV
Runtime
(minutes,
approximate)*
393
182
110
150XTV (1 Battery)
566
261
158
150XTV (2 Batteries)
1211
576
358
3.5HP
754
356
220
4.0HP
826
389
246
* Actual runtimes are a function of battery life, equipment loading and environmental conditions.