![Alpha alphacell gelcell series Скачать руководство пользователя страница 25](http://html1.mh-extra.com/html/alpha/alphacell-gelcell-series/alphacell-gelcell-series_user-manual_2905061025.webp)
25
745-680-C0-002, Rev. B1
6.0 Battery Parameters by Model Number
Parameter
Model Number
220 GOLD-HP
220GxL
195 GOLD-HP
195GxL
Terminal Type
Threaded Insert
Threaded Insert
Threaded Insert
Threaded Insert
Bolt Size
1/4"-20 UNC Bolt
1/4"-20 UNC Bolt
1/4"-20 UNC Bolt
1/4"-20 UNC Bolt
Annual Retorque Inch-Lb / N•m
110In-lb / 12.4N•m 110In-lb / 12.4N•m 110In-lb / 12.4N•m
110In-lb / 12.4N•m
Open Circuit Voltage
12.84
12.84
12.84
12.84
Average Float Voltage Range (volts/unit)
13.5 to 13.8
13.5 to 13.8
13.5 to 13.8
13.5 to 13.8
20-Hour Ampere Rate to 1.75 V/C
5.45
5.45
5.00
5.00
Typical Impedance @ 60Hz ohms
0.0050
0.0050
0.0050
0.0050
Typical Conductance 7Hz mohms
960 to 1400
960 to 1400
880 to 1320
880 to 1320
Typical 10 Sec. Voltage @ 100 amp
11.4
11.4
11.3
11.3
Parameter
Model Number
195GxL FT
165GxL
135AGM-P
85GxL-HP
Terminal Type
16mm Insert
Threaded Insert
Threaded Insert
Threaded Insert
Bolt Size
M6 thread
1/4"-20 UNC Bolt
1/4"-20 UNC Bolt
10-32 UNC Bolt
Annual Retorque Inch-Pounds / N•m
110In-lb / 12.4N•m 110In-lb / 12.4N•m 110In-lb / 12.4N•m
25In-lb / 2.8N•m
Open Circuit Voltage
12.84
12.84
12.84
12.84
Average Float Voltage Range (volts/unit)
13.5 to 13.8
13.5 to 13.8
13.5 to 13.8
13.5 to 13.8
20-Hour Ampere Rate to 1.75 V/C
5.50
4.30
3.75
2.50
Typical Impedance @ 60Hz ohms
0.0050
0.0055
0.0055
0.0040
Typical Conductance 7Hz mohms
800 to 1200
800 to 1200
900 to 1350
480 to 720
Typical 10 Sec. Voltage @ 100 amp
10.8
11.2
11.2
11.6
Table 3, Battery Parameters, Current Models
(threaded insert terminals)
Содержание alphacell gelcell series
Страница 2: ...Power Alpha Technologies...
Страница 30: ...This page intentionally blank...