Alpha alphacell gelcell series Скачать руководство пользователя страница 22

745-680-C0-002, Rev.B1

22

5.0  Battery Symptoms and Solutions

Problem with

Symptom

Possible Causes

Possible Result

Corrective Actions

Capacity Test 

Results

Reduced operat-

ing time at 77°F  

(25°C) with 

smooth voltage 

decline

Normal life cycle

Eventual failure to support the 

load followed by potential for 

shorted cells

Replace battery system 

when at 70% of rated 

capacity or before

Reduced operat-

ing time at 77°F 

(25°C) with steep 

voltage decline or 

voltage plateaus

Individual low capacity cells

Reversed cells during discharge 

Reversed cells will become very 

hot and will not fully recharge

Replace the isolated low 

capacity batteries

Excessive initial 

voltage drop even 

to the point of 

dropping load in 

the first several 

seconds

• 

Battery is extremely cold

• 

Cabling is too small 

gauge

• 

High resistance 

connections

• 

Battery is undersized

• 

Shorted cells

• 

Excessive voltage drop

• 

Cells will become hot, could 

develop thermal runaway; 

internal arcing could result in 

an explosion

• 

Heat the battery

• 

Run parallel cables 

or increase gauge of 

cables

• 

Clean and reassemble 

connections

• 

Add required parallel 

strings

• 

Replace isolated 

units with shorts and 

evaluate entire string

Visual Battery 

Checks

Cover or container 

crack

Handling or impact damage

Cell dryout or ground fault. 

Potential internal gas ignition

Replace damaged unit.

Cover or container 

explosion

Ignition of cell internal gasses 

due to external source, 

fusing, or internal conductive 

path or internal spark due 

to shorting. Potential exists 

for ill-maintained batteries or 

those left in service beyond 

useful life.

• 

Personal injury and equip-

ment damage at time of 

explosion.

• 

Failure to support load.

Replace damaged unit and 

evaluate balance of string.

Burned area on 

container

Crack in container wicking 

electrolyte to grounded rack. 

Ground fault

Could result in 

• 

personal hazard due to 

conductive path to rack

• 

smoke or battery fire

• 

thermal runaway

Clear the ground fault and 

replace defective unit. Evalu-

ate balance of string.

Permanently 

deformed 

(swollen) container

Thermal runaway possible 

caused by high temp., 

environment, overcharging, 

excessively high recharge 

current, shorted cells, ground 

fault, or a combination 

Could result in the emission of 

hydrogen sulfide, detectable as a 

rotten egg odor, battery fire, and 

inability to support the load

Replace the battery system 

and correct the items leading 

to the theramal runaway 

condition

Rotten egg odor

Possible caused by high 

temperatuare environment, 

overcharging, excessively 

high recharge current, shorted 

cells, ground fault, or a 

combination of these.

Odor is a product of thermal 

runaway

Replace the battery system 

and correct items leading to 

thermal runaway condition

Melted grease at 

terminals

Hot connections due to 

excessive resistance caused 

by loose connections, dirty 

contact surfaces or corrosion 

within connection

• 

Excessive voltage drop 

perhaps leading to short 

operating time or damaged 

terminals

• 

In extreme case could lead 

to melted terminal and 

ignition of the battery cover

• 

Clean and reassemble 

connection if damaged

• 

Replace batteries with 

damaged terminals

Corrosion at 

terminals

Possibly electrolyte leaking 

from battery terminal seal 

attacking the interunit 

container

Increased connection resistance 

and resulting increase in the 

connection heating and voltage 

drop at high rate discharge.

Disassemble connection, 

clean, coat connecting 

surfaces and terminal area, 

seal with anti-oxidation 

grease, reassemble the 

connection. If leakage about 

terminal area is obvious, the 

battery should be replaced.

Table 2, Battery Symptoms and Solutions

Содержание alphacell gelcell series

Страница 1: ...AlphaCell GelCell Series AlphaCellTM GelCell Battery Users Guide Storage Maintenance and Deployment Effective April 2013 Alpha Technologies...

Страница 2: ...Power Alpha Technologies...

Страница 3: ...Photographs contained in this manual are for illustrative purposes only These photographs may not match your installation Operator is cautioned to review the drawings and illustrations contained in t...

Страница 4: ...enance Tasks and Schedule 13 3 1 Monthly Remote Status Monitoring 13 3 2 Quarterly Preventive Maintenance 14 3 3 AlphaCellTM Battery Maintenance Log 16 3 4 Battery Evaluation Procedures 18 3 5 Battery...

Страница 5: ...tenance 14 Fig 6 Flow Chart for Battery Refurbishment Plan 19 Fig 7 Charger Modes 21 Table 1 Conductance values new vs suspect batteries 18 Table 2 Battery Symptoms and Solutions 22 Table 3 Battery Pa...

Страница 6: ...ion of this product the following symbols have been placed throughout this manual Where these symbols appear use extra care and attention A WARNING presents safety information to PREVENT INJURY OR DEA...

Страница 7: ...warranty Apply no ox grease on all exposed connections When necessary clean up any spilled electrolyte in accordance with all federal state and local regulations or codes Follow approved storage inst...

Страница 8: ...volt meter prior to any installation or removal procedure Observe circuit polarities Always use the buddy system when working under hazardous conditions Ensure no liquids or wet clothes contact inter...

Страница 9: ...ures Neutralize any spilled battery emission with the special solution contained in an approved spill kit or with a solution of one pound 454g bicarbonate of soda to one gallon 3 8l of water Report a...

Страница 10: ...ctices detailed in this guide will not only insure the battery operates per specifications but also provides the proper backup for the Alpha Powering system in which it is installed To achieve these g...

Страница 11: ...example in Fig 3 two 36V 90Ah capacity strings are connected in parallel to provide a nominal 36V at 180Ah A 12V battery is made up of six 2V cells internally connected to provide 12 volts The batter...

Страница 12: ...e responsible for the status monitoring equipment at the head end or NOC 2 1 Required Tools and Equipment Prior to beginning maintenance ensure that all required tools and equipment including safety e...

Страница 13: ...ery voltage varies more than 0 5V above or below the average for the string then a site visit is required Example V1 13V V2 13V V3 14V Average voltage 13 3V If V3 greater than average by 0 5V then a s...

Страница 14: ...3 Volts of the string average Battery String Float Current 0 5A Log each battery s conductance and voltage Disconnect Batteries Record Information on Site Visit Record Monitor as per PM Program Site...

Страница 15: ...V3 is greater than average by 0 5V then the batteries should be replaced Batteries removed from the site should then be tested per Section 3 5 Battery Refurbishment Plan 4 5 Log the site location batt...

Страница 16: ...3 08 2 70 13 5 1080 A 3 195GXL 4 08 3 08 2 70 13 4 1120 B 1 195GXL 4 08 3 08 1 70 13 4 1090 B 2 195GXL 4 08 3 08 1 70 13 4 1105 B 3 195GXL 4 08 3 08 1 70 13 6 1060 A 1 195GXL 4 08 3 08 7 8 1 85 13 3 1...

Страница 17: ...luation Procedure 2 Evaluation Procedure 3 Vdc Float No Load Conductance mhos 77 F Vdc 24 Hour OCV Conductance mhos 77 F 25 C Vdc 100A after 10 seconds Vdc 24 Hour OCV S t r i n g B a t t e r y T y p...

Страница 18: ...e of the suspected battery 24 hours after the battery has come off of float charge Care must be taken to ensure that the battery is at full state of charge when it is disconnected from the power suppl...

Страница 19: ...in string Measure Conductance Measure Battery Voltage Sort Batteries per Conductance Voltage Batteries Returned from Site Measure and document 24 hour Open Circuit Voltage OCV Must occur within 24 hou...

Страница 20: ...by 17 x 0 0028 V C per degree or 0 048 V C For the 180 cell string this is 41 36 to 42 26 Vdc Under or overcharging If the battery is undercharged for a period of time during which there are multiple...

Страница 21: ...rrent into the batteries becomes less than 0 5A or approximately six hours elapses from the time ACCEPT mode was entered When the batteries are fully recharged the charger switches to the FLOAT mode o...

Страница 22: ...uate balance of string Burned area on container Crack in container wicking electrolyte to grounded rack Ground fault Could result in personal hazard due to conductive path to rack smoke or battery fir...

Страница 23: ...ttery float voltage 14 5 VDC for 6 cell Potentially open cells in individual battery Confirm by checking for zero float current or check for very high impedance of the battery Failure to support load...

Страница 24: ...tery discharged or battery conductive path plate grid or active material or electrolyte volume deterioration Shorted cells Open cells Reduced operating time Conducive to thermal runaway Will not suppo...

Страница 25: ...mohms 960 to 1400 960 to 1400 880 to 1320 880 to 1320 Typical 10 Sec Voltage 100 amp 11 4 11 4 11 3 11 3 Parameter Model Number 195GXL FT 165GXL 135AGM P 85GXL HP Terminal Type 16mm Insert Threaded In...

Страница 26: ...60Hz ohms 0 0050 0 0050 0 0050 0 0050 Typical Conductance 7Hz mohms 960 to 1400 960 to 1400 880 to 1320 880 to 1320 Typical 10 Sec Voltage 100 amp 11 4 11 4 11 3 11 3 Parameter Model Number 210GXL HP...

Страница 27: ...Battery becomes unserviceable due to fire wreckage freezing or any act of God 8 Battery must be used with a temperature compensation charger having characteristic charging curves voltage and current...

Страница 28: ...ver Alloy Pre Dec 2006 5 Years 1 5 Years 4 Years 180 165 GXL Lead Flag Gel Silver Alloy Pre Oct 2005 N A 1 5 Years 3 Years 180 165 G Lead Flag Gel Pre Oct 2005 N A 1 Year 1 Year 210 180 165 GXL 5 Lead...

Страница 29: ...arranty battery claims Record battery float voltage while the battery is still connected to the system Record battery open circuit voltage OCV 24 hours following removal from the system Describe the p...

Страница 30: ...This page intentionally blank...

Страница 31: ...This page intentionally blank...

Страница 32: ...a Technologies GmbH Hansastrasse 8 D 91126 Schwabach Germany Tel 49 9122 79889 0 Fax 49 9122 79889 21 Alphatec Ltd 339 St Andrews St Suite 101 Andrea Chambers P O Box 56468 3307 Limassol Cyprus Tel 35...

Отзывы: