Alpha Alpha CB24 Скачать руководство пользователя страница 16

16

5.3

TEST FOR GAS SOUNDNESS AND PURGE THE SUPPLY

1.

With the boiler gas service cock closed (slot at right angles to valve). Pressure test the gas supply and inlet pipework
connection to the boiler gas service cock for soundness in accordance with BS 6891.

2.

Loosen the gas inlet pressure test point screw on the gas valve (see Fig. 17). Ensure the gas supply is on and open the
boiler service cock to purge in accordance with BS 6891.

3.

Retighten the test point screw and test for gas soundness. Close the boiler gas service cock.

5.4

INITIAL LIGHTING - Refer to Fig. 16

1.

Ensure that the gas and electrical supplies to the boiler are off and that the mains water inlet valve and the central heating
flow and return valves are open.

2.

Turn on the gas and electrical supplies to the boiler.

3.

Ensure all external controls are calling for heat. If the optional Clock is fitted, refer to the User's instructions, set the time
and ensure the Clock is in an 'on' mode.

4.

Set the hot water and central heating temperature selectors to maximum.

5.

Set the selector switch to 

 (DHW only).

6.

Open a hot water tap, the main burner will light and the boiler will provide hot water. Close the tap and the burner will go out.

7.

Set the selector switch to 

 (CH and DHW). The boiler will now run in the central heating mode. The pump will start,

the fan will start; once the pressure switch is proved, the main gas valve solenoid will open allowing the main burner to
light from the ignition electrodes.

5.5

CHECK THE BURNER PRESSURES - Fig. 17

Turn the boiler off. Loosen the burner pressure test point screw on the
gas valve and connect a pressure gauge. Allow the boiler to run for 10
minutes and check the burner pressures.

Hot water mode

1.

Set the selector switch to 

 (DHW only) and fully open a hot water tap.

2.

The burner will light at the ignition rate and the burner pressure will
increase to maximum.

3.

Gradually close the hot tap and check that the burner pressure
decreases to its minimum. Fully open the tap and check that the
burner pressure increases. Close the tap and check that the burner
goes off.
Note: The burner pressure settings have been factory set and do not
require adjusting. If incorrect, check that the inlet gas pressure is 20 mbar.
If the inlet gas pressure is not 20 mbar, either the pipework is too small
or the gas supply to the house is insufficient, in which case contact your gas supplier.

Central heating mode

1.

Set the selector switch to 

 (DHW and CH).

2.

The burner will light at the ignition rate and will increase to the factory pre-set maximum output after 1 minute.

3.

Turn off the boiler. Disconnect the pressure gauge and tighten the test point screw.

Test for gas soundness using suitable leak detection fluid.

Note: Refer to Technical Data, section 2.1 for burner pressure settings.

5.6

FINAL COMMISSIONING

1.

Allow the heating system to heat up, then balance the system to achieve the necessary temperature difference across the
heating flow and return pipes at the boiler and check the system volume and pressure. (Refer to Technical Data, sections
2.2 and 2.8).

2.

Turn off the boiler.

3.

Thoroughly flush out the water pipework and with no pressure in the boiler heating circuit, empty the cyclone at it's drain point
(see Fig. 11) of any debris. Clean the mains water inlet filter (see Fig. 11).

4.

Re-pressurise the system as described in section 5.1.

5.7

FINAL ASSEMBLY

1.

Raise the control panel and secure in position with the screws provided.

2.

If the boiler is to be left in service with the User, set the controls, clock (if fitted, see User's Operating manual) and room
thermostat (if fitted) to the User's requirements.

Alpha CB24/28 - Commissioning

Fig. 17

Содержание Alpha CB24

Страница 1: ...epicar House London Road Wrotham Heath Sevenoaks Kent TN15 7RS For Technical help or for Service call ALPHA HELPLINE Tel 0870 3001 964 Alpha CB24X G C No 47 532 14 Alpha CB24 G C No 47 532 15 Alpha CB...

Страница 2: ...are installed by a competent person ie CORGI registered personnel in accordance with the following recommendations Current Gas Safety Installation and Use Regulations All current Building Regulations...

Страница 3: ...C Rise L min G P M Room sealed chamber panel fitted MAX 34 0 116 000 28 0 95 500 11 7 4 68 3 25 114 8 11 4 2 5 MIN 14 3 48 800 11 2 38 200 2 5 1 0 1 37 48 38 Domestic Hot Water Heat Input kW Gross Btu...

Страница 4: ...Vertical Flue terminal assembly is equivalent to 1 m of flue length 2 8 AVAILABLE PUMP HEAD FOR CENTRAL HEATING gal min 3 7 2 8 2 3 1 8 1 5 Btu h 79 500 60 000 50 000 40 000 31 700 kW 23 3 17 58 14 65...

Страница 5: ...Room sealed chamber 10 Fan 11 Air pressure switch 12 Flue hood 13 Overheat thermostat 14 Expansion vessel Fig 2 15 Automatic air vent 16 Pump 17 Drain point 18 Pressure relief valve 19 Primary pressur...

Страница 6: ...tment The minimum clearances for servicing must always be maintained Note A cupboard or compartment used to enclose the boiler must be designed and constructed specifically for the purpose i e comply...

Страница 7: ...L FLUE OPTIONS Lmax 4 metres L B C E 185 mm Alpha CB24 28 General Boiler Information L B C 185 mm C B E C B E B F B C L B E F 185 mm 90 bend 1 metre L B C 185 mm 2 x 45 bends 1 metre Fig 3 VERTICAL FL...

Страница 8: ...e have access the terminal must be protected by a terminal guard A suitable guard is available from Tower Flue Components Ltd Vale Rise Tonbridge Kent TN9 1TB 3 6 BOILER LOCATION The boiler is not sui...

Страница 9: ...essure cold should be set to 1 0 bar This pressure is equivalent to a static head see Fig 5 of 10 2 metres of water Provision should be made to replace water lost from the system This can be by manual...

Страница 10: ...t operation If the pressure is above 7 bar a pressure reducing valve must be fitted To ensure economic use the pipe runs between the boiler and taps should be in 15 mm copper pipe and be as short as p...

Страница 11: ...B24 28 Installation Fig 10 Fig 9 4 4 FIT THE BOILER Refer to Fig 10 1 Lift the boiler and locate it on the mounting bracket 2 Fit the bottom screws to secure the boiler in position 4 5 CONNECT THE PIP...

Страница 12: ...e 6 Cut both the inner and outer ducts to length Note Do not cut the outer duct end with the two holes these are for securing the terminal Ensure that all cuts are square and burr free 7 Fit the flue...

Страница 13: ...ing it tight against the wall If fitting the collar externally ensure it does not restrict any of the openings of the flue terminal 4 7 FIT A FLUE EXTENSION Figs 12 13 Note 1 The maximum flue assembly...

Страница 14: ...erminal block cover and remove the link between terminals 1 and 2 Pass the cable through the cable clamp and connect it to terminals 1 and 2 Replace the terminal block cover Refer to section 2 9 4 Rep...

Страница 15: ...the exposed spindle about half a turn then replace the cap 6 Check the operation of the pressure relief valve see Fig 2 by turning the head anti clockwise until it clicks The click is the valve liftin...

Страница 16: ...theselectorswitchto DHWonly andfullyopenahotwatertap 2 The burner will light at the ignition rate and the burner pressure will increase to maximum 3 Gradually close the hot tap and check that the burn...

Страница 17: ...en set to it will operate in the Domestic Hot Water and Central Heating mode Note The clock if fitted only controls the operating times of the central heating not domestic hot water DHW is available c...

Страница 18: ...e frequency of servicing will depend upon the particular installation conditions and usage but in general once per year should be adequate It is the law that any service work must be carried out by a...

Страница 19: ...the bottom of the inner case 5 Unscrew and replace any injector that appears damaged 6 Clean the top of the burner with a soft brush and check that the flame ports are clear Blockages may be removed...

Страница 20: ...ng circuit Close the central heating flow and return valves see Fig 11 Connect a suitable pipe to the drain point see Fig 2 and route it to a suitable container Open the drain point 2 Hot water circui...

Страница 21: ...t the boiler as described in Routine Servicing section 7 4 paragraphs 5 to 9 8 8 AIR PRESSURE SWITCH Fig 20 1 Gain access to the combustion chamber as in section 8 1 2 Disconnect the pressure sensing...

Страница 22: ...ly push the valve towards the rear of the boiler take care not to damage the manifold sealing washer and lift out the valve assembly 7 Fit the new assembly and re assemble in reverse order 8 Light the...

Страница 23: ...rear of the control panel 3 Disconnect the wiring from the clock 4 Remove the clock retaining screws and withdraw the clock from the control panel 5 Fit the new clock and connect the wires as follows...

Страница 24: ...heating circuit for primary sensor or hot water circuit for DHW sensor as described in section 8 2 2 Primary Sensor The primary sensor is positioned on the right hand side of the heat exchanger see F...

Страница 25: ...Gain access behind the casing and drain the boiler heating circuit as described in sections 8 1 and 8 2 2 Remove the four screws securing the bottom tray and remove the tray Disconnect the pressure re...

Страница 26: ...e tightening the fixing screws 4 Re assemble in reverse order 8 28 EXPANSION VESSEL Note If there is less than 450 mm clearance above the boiler or a rear exit flue is used it is not possible to repla...

Страница 27: ...27 9 1 ILLUSTRATED WIRING DIAGRAM Alpha CB24 28 Wiring Diagrams 9 WIRING DIAGRAMS...

Страница 28: ...28 Alpha CB24 28 Wiring Diagrams 9 2 FUNCTIONAL FLOW WIRING DIAGRAM...

Страница 29: ...ontinuity Resistance to Earth Short Circuit and Polarity with a suitable meter Note These checks must be repeated after any servicing or fault finding 3 Ensure all external controls are calling for he...

Страница 30: ...30 Alpha CB24 28 Fault Finding 10 3 DOMESTIC HOT WATER Follow operational sequence...

Страница 31: ...31 Alpha CB24 28 Fault Finding 10 4 FAULT FINDING SOLUTIONS A to F...

Страница 32: ...32 Alpha CB24 28 Fault Finding 10 5 FAULT FINDING SOLUTION SECTIONS G to L...

Страница 33: ...r insulation panel set CB24 CB24X Combustion chamber insulation panel set CB28 CB28X Description British Gas GC No E57 720 E57 732 E57 733 E57 733 E57 736 E57 737 E57 739 E57 741 E57 665 E57 666 E76 3...

Страница 34: ...TAILS OF BOILER INSTALLATION Date of Installation Name of Installer Address Postcode Telephone No Boiler Serial Number see data label on inside of left hand case panel DETAILS OF BOILER SERVICE HISTOR...

Страница 35: ...35 Alpha CB24 28...

Страница 36: ...92 These instructions have been carefully prepared but we reserve the right to alter the specification at any time in the interest of product improvement Alpha Therm Limited 2003 Alpha Therm Limited N...

Отзывы: