9400016-J0 Rev D
30
7.2.1 Frame Ground
There are two options for connecting a frame ground to the CXPS-E3, in both cases use 2 AWG cable.
Connection to CXPS-E3 Directly
Connect a cable (matched to maximum size breaker, usually 2 AWG or less) between one of the side panels of the
CXPS-E3 to the master ground bus (MGB) or floor ground bus (FGB). This connection can be made using a 1/4" x
5/8" lug and two 1/4" x 20 bolts into the PEM nuts indicated in the drawing below.
Connection to Overhead Trays
Connect the CXPS-E3 to the frame using rails using 12-24 self-tapping screws. Ensure paint is removed to ensure a
good electrical connection between E3 and frame.
Connect a cable to the frame in which the E3 is installed. The rack upper crossbar (Figure 17) has five 5/8" diameter
holes to accommodate threaded rod attachment to the overhead trays. Connect the frame ground 3/8" in 1" centers
and 1/4" on 5/8" centers. Remove paint in lug contact area to ensure a good electrical connection.
Ground wire
connection points
Ground wire
connection points
Figure 20 — Connecting the Frame Ground to the CXPS-E3
Figure 21 — Connecting the Frame Ground to Overhead Trays
Frame ground 1/4" on 5/8" centers
Frame ground 3/8" in 1" centers
5 x 5/8" diameter holes for connections to
the overhead trays