![Alpha Technologies CXPS-E3 19 Скачать руководство пользователя страница 24](http://html1.mh-extra.com/html/alpha-technologies/cxps-e3-19/cxps-e3-19_technical-manual_2905888024.webp)
23
9400016-J0 Rev D
6.3.1 Installing the batteries
Verify that all battery breakers, DC circuit breakers, and fuses on the distribution panels are either in the OFF position
or removed.
Apply a corrosion-inhibiting agent, such as NO-OX-ID “A”, on all battery terminal connections.
1. If required, assemble the battery rack and the cells or mono-blocks as per the installation instructions supplied
with the batteries.
2. Ensure that the battery output cabling can reach the [+] and [–] terminals of the series battery string and that the
batteries are oriented correctly for easy installation of the inter-unit “series” connectors.
3. Remove any NO-OX-ID “A” grease from battery terminals.
4. Burnish the terminal posts with a non-metallic brush, polishing pad or 3M Scotch Brite scouring pad.
5. Apply a light coating of NO-OX-ID “A” grease to the terminal posts.
6. If lead plated inter-unit connectors are used, they should also be burnished and NO-OX-ID “A” grease applied as
above. Install the inter-unit connectors.
7. After all battery connections are completed, torque the connections as per the battery specifications (typically
100 in-lb).
Refer to the system startup procedure before connecting the batteries online.