background image

Your Power Solutions Partner

Cordex HP LPS04

Installation & Operation Manual

Part # 0120037-J0

 

Effective: 

07/2020

Содержание ALPHA OUTBACK ENERGY Cordex HP LPS04

Страница 1: ...Your Power Solutions Partner Cordex HP LPS04 Installation Operation Manual Part 0120037 J0 Effective 07 2020 ...

Страница 2: ......

Страница 3: ...eserved Alpha is a registered trademark of Alpha Technolo gies No part of this documentation shall be reproduced stored in a retrieval system translated transcribed or transmit ted in any form or by any means manual electric electronic electromechanical chemical optical or otherwise without prior explicit written permission from Alpha Technologies This document the software it describes and the in...

Страница 4: ...4 2 LPS04 Connections and Indicators 9 4 3 Connecting the DC Input 9 5 Site Evaluation and Pre Installation 10 5 1 Pre Installation Requirements 10 5 2 Packing Materials 10 5 3 Check for Damage 11 5 4 General Receipt of Shipment 11 6 LPS04 Installation 12 6 1 General Instructions 12 6 2 Safety Precautions 12 6 3 Tools Required 12 6 4 Mounting 12 6 5 Input and Output Wiring 14 6 6 Input Cables 14 6...

Страница 5: ... Panel or wall mount option A 12 Figure 5 Panel or wall mount option B 12 7 Warranty and Service Information 16 7 1 Technical Support 16 7 2 Warranty Statement 16 7 3 Limited Hardware Warranty 16 7 4 Battery Warranty 16 7 5 Warranty Claims 16 7 6 Service Centers 16 8 Acronyms and Definitions 17 9 Certification 18 ...

Страница 6: ...ath which the information appears CAUTION CAUTION indicates safety information intended to PREVENT DAMAGE to material or equipment Cautions are designated with a yellow warning triangle the word CAUTION and a rule beneath which the information appears WARNING WARNING presents safety information to PREVENT INJURY OR DEATH to personnel Warnings are indicated by a shock hazard icon the word WARNING a...

Страница 7: ...tact with internal components Hazardous electrically live parts inside this unit are energized from the batteries even when the AC input power is disconnected The enclosure which contains the DC or AC power system along with customer installed radios must remain locked at all times except when authorized service personnel are present Always assume electrical connections or conductors are live Turn...

Страница 8: ...tions for the installation of the remote communicating equipment Alpha s LPS04 modular DC to DC converter unit incorporates a full range of standard features including current limiting and individual ground fault interrupt for each circuit Particular emphasis is placed on recognizing a fault con dition and shutting down the circuit as quickly as possible to ensure the highest level of safety Compl...

Страница 9: ... 9kg 6 5lbs Environmental Temperature Operating 40 to 65 C 40 to 149 F Temperature storage 40 to 85 C 40 to 185 F Humidity 0 to 100 RH non condensing Altitude 500 to 2800m 1640 to 9186ft Performance Features Alarm relays 1x Form C Alarm indicating LEDs 1 per channel Channel OK green Recoverable yellow Irrecoverable Fault red Agency Compliance Safety CSA 60950 1 07 ed 2 UL 60950 1 ed 2 CSA 60950 21...

Страница 10: ...ter channel status as follows Table A Converter Status LEDs LED State Converter status Green Normal operation Vout 90 Yellow Recoverable Over temperature Blinking yellow Recoverable OCP Overload Input quality not OK Red Locked State OVP Fuse Fail Blinking red Recoverable GFI OFF No power Input fuse cut off 4 1 2 Module Alarm Relay An alarm is activated after any of the following conditions on any ...

Страница 11: ...ound connection 10 32 ground stud 4 3 Connecting the DC Input WARNING Warning The LPS04 unit shall be permanently connected to the DC mains supply with the supplied power cable A DC breaker shall be used as a disconnect device and shall be rated at 15A DC Grounding The LPS04 unit shall be reliably grounded via a 6 AWG copper inductor at the grounding terminal provided on the LPS04 unit Figure 2 Ca...

Страница 12: ... upstream system using a 5 pin protector to a level corre sponding to a Bourns 2410 Series For example 2410 33 G MSP S provides the part in a red color This protector should be UL 497 listed and rated for 300 400 Volts voltage breakdown range 5 1 4 Installation Locations Allowable installation locations for the LPS04 include the following outdoors direct sunlight and inside or outside a cabinet 5 ...

Страница 13: ...ction for any internal damage In the unlikely event of internal damage inform the carrier and con tact Alpha Technologies for advice on the impact of any damage 5 4 General Receipt of Shipment The inventory included with your shipment depends on the options you have ordered The options are clearly marked on the shipping container labels and bill of materials Call Alpha Technologies if you have any...

Страница 14: ...tion lenses if necessary at all times during installation Use insulated metallic tools The installer should follow all applicable local rules and regulations for electrical and battery installations e g CSA UL CEC NEC OSHA and local fire codes 6 3 Tools Required Various insulated tools are essential for product installation The following list is a guide Phillips head screwdriver 2 tip size 3 16 Sl...

Страница 15: ...ion A MOUNTING ORIENTATION A REMOVE ONLY INDICATED 6300266 HOLE PLUG SCREW S AT THIS ORIENTATION 2 PHILIPS HEAD MOUNTING ORIENTATION B REMOVE ONLY INDICATED 6300266 HOLE PLUG SCREW AT THIS ORIENTATION 2 PHILIPS HEAD Figure 5 Panel or wall mount option B ...

Страница 16: ...n Chassis Ground 6 7 Output Cables Output Cable 24 AWG 12 Conductor 6ft Output Wire Color Circuit Designation Output 1 White Blue 190V_OUT1 Blue 190V_OUT1 Output 2 White Orange 190V_OUT2 Orange 190V_OUT2 Output 3 White Green 190V_OUT3 Green 190V_OUT3 Output 4 White Brown 190V_OUT4 Brown 190V_OUT4 Alarm Blue Red Relay_NC Red Relay_COM Gray Relay_NO White Gray ...

Страница 17: ...ing Yellow Recoverable OCP Overload Ensure the load is within the rated current Recoverable Vout low Check that output is within the regular range Non recoverable Converter Input Fuse fail Potential component failure Replace with new module Red Recoverable OVP OVP will cause the output to restart every 2 seconds until the fault is removed If the fault persists for 60 seconds the output will shut d...

Страница 18: ...e during or after the warranty period No other obligations are expressed or implied Warranty also does not cover damage or equipment failure due to cause s external to the unit including but not limited to environmental conditions water damage power surges or any other external influence The customer is responsible for all shipping and handling charges Where products are covered under warranty AOE...

Страница 19: ...in expressing wire cross sectional area MOV Metal oxide varistor MTBF Mean time between failures NC Normally closed NEC National Electrical Code for the USA NO Normally open OSP Outside plant OVP Over voltage protection RFT circuit Remote feeding telecommunication circuit A secondary circuit within the equipment intended to supply or receive DC power via a telecommunication network at voltages exc...

Страница 20: ...certified to CSA C22 2 No 107 3 and UL 1778 As part of the reciprocal US Canada agreement regarding testing laboratories the Standards Council of Canada Canada s national accreditation body granted Underwriters Laboratories UL authority to certify products for sale in Canada 2 Only Underwriters Laboratories may grant a licence for the use of this mark which indicates compliance with both Canadian ...

Страница 21: ...OUNTING ORIENTATIONS REFER TO SHEET 2 2 NOTES UNLESS OTHERWISE SPECIFIED REFER TO BUBBLE NUMBER IN BILL OF MATERIALS ITEM QTY 142 102 122 303 144 3 306 3 175 5 RECOMMENDED 4X 12 TRI LOBE SCREWS OR BOLTS 4X 12 NARROW TO NORMAL FLAT WASHERS INPUT 18AWG 3 CONDUCTOR WIRE CABLE OUTPUT 24AWG 12 CONDUCTOR WIRE CABLE A 54 2 D DETAIL A 10 32 SERRATED FLANGE NUT FOR EXTERNAL GROUND MOUNT LUG ON TOP OF EXTER...

Страница 22: ...N LPS04 MOUNTING ORIENTATION A REMOVE ONLY INDICATED 6300274 HOLE PLUG SCREW S AT THIS ORIENTATION 2 PHILIPS HEAD MOUNTING ORIENTATION B REMOVE ONLY INDICATED 6300274 HOLE PLUG SCREW AT THIS ORIENTATION 2 PHILIPS HEAD DO NOT SCALE DRAWING 2 4 5 3 1 B E C A D 5 4 3 2 1 E D C B A ...

Страница 23: ......

Страница 24: ...adquarter Germany Hansastrasse 8 D 91126 Schwabach Tel 49 9122 79889 0 Fax 49 9122 79889 21 Mail info alpha outback energy com France and Benelux fbnl alpha outback energy com Spain spain alpha outback energy com For more information please visit www alpha outback energy com Russia russia alpha outback energy com Africa africa alpha outback energy com Eastern Europe ee alpha outback energy com Mid...

Отзывы: