9
0120037-J0 Rev. C
4.2 LPS04 Connections and Indicators
For detailed information on the connections, refer to section 6.5 of this manual.
Input connection: 18 AWG 3-conductor wire cable
Output connection: 24 AWG 12-conductor wire cable
Ground connection: #10-32 ground stud
4.3 Connecting the DC Input
WARNING!
Warning: The LPS04 unit shall be permanently connected to the DC mains supply with
the supplied power cable. A DC breaker shall be used as a disconnect device, and shall
be rated at 15A DC.
Grounding: The LPS04 unit shall be reliably grounded via a #6 AWG copper inductor at
the grounding terminal provided on the LPS04 unit.
Figure 2 — Cable Gauge
Figure 3 — Ground Connection