Page
44
to
52
Problem
Possible cause
Solution
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F42, F43, F44, L42, L43,
L44
INTERNAL PROTECTION
FUSES ON THE
BATTERIES BROKEN
Contact the nearest service centre
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
A13, A14, A15
PROTECTION DEVICE
TRI POWER X33
HETREAM FROM THE
BYPASS LINE OPEN
(ONLY IF BYPASS IS
SEPARATE)
Restore the protection device Tri Power X33
HEtream. WARNING:
check that there is no overload or short circuit at
the output of the TRI POWER X33 HE
BYPASS ISOLATOR
OPEN (SWBYP ONLY IF
BYPASS IS SEPARATE)
Close the isolator located behind the door
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F19, F20
BATTERY CHARGER
FAULT
Open the battery fuse holders (SWBATT) and
insert the maintenance bypass (SWMB), turn the
TRI POWER X33 HE off completely. Turn the TRI
POWER X33 HE back on and if the problem
persists, contact the nearest service centre
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
A26, A27
BATTERY FUSES
BLOWN OR FUSE
HOLDER ISOLATORS
OPEN
Replace the fuses or close the isolators
(SWBATT). WARNING: if necessary, we
recommend fuses be replaced with others of the
same type (see TRI POWER X33 HE internal
protections)
THE DISPLAY SHOWS
THE CODE S06
THE BATTERIES ARE
DISCHARGED; THE TRI
POWER X33 HE
WAITS FOR THE
BATTERY VOLTAGE TO
EXCEED THE SET
THRESHOLD
Wait for the batteries to recharge or force startup
from the “SYSTEM ON” menu
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
F06, F07, F08
INPUT RELAY LOCKED
Activate the maintenance bypass (SWMB), switch
off the TRI POWER X33 HE, open the SWIN and
contact the nearest service centre.
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
L01, L10, L38, L39, L40,
L41
FAULT IN:
TEMPERATURE
PROBE OR TRI
POWER X33 HE
COOLING SYSTEM
MAIN AUXILIARY
POWER SUPPLY
STATIC BYPASS
SWITCH
Activate the maintenance bypass (SWMB), turn the
TRI POWER X33 HE off and back on again.
Exclude the maintenance bypass. If the problem
persists, contact the nearest service centre
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
A22, A23, A24, F23,
L23, L24, L25
THE LOAD APPLIED TO
THE TRI POWER X33 HE
IS TOO HIGH
Reduce the load to below the 100% threshold (or
user threshold for the code A22, A23 or A24)
THE DISPLAY SHOWS
ONE OR MORE OF THE
FOLLOWING CODES:
L26, L27, L28
SHORT CIRCUIT AT
OUTPUT
Switch off the TRI POWER X33 HE.
Disconnect all the devices connected to the phase
concerned by the short circuit.
Turn the TRI POWER X33 HE back on. Reconnect
the devices one by one until the fault is identified.
Содержание Tri Power X33 HE
Страница 1: ...Page 0 to 52 Tri Power X33 HE 30 125KVA User Manual...
Страница 32: ...Page 31 to 52 Menu display...