FUNCTION
DESCRIPTION
DEFAULT
POSSIBLE CONFIGURATIONS
MOD.
Advanced Functions
Input frequency
tolerance
Selects the allowed input
frequency range for
switching to bypass and for
output synchronisation
± 5%
± 0.25%
± 0.5%
± 0.75%
± 1 ÷ ±10 in steps of 1%
SW
Bypass voltage
thresholds
Selects the voltage range
allowed for switching to
bypass
Low:
180V
High:
264V
Low: 180 ÷ 200 in steps of 1V
High: 250 ÷ 264 in steps of 1V
SW
Bypass voltage
thresholds for ECO
Selects the voltage range
allowed for ECO mode
operation
Low:
200V
High:
253V
Low:
180 ÷ 220 in steps of
1V High: 240 ÷ 264 in steps of 1V
SW
Activation
sensitivity for ECO
Selects activation sensitivity
during ECO mode
operation
Normal
Low
Normal
High
CP
Power supply of
load in stand-by
Load on bypass power
supply with TRI POWER
X33 HE off
(stand-by status)
Disabled (load
NOT powered)
Disabled (not powered)
Enabled (
powered
)
SW
Bypass operation
Selects the bypass line
operating mode
Enabled / High
sensitivity
Enabled / High sensitivity
Enabled / Low sensitivity
Disabled with input / output
synchronisation
Disabled without input / output
synchronisation
SW
Inverter
synchronization
(External Sync)
Selects the synchronisation
source for the inverter
output
From bypass
line
From bypass line
From external input
SW
Start-up delay
Waiting time for automatic
restart after the mains
power supply has been
restored
5 sec.
Disabled
1 ÷ 255 in steps of 1 sec.
CP
Power Walk-In
Enables the mode for
gradual return to mains
power
Disabled
Enabled
Disabled
SW
Duration of Power
Walk-In
Sets the duration of the
gradual return to mains
power (only if Power Walk-
in is enabled)
10 sec.
Min.: 1 sec. - Max.: 30 sec.
SW
Speed of
synchronisation
between inverter
and bypass line
Selects the synchronisation
speed between the inverter
and the bypass line
1 Hz/sec
0.5 Hz/sec
1 Hz/sec
1.5 Hz/sec
2 Hz/sec
SW
External
temperature probe
(optional)
Enables reading of the
external temperature probe
Not enabled
Not enabled
Enabled
SW
* Once these output voltage values are set, the TRI POWER X33 HE output power is reduced (see the “Power
reduction for 200V and 208V phase-
neutral loads” paragraph)