5.
Select
User Alarm On
from the
Action #1
drop down menu.
Figure 51
— User Input Configuration: Setting an Action
6.
Click the
Update Configuration
button and enter the password to confirm if required.
7.
Check the
User Input Current Status
at the
UPS Monitoring > User Input Status
page.
Figure 52
— User Input Current Status
Perform a quick test by shorting the User Input 1 to SC (ground) with a short length of PVC insulated electronic
wire. The Alpha FXM should issue a User Input Alarm.
Figure 53
— User Input Current Status
Hovering the cursor over the amber indicator displays the corresponding context sensitive message.
Page
6
4
to
106