RELAY TEMP
55
120/60/N
LINE
7.2.3
Controlling the external fan by temperature triggered dry contact
The Temperature trigger has a user configurable range of +20°C to +55°C (68
– 131°F). When the battery
temperature (monitored by the battery temperature probe) reaches the high temperature threshold, the assigned
relay energizes and can be used to turn on the external fan. The relay is de-energized when the temperature
drops by 10ºC (18ºF). The default high temperature threshold is 55ºC (63ºF).
7.2.3.1
Procedure
From the Logo screen, navigate to
Control Menu
>
RELAY TEMP
. Press the
SELECT
button and the current
temperature display will start flashing. Use the
Scroll
button to change the temperature in 5°C (9ºF) increments.
Press
SELECT
to accept the changes or
CANCEL
to abort.
7.2.4
Making Measurements
The System Status menu lets you make measurements of various Alpha FXM inputs, outputs, temperatures and
other values.
7.2.4.1
Procedure
1.
From the Logo screen go to the SYSTEM STATUS menu.
2.
Press the SELECT button to enter the submenu (Table C).
3.
Press the SCROLL button to move between items in the submenu. When you reach the item you want to
measure, stop pressing the button. The measurement is automatically displayed on the LCD. It is
automatically updated every 0.5 seconds.
Table C
— System Status Menu
LCD display
Meaning
Description
VIN
Input Voltage
The line input voltage into the Alpha FXM
VOUT
Output Voltage
The Alpha FXM output voltage (true RMS).
IOUT AC
Output Current
(AC)
The Alpha FXM AC output current (true RMS).
BATT TEMP
Battery
Temperature
The battery’s temperature (°C).
FREQ IN
Input Frequency
The frequency of line power into the Alpha FXM (Hz).
OUTPUT PWR
Output Power
The Alpha FXM output power in VA (true RMS).
BATT VOLT
Battery Voltage
The battery output voltage (VDC).
CHGR CUR
Charger Current
The Alpha FXM battery charging current is set to this value (Amps).
DATE
Displayed in the format set by the user.
TIME
Displayed in the format set by the user.
INV COUNT
# of line failures
Shows how many times the inverter has been active since the last time
the inverter counter was cleared. See INV RECORD description in Table
B.
Page
4
6
to
106