23
Subject to change without notice | 83056600dUK – Translation of the original operating manual | ait-deutschland GmbH
12.1
Unlock the safety temperature
limiter
A safety temperature limiter is installed in the electric
heating element. If the heat pump fails or there is air in
the system:
► Check whether the Reset button (2) of the safe
-
ty temperature limiter (1) has jumped out (by ap-
prox. 2 mm).
► Press the reset button back in again.
►
If the safety temperature limiter trips again, con-
tact the local partner of the manufacturer or the
factory‘s customer service.
13 Dismantling and Disposal
13.1 Dismantling
Unit is safely disconnected from the power supply
and protected against being switched back on
again.
►
Collect all media safely.
►
Separate components by their materials.
13.2 Disposal and Recycling
►
Dispose of media harmful to the environment
according to local regulations, e.g. antifreeze
mixture, refrigerant.
►
Recycle or ensure proper disposal of unit
components and packaging materials according
to local regulations.
Buffer (standby) battery
1.
Use a screwdriver to push out the buffer battery
on the processor board of the control
2.
Dispose of the buffer battery according to local
regulations.