LIFTING THE UNIT WITH A CRANE
Remove the strips on the sides of the wooden pallet…
Pass the roundslings under the unit. Place lengths
of timber between the roundslings and the unit to
prevent pressure damage to the housing, or dismantle
the facing panels (for dismantling instructions, see
“Attaching the air deflector hoods”)…
A Front view (operating side)
B Side view 1
WARNING!
Roundslings should not be too close together
or too near the middle; otherwise the unit
may tilt or overturn!
ATTENTION
Pass roundslings past the fan on the side. Make sure
that the loaded roundslings do not press against
the fan.
Lift the unit with the crane and place it on the base.
Make sure that the unit's baseframe is in full contact
with the base.
ATTACHING THE AIR DEFLECTOR HOODS
WARNING!
Rotating parts on the unit.
For safety reasons, mount the two air
deflector hoods on the unit before carrying
out any other work.
If you haven't done so already, remove the lower facing
panels from the switch box and water connection side
of the unit…
•
To do this, undo the two quick-release screws in the
lower facing panels…
•
Pull each of the facing panels upwards and outwards,
lift them out of the unit frame and put in a safe place…
1 Lower facing panels
Removing the upper facing panels from the unit…
•
To do this, undo the two screws at the bottom edges
of each of the upper facing panels…
•
Pull each of the facing panels downwards and outwards,
lift them out of the unit cover at the top and put in a