Troubleshooting

12

Pump Alarm- E4 Error Code

**

UNIT WILL NOT FUNCTION UNTIL ERROR CODE IS CLEARED.

If E4 (pump alarm) is shown on the display, complete the following steps:

1. Reset the unit by unplugging the power cord and then reconnecting it.

2. Manually check to see if the pump is operational by pressing the drain button. Check 

if the pump energizes and de-energizes properly. Additionally, check to see if any water 

purged from the system.

3. If you haven’t cleaned the system recently, check the discharge line for an obstruction, 

then clean as described in the Maintenance section.

4. Replace the hose and/or pump, if maintenance alone isn’t sufficient. 

Solution

Cause

Symptom

Poor Connection

Verify

that

both ends of the power cord are 

plugged in

Power Outage

Reset power

Trouble

Code

:

LO

Clean

the

filter

Clear

the

blockage

Filter

is

Dirty

Air

Inlet

or

Outlet

is

Blocked

.

Diaplay is Blank

No

AirFlow

Trouble

Code

:

E4

Trouble

Code

:

E1

Problem with Pump

Room

Temperature

is

below 33

Humidity Sensor or 
Communication Error

Check to ensure that the sensor wire is 
connected at both ends, if no issues are 
visible, the sensor may be faulty.

Verify that the pump is properly installed 
and functioning. If so, unplug the unit for 
two minutes, then restart.

Increase the room temperature so it is 
within operation range (above 33

). If 

error still display, check sensor.

Trouble

Code

:

HI

Room

Temperature

is

above 105

Decrease the room temperature so it is 
within operating range (below 105

). If 

error still displays, check the sensor.

E5

 Trouble

Code

Refrigerant Leak

Contact Your Installer for Assistance.

Содержание Sentinel SLGR 1400X

Страница 1: ...469 Web www alorair com Add 4240 Latham Street Suite D Riverside CA 92501 E mail Sales alorair com Installation Operations Manual Sentinel SLGR 1400X Patent pending Specifications subject to change wi...

Страница 2: ...tration Specifications How it Works Installation Key Functions Indicator Lights Remote Control Operating Instructions Unit Diagram Maintenance Dehumidifier Storage Troubleshooting Spare Parts Warranty...

Страница 3: ...insert objects or your fingers into the inlet or discharge Do not use water to clean the exterior of the dehumidifier To clean unit unplug from power then use a damp cloth to wipe the exterior Do not...

Страница 4: ...will energize Air is then drawn across an evaporator coil which is cooler than the dew point of air This means moisture will condense out of the air The air is then reheated through the condenser coi...

Страница 5: ...n continuously regardless of humidity simply use the down arrow key to set the humidity below 36 4 Key Functions The continuous light will illuminate green and the display will show CO To switch back...

Страница 6: ...is above the setpoint the light will be solid green and the machine will operate If the humidity is below the setpoint the unit will be in standby mode and the light will be flashing 3 Continuous Mod...

Страница 7: ...n Press the on off button and the machine will start running two beeps Press the button again to turn the machine off 2 Up Button Down Button Use the up and down arrows to adjust the humidity level 3...

Страница 8: ...he power button again and the dehumidifier will stop Note that the fan will continue to operate for 1 minute after the unit has shut off The Sentinel SLGR1400X has an integrated condensate pump During...

Страница 9: ...8 Unit Diagram Front View Back View Side Panel Remote Control Control Panel Pre filter Drain Hose Connection Power Cord...

Страница 10: ...drain The pump requires routine maintenance that is not covered by the warranty Preventative maintenance is necessary to prevent issues from dirt and slime that may accumulate in the drain system This...

Страница 11: ...m or towels can be used to remove any remaining water 2 Unplug the dehumidifier and remove the cover so you have access to the pump 3 Remove the pump head from the reservoir by unscrewing the screw Wi...

Страница 12: ...ended period of time complete the following steps 1 Turn off the unit and allow it to dry 2 Complete steps 1 3 in Advanced Pump Cleaning to clean out the pump reservoir 3 Wrap and secure the power cor...

Страница 13: ...rify that both ends of the power cord are plugged in Power Outage Reset power Trouble Code LO Clean the filter Clear the blockage Filter is Dirty Air Inlet or Outlet is Blocked Diaplay is Blank No Air...

Страница 14: ...Board N 102 Alorair RH Temp Sensor Internal Components N 801 N 118 Compressor Compressor Capacitor N 800 Coil Assembly N 119 Hot Gas Valve Assembly N 803 Condensate Pump Assembly Filters External Com...

Страница 15: ...omer is responsible for all risk of loss or damage Alorair Warranty Steps 1 Once receive the goods customers must log in www Alorair com to fill out the warranty Registration form and submit to Alorai...

Страница 16: ...RRANTIES AND LIABILITIES SET FORTH ARE IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR IMPLIED IN LAW OR IN FACT INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR PARTICULAR PURPOSE Alorair...

Отзывы: