● Example M:
● If the previous procedure indicates proper voltage at the top (input)
terminals of the main breaker, test the voltage at the bottom (output) main
breaker terminals (See Example “D” and Example “B”). The meter reading
should indicate 120 volts + 10%. If the reading of 120 Volts +10% is not
measured at each terminal, the main breaker is faulty and must be
replaced. Contact Allmand Parts Department (308-995-4495) for the
correct replacement circuit breaker.