background image

Nite Lite 

V

 Series  

SERIAL NUMBER 39-000001 AND UP 

 
 
 

● Example L:

 

 
 
 
 
 
 
 
 
 
 
 
 
 

10 

Содержание Nite Lite V Series

Страница 1: ...p Sea 1 wire 101070 Fuel Shut Off Solenoid 920751 Electric Fuel Pump 103331 Radiator Kit JB 102910 15 Amp switch lights 106781 SLS Module 108053 Cat 1 1 Parts Auto Shutdown Module 650302 Voltage Regul...

Страница 2: ...ays Unit runs for 45 seconds to 1 minute and shuts down If the unit starts up and runs for 45 seconds to a minute then this indicates the SLS module does not sense A C power from the generator While t...

Страница 3: ...gauge wire connected into the back side of the main breaker Example B below This wire receives 120 volts black to orange wire w 2 amp inline fuse Check power from the black wire through the orange to...

Страница 4: ...Nite Lite V Series SERIAL NUMBER 39 000001 AND UP thein Example B Multiple lights will not Illuminate 4...

Страница 5: ...r cord Once the unit is started the generator should start producing power 120 240 volts There is a 45 second window once started that the system SLS looks for generator voltage from the main breaker...

Страница 6: ...use a smaller Uf Microfarad or different voltage rating for Generators Disconnect Both capacitor leads for the light capacitors Using a screwdriver or similar instrument with an insulated handle shor...

Страница 7: ...and or current may be present when a voltage test is being conducted To reduce the risk of serious injury or death from electrical shock if you are not trained to safely work with high voltage do not...

Страница 8: ...20 volts 10 indicates that the generator may be malfunctioning or that there may be a problem with the main circuit breaker the pop out receptacle circuit breaker the GFCI receptacle itself or the wir...

Страница 9: ...late away from the control panel box Allow the face plate to hang from the attached wiring Caution Do not allow any of the terminals on the control panel faceplate contact the control panel box or any...

Страница 10: ...Nite Lite V Series SERIAL NUMBER 39 000001 AND UP Example L 10...

Страница 11: ...breaker test the voltage at the bottom output main breaker terminals See Example D and Example B The meter reading should indicate 120 volts 10 If the reading of 120 Volts 10 is not measured at each...

Страница 12: ...voltage and or current may be present when a voltage test is being conducted To reduce risk of serious injury or death from electrical shock if you are not trained to safely work with high voltage do...

Страница 13: ...to create the necessary power to operate all of the lamps consistently Example D Note Slow engine speed may be caused by a number of factors a Incorrectly adjust engine governor Adjust governor as sh...

Страница 14: ...ery Go to the Ignition and open up the panel behind This will expose the SLS Module and relay block In the relay block look for the 15 amp fuse 105844 and ensure this fuse is good If bad then replace...

Страница 15: ...UP into terminal R From terminal R the connection must be ran into Engine harness 5 pin Ensure contact is being made Example R see next page for wiring instructions Example R Filters per Engine optio...

Страница 16: ...1 Every 500 hours Perkins 403F 11 Every 500 hours 16 FUEL 108430 FILTER KIT ALL FUEL 108963 KUBOTA D905 D1005 D1105 8KW AIR 650290 OIL 920743 FUEL 920745 FILTER KIT ALL FUEL 108962 PERKINS 403F 11 8KW...

Страница 17: ...Check engine operators manual for specific recommended lubricants Additional warranty information claim forms can be obtained on Allmand com Please contact Allmand Tech line for additional help and t...

Отзывы: