background image

Page 4  of  16

506941-01

Issue 1148

NOTE:

   

If a gas furnace that’s connected to a common 

venting system is being removed when this package unit 
is installed, then read and follow the instructions in the 
“Removal of Unit from Common Venting System” section 
that follows.  Otherwise, you may skip this section.

Removal of Unit from Common Venting System

When an existing furnace is removed from a common venting 
system serving other appliances, the venting system is likely 
to be too large to properly vent the remaining attached 
appliances.  The following test should be conducted with 
each appliance while the other appliances connected to the 
common venting system are not in operation.

1.  Seal any unused openings in the common venting 

system.

2.  Visually inspect the venting system for proper size and 

horizontal pitch and determine there is no blockage or 
restriction, leakage, corrosion, or other defi ciencies 
which could cause an unsafe condition.

3.  Insofar as is practical, close all building doors and 

windows between the space in which the appliances 
remaining connected to the common venting system 
are located and other spaces in the building.  Turn on 
clothes dryers and any appliance not connected to the 
common venting system.  Turn on exhaust fans, such 
as range hoods and bathroom exhausts, so they will 
operate at maximum speed.  Do not operate a summer 
exhaust fan.  Close fi replace dampers.

4.  Following the lighting instructions, place the unit being 

inspected in operation.  Adjust the thermostat so the 
appliance will operate continuously.

5.  Test for spillage at the draft control relief opening after 

5 minutes of main burner operation.  Use the fl ame of 
a match or candle.

6.  Follow the preceding steps for each appliance 

connected to the common venting system.

7.  After it has been determined that each appliance 

remaining connected to the common venting system 
properly vents when tested as outlined above, return 
doors, windows, exhaust fans, fireplace dampers, 
and any other fuel burning appliance to their previous 
condition of use.

 
8.  If improper venting is observed during any of the above 

tests, the common venting system must be corrected. 
See National Fuel Gas Code, ANSI Z223.1 (latest 
edition) or CAN/CGA B149.1 & .2 Canadian Installation 
Codes

 

to correct improper operation of common venting 

system.

Minimum horizontal clearance of 4’ (ft.) from electric meters, 
gas meters, regulator, and relief equipment is required.

In addition to the above requirements, consideration must 
be given to prevent unwanted ice buildup from the vent 
condensate.  The vent should not be located on the side of 
a building where the prevailing winter winds could trap the 
moisture, causing it to freeze on the walls or on overhangs 
(under eaves).   The vent location should not discharge over 
a sidewalk, patio, or other walkway where the condensate 
could cause the surface to become slippery.

The products of combustion must not be allowed to 
accumulate within a confi ned space and recirculate.

Vent Cover

For shipping purposes, the unit is shipped with the vent cover 
packaged in the unit supply air compartment.  Retrieve the 
vent cover from the supply air compartment. 

To attach the vent cover to the unit:

1.  Locate the vent screen. It is packed in the plastic bag 

that contains these Installation Instructions.

2.  Remove the two screws that will be used to attach the 

screen to the unit (see Figure 4).

3.  Center the screen over the hole and re-insert the screws 

removed in Step 2.

4.  Remove the 4 screws that will be used to attach the 

vent cover (see Figure 4).  Install the vent cover using 
these screws.  A properly installed vent cover will not 
extend above the top of the unit.

Installing the Vent Cover

Figure 4

Screen

Screen attachment screws

Vent Cover

Vent Cover
Attachment
Screws
(Plus 2 on 
other side)

Содержание RGE Series

Страница 1: ...d home application the ductwork must be sized to achieve static pressures within the manufacturer s guidelines All other installation guidelines must also be followed Failure to do so may result in equipment damage personal injury and improper performance of the unit WARNING Never use a flame to check for gas leaks Explosion causing injury or death may occur WARNING Do not store combustible materi...

Страница 2: ...a forklift while still in the factory supplied packaging The lengths of the forks of the forklift must be a minimum of 42 Inspection As soon as the unit is received it should be inspected for possible damage during transit If damage is evident the extent of the damage should be noted on the carrier s freight bill A separate request for inspection by the carrier s agent should be made in writing Lo...

Страница 3: ...f a roof curb is used follow the manufacturer s Installation Instructions and be sure that all required clearances are observed see Clearances section on this page This unit is shipped with four 4 corner brackets in place on the underside of the unit see Figure 1 All four 4 brackets must be removed before unit is installed onto roof curb assembly To avoid interference with roof curb remove the out...

Страница 4: ...termined that each appliance remaining connected to the common venting system properly vents when tested as outlined above return doors windows exhaust fans fireplace dampers and any other fuel burning appliance to their previous condition of use 8 If improper venting is observed during any of the above tests the common venting system must be corrected See National Fuel Gas Code ANSI Z223 1 latest...

Страница 5: ... Air Conditioning Contractors of America ACCA A closed return duct system shall be used This shall not preclude use of economizers or outdoor fresh air intake It is recommended that supply and return duct connections at the unit be made with flexible joints The supply and return air duct systems should be designed for the CFM and static requirements of the job They should not be sized by matching ...

Страница 6: ...parate line and installed in accordance with all safety codes listed on page 1 After the gas connections have been completed open the main shutoff valve admitting normal gas pressure to the mains Check all joints for leaks with soapy solution or other material suitable for the purpose Never use a flame to check for gas leaks Explosion causing injury or death may occur WARNING The furnace must be i...

Страница 7: ...most regulator manufacturers and LPG propane gas suppliers Check all connections for leaks when piping is completed using a soapy solution Some soaps used for leak detection are corrosive to certain metals Carefully rinse piping thoroughly after completing leak detection Electrical Wiring See Figures 6 7 All wiring should be done in accordance with the National Electrical Code ANSI NFPANo 70 lates...

Страница 8: ... At no time should the standby gas pressure exceed 13 w c nor the operation pressure drop below 5 w c for natural gas units or 11 w c for propane gas If gas pressure is outside these limits contact the gas supplier for corrective action 4 Adjust temperature rise to be within the range specified on the raƟng plate To Light Main Burners 1 Turn off electrical power to unit 2 Turn the thermostat to lo...

Страница 9: ... d To Reassemble Reverse above steps Example The heating value of the gas is 1053 BTU cubic foot By actual measurement it takes 38 seconds for the hand on the 1 cubic foot dial to make a revolution with a 100 000 BTU HR furnace running The result is 99 750 BTU HR which is close to the 100 000 BTU HR rating of the furnace Manifold Gas Pressure Adjustment Regulator LPG Propane Gas LPG propane units ...

Страница 10: ...nnected open the main manual gas shutoff valve check for and correct any gas leaks Turn electrical power on initiate a call for heat and check for proper burner operation 8 Install burner access panel Heat Anticipator The heat anticipator setting is 0 75 amp It is important that the anticipator setpoint be correct Too high of a setting will result in longer heat cycles and a greater temperature sw...

Страница 11: ...pre purge period 30 seconds nominal 3 When the pre purge period has expired the ignition control energizes the main gas valve and spark electrode for a period of 10 seconds 4 If the flame sensor does not sense that a flame has been established in the 10 second interval then the ignition control will de energize the gas valve and begins a 30 second interpurge period then initiates another trial for...

Страница 12: ...box Carefully remove the flue collector box without ripping the adjacent insulation 4 Using a wire brush on a flexible wand brush out the inside of each heat exchanger from the burner inlet and flue outlet ends 5 Run the wire brush down the heat exchanger tubes from the burner end 6 Brush out the inside of the flue collector box 7 Clean the combustion air blower wheel and housing Run the wire brus...

Страница 13: ...506941 01 Page 13 of 16 Issue 1148 CONNECTION DIAGRAM SINGLE STAGE HEAT 230 V 3 PHASE Figure 10 ...

Страница 14: ...Page 14 of 16 506941 01 Issue 1148 CONNECTION DIAGRAM SINGLE STAGE HEAT 460 V 3 PHASE Figure 11 ...

Страница 15: ... All applications Ten 10 years LF24 and TUA Stainless All applications Fifteen 15 years LD24 Aluminized All applications Two 2 years LD24 Stainless All applications Five 5 years LG14 All applications Five 5 years Burners LG14 Three 3 years Compressors 4SCU13LC 4SHP13LC Five 5 years TSA TPA Five 5 years KCA KGA KHA TCA TGA THA Five 5 years RGE13 RHP13 RCE13 Five 5 years NOTE If the date of original...

Страница 16: ...omponents indoor unit outdoor unit and re frigerant control devices which do not match or meet the specifica tions recommended by the manufacturer e Operation of packaged gas electric units equipped with aluminized heat exchanger with mixed air temperatures of less than 45 F 7 C f Operation of furnaces with return air temperatures of less than 60 F 16 C or operation of a furnace field installed do...

Отзывы:

Похожие инструкции для RGE Series